Fig. Gas supply pressure
4
1
3
2
1. Adjuster screw
2. Gas control valve
3. Gas supply pipe
4. Sealing screw
8.9.4
CO
2
value
Check the CO
2
value:
Open the gas supply.
Remove the cap (1) from the test nipple (2) of the flue gas outlet pipe.
Place the measurement probe of the CO
2
meter in the test nipple of the flue gas
outlet pipe.
Turn on the water heater, refer to Turn on the water heater (see section 4.2).
Set parameter
201
to
Hi
, refer to Settings (see section 10).
1.
2.
3.
4.
5.
54