The user menu parameters are:
Parameter Description
Unit/Value Adjustable Range
Default
001
Turn the water heater on or off.
OFF
ON
Yes
OFF
- water heater off (OFF
mode)
ON
- water heater on (ON
mode)
OFF
002
Setpoint ON mode
ºC
Yes
40
…max setpoint
(1)
65
003
Hysteresis
ºC
Yes
2
…
15
10
004
Turn setpoint EXT mode (
005
)
on or off.
ENA
dIS
Yes
ENA
- Enable
dIS
- Disable
dIS
005
(2)
Setpoint EXT mode
ºC
Yes
40
…max. setpoint
(1)
70
1 - The maximal setpoint (parameter
207
) is factory set at
70
. A qualified engineer can modify this
value.
2 - Parameter
005
will only be accessible when parameter
004
is set on
ENA
.
3.2
Status of the water heater
During operation, the display shows the status of the water heater.
3.2.1
Operating modes
The Innovo has 3 operating modes:
•
OFF mode (see 3.2.1.1)
•
ON mode (see 3.2.1.2)
•
External ON mode (EXT mode) (see 3.2.1.3)
3.2.1.1 OFF mode
Use parameter
001
to switch the water heater to OFF mode.
In the OFF mode the water heater is de-activated. The display shows the characters
OFF
.
Fig. OFF mode display
Fig. Frost protection is activated
To prevent that the water in the system freezes, the frost protection is activated when the
water heater is in OFF mode. The frost protection starts when the temperature of the
water drops below 5°C. The display shows the frost protection symbol.The water heater
will heat the water to 20°C and then turns back to OFF mode.
3.2.1.2 ON mode
Use parameter
001
to switch the water heater to ON mode.
In the ON mode the water heater continuously responds to the heat demand.
When the water heater is heating the water, the display on the operator interface
alternately shows two different screens. The first shows the actual temperature, the
second shows the setpoint temperature.
When the water heater is not heating the water, only the actual temperature is visible. The
symbols Heat demand and In operation will not be shown.
0312266_INNOVO_UKUK_
V5.1, 2022-07-12
21
Summary of Contents for Innovo IR 12-160
Page 6: ...6 ...
Page 13: ...User part 0312266_INNOVO_UKUK_V5 1 2022 07 12 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 27: ...Installation Maintenance and Service part 0312266_INNOVO_UKUK_V5 1 2022 07 12 27 ...
Page 28: ...28 User part ...
Page 36: ...36 Installation Maintenance and Service part ...
Page 56: ...56 Installation Maintenance and Service part ...
Page 58: ...58 Installation Maintenance and Service part ...
Page 70: ...70 Installation Maintenance and Service part ...
Page 83: ...0312266_INNOVO_UKUK_V5 1 2022 07 12 83 ...
Page 87: ...13 4 Electrical wiring diagram 0312266_INNOVO_UKUK_V5 1 2022 07 12 87 ...
Page 89: ...13 5 Declaration of conformity 0312266_INNOVO_UKUK_V5 1 2022 07 12 89 ...
Page 90: ......
Page 91: ......
Page 94: ...92 Installation Maintenance and Service part ...