Calculate the maximum length of the air inlet and the flue gas outlet seperately:
1.
Sum the lengths of the different pipe sections without bends. Ignore the length of
the adaptor box.
2.
Sum the lengths of the bends. Ignore the bend in the adapter box:
-
Sum L
equivalent
for each 45° bend.
-
Sum L
equivalent
for each 90° bend.
3.
Sum the lengths of the pipe sections and the lengths of the bends to calculate the
overall length of the air inlet and the flue gas outlet.
4.
Adjust the length of the air inlet and/or the flue gas outlet when the overall length
exceeds the maximum length as stated in the table.
8.7.3
C43/C53/C63 systems
The length of the air inlet and flue gas outlet is the same for C43, C53 and C63 systems as
for C13 and C33 systems:
•
Refer to C13/C33 concentric systems (see 8.7.1) for the maximum pipe lengths of
concentric systems.
•
Refer to C13/C33 parallel systems (see 8.7.2) for the maximum pipe lengths of
parallel systems and non-concentric systems.
Note
Only use a C43 venting system when the common duct is a natural draught chimney. The
common duct is part of the building, not a part of the system.
Note
In a C53 venting system the flue gas terminal must be CE approved and must comply to
the EN 1856-1 requirements.
Note
Connect a C63 venting system to a separately approved and marketed system for the
supply of combustion air and discharge of flue gasses.
The flue gas terminal must comply to the EN 1856-1 requirements. The maximum
allowable recirculation rate is 10% under wind conditions.
Contact A.O. Smith for more information and/or part numbers of the C43, C53 and C63
venting systems.
Concentric systems
Refer to the table for the correct pipe dimensions of the C43, C53 and C63 concentric
systems.
Description
Venting material
PP
Venting material
Alu
Manufacture venting material Muelink & Grol
Muelink & Grol
Construction
Concentric
Concentric
Material flue gas outlet
PP - Temp. Class T120 Thick walled aluminum
Material air inlet
Thin walled galvanized
steel
Thin walled galvanized
steel
Diameter flue gas outlet
80
+0,6
/
-0,6
mm
80
+0,3
/
-0,7
mm
Diameter air inlet
124
+0,5
/
-1
mm
(Dn 125)
124
+0,5
/
-1
mm
(Dn 125)
Refer to C13/C33 concentric systems (see 8.7.1) for the A.O. Smith part numbers. The
same parts can be used for the C43, C53 and C63 concentric systems.
n
0312266_INNOVO_UKUK_
V5.1, 2022-07-12
47
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...