Fig. SGS 28 to 60 - CO
2
adjustment (partial load)
IMD-1095c R0
Fig. SGS 80 to 120 - CO
2
adjustment (partial load)
IMD-1097b R0
Note
Turning to the left (anticlockwise) means more less (lower CO
2
level) and turning to the
right (clockwise) means more gas (higher CO
2
level).
Note
After conversion, you must check that the gas control valve is gastight.
Remove the CO
2
measurement probe from the measurement nipple of the flue gas
outlet pipe.
Put the cap back on the measurement nipple of the flue gas outlet pipe.
Shut off the gas supply.
Replace the covers.
7.9.5
Switching pressure measurement
To measure the switching pressure, proceed as follows:
Isolate the appliance from the power supply (see section 4.2.2).
Carefully remove the covers from the appliance.
The electrical section is now visible.
Remove the black caps from the measurement point of the pressure switch.
Connect the + of the pressure gauge to the H of the measurement point of the
pressure switch.
Connect the - of the pressure gauge to the L of the measurement point of the
pressure switch.
Zero the pressure gauge.
n
23.
24.
25.
26.
1.
2.
3.
4.
5.
6.
7.
0311753_SGS_28-120_II_UKUK_V2.0 , 2017-05-03
77
Summary of Contents for SGS-28
Page 6: ...6 ...
Page 13: ...User part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 40: ...40 User part ...
Page 41: ...Installation Maintenance and Service part 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 41 ...
Page 42: ...42 User part ...
Page 82: ...82 Installation Maintenance and Service part ...
Page 90: ...90 Installation Maintenance and Service part ...
Page 104: ...104 Installation Maintenance and Service part ...
Page 110: ...Fig Dimensions SGS 28 30 50 60 110 Installation Maintenance and Service part ...
Page 112: ...Fig Dimensions SGS 80 100 120 112 Installation Maintenance and Service part ...
Page 121: ...12 8 Declaration of conformity 0311753_SGS_28 120_II_UKUK_V2 0 2017 05 03 121 ...
Page 124: ...124 Installation Maintenance and Service part ...
Page 126: ...126 Installation Maintenance and Service part ...