Parameter Description
Unit/Value Adjustable Range
Default
270
Last lock-out error
#
No
C02
…
S14
---
- no error
-
271
Interval between last lock-out
and read-out.
Minutes
Hours
Days
Weeks
No
00n
...
59n
= 0 till 59 minutes
01h
...
23h
= 1 till 23 hours
01d
...
06d
= 1 till 6 days
01
...
63
= 1 till 63 weeks
-
272
Last blocking error
#
No
C02
…
S14
---
- no error
-
273
Interval between last blocking
error and read-out.
Minutes
Hours
Days
Weeks
No
00n
...
59n
= 0 till 59 minutes
01h
...
23h
= 1 till 23 hours
01d
...
06d
= 1 till 6 days
01
...
63
= 1 till 63 weeks
-
274
Number of flame failures
#
No
0
…
990
-
275
Number of successful ignitions
×100
No
0
…
990
-
276
Number of failed ignitions
#
No
0
…
990
-
277
Total of actual days that control
is active
×10 days
No
0
…
990
-
278
Total of actual burning days
×10 days
No
0
…
990
-
281
Selection code
#
No
0
…
990
-
1 - The maximal setpoint (parameter
207
) is factory set at
70
. A qualified engineer can modify this
value.
2 - Parameter
005
will only be accessible when parameter
004
is set on
ENA
.
Note
When parameter
202
is set to
Off
, the anode warning
Ano
will not be shown on the
display. Also when there is a problem with the anode protection, this warning will not be
shown. The tank protection cannot be guaranteed. The warranty will be void.
10.3
Hysteresis
The water heater does not start immediately when the water temperature is below the
temperature setpoint. To prevent that the water heater switches on and off too often,
there is a margin; the hysteresis.
The standard hysteresis is 10 °C. Thus, the water heater starts to heat up when the water
temperature is 10 °C below the temperature setpoint. Use parameter
003
to change the
hysteresis.
n
0312266_INNOVO_UKUK_
V5.1, 2022-07-12
61
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...