REFER TO FIG. 1 FOR CONNECTION DETAILS.  BEFORE
ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS
CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG)
MUST BE INCORPORATED IN THE PIPING, FIG. 1.

  The dirt leg

must be readily accessible.  Install in accordance with
recommendations of serving gas supplier.  Refer to the latest
edition of ANSI Z223.1.

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to thermostat gas inlet.
The thermostat inlet has a pad for use with a backup wrench.

Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints.  Do not apply compound to the first
two threads.  Use compounds resistant to the action of liquefied
petroleum gases.  Do not use teflon tape on thermostat fittings.

CONNECTION OF GAS PIPE

1. When connecting gas pipe to unit, apply wrench to flange

only.  Note:  Do not use wrench on gas valve or gas valve
bracket.

2. PERFORM THE GAS LEAK TEST ANY TIME WORK IS DONE

ON A GAS SYSTEM TO AVOID THE POSSIBILITY OF FIRE OR
EXPLOSION WITH PROPERTY DAMAGE, PERSONAL
INJURY, OR LOSS OF LIFE.

The Gas Leak Test is performed as follows:  Paint pipe
connections upstream of gas control with a rich soap and
water solution to test for leaks before operating main burner.
Bubbles indicate gas leak.  To stop leak, tighten pipe
connections.  After piping connections are checked, turn on
main burner.  (See Lighting and Operating Installations in
this manual or on water heater.)  With main burner in operation,
paint pipe joints (including flanges) and control inlet and outlet
with rich soap and water solution.  Bubbles indicate gas leak.

To stop leak, tighten flange screws, joints and pipe
connections.  Replace part if leak can't be stopped.

DISCONNECT THE APPLIANCE AND ITS INDIVIDUAL SHUT
OFF VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING
ANY SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSI (3.5
kPa).  GAS SUPPLY LINE MUST BE CAPPED WHEN
DISCONNECTED FROM THE HEATER.  FOR TEST
PRESSURES AT 1/2 PSI (3.5 kPa) OR LESS, THE APPLIANCE
NEED NOT BE DISCONNECTED, BUT MUST BE ISOLATED
FROM THE SUPPLY PRESSURE TEST BY CLOSING THE MAIN
MANUAL GAS VALVE.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE.  USE SOAP AND WATER SOLUTION OR OTHER
MATERIAL ACCEPTABLE FOR THIS PURPOSE. DO NOT USE
MATCHES CANDLES, FLAME OR OTHER SOURCES OF
IGNITION TO LOCATE GAS LEAKS.

RELIEF VALVE

A NEW TEMPERATURE AND PRESSURE RELIEF VALVE
COMPLYING WITH THE STANDARD FOR RELIEF VALVES AND
AUTOMATIC GAS SHUT OFF DEVICES FOR HOT WATER
SUPPLY SYSTEMS, ANSI Z21.22 (LATEST EDITION) MUST BE
INSTALLED IN THE HEATER IN THE MARKED OPENING
PROVIDED.  THE VALVE MUST BE OF A SIZE (INPUT RATING)
THAT WILL BE ADEQUATE FOR YOUR SIZE HEATER.

Check the metal tag on the relief valve and compare it to the
heater’s rating plate.  The pressure rating of relief valve must not
exceed the working pressure shown on the rating plate of the
heater.  In addition the hourly Btu rated temperature steam
discharge capacity of the relief valve shall not be less than the
input rating of the heater. 

 NO VALVE IS TO BE PLACED

FIGURE 3

 WARNING

VENT HOOD(S) MAY BE

EXTREMELY HOT

DURING OPERATION.

Summary of Contents for GPS-75

Page 1: ...as well as the WARNINGS and CAUTIONS CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE INSTALLINGAND USING THISAPPLIANCE GAS WATER HEA...

Page 2: ...manufacturer by calling 1 800 821 2017 When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired as listed in fig 1 Standard hardware items may b...

Page 3: ...to find the cause yourself Go to a neighbor s house leaving your doors open to ventilate the house then call your gas supplier or service agent Keep area clear until a service call has been made At ti...

Page 4: ...e clearance for servicing this appliance should be considered before installation such as changing the anodes etc Minimum clearances for proper operation are given above WARNING In cold climates provi...

Page 5: ...micals such as those used for boiler treatment shall NEVER be introduced into this system 3 This unit may NEVER be connected to any existing heating system or component s previously used with a non po...

Page 6: ...ns in this manual or on water heater With main burner in operation paint pipe joints including flanges and control inlet and outlet with rich soap and water solution Bubbles indicate gas leak To stop...

Page 7: ...ower vented appliances are classified by building codes as vent connectors Required clearances from combustible materials must be provided in accordance with information in this manual under LOCATION...

Page 8: ...to the built in drain port of the rubber boot on the blower assembly For your convenience the rubber boot is supplied with a removable cap on the built in drain port Prior to operating the water heat...

Page 9: ...enclosure E Splice field wiring into existing wiring using code authorized method wire nuts etc F Be certain that neutral and line connections are not reversed when making these connections G Ground h...

Page 10: ...be supported every 5 feet of vertical run and every 3 feet of horizontal run All piping and fittings must be joined by the proper procedures as described under VENT PIPE PREPARATION FIGURE9 IMPORTANT...

Page 11: ...type of cutter is used the flare on the end must be completely removed STEP A NOTE Power saws should be specifically designed to cut plastic pipe B Deburring Use a knife plastic pipe deburring tool or...

Page 12: ...ld not be disturbed immediately after the cementing procedure and sufficient time should be allowed for proper curing of the joint Exact drying time is difficult to predict because it depends on varia...

Page 13: ...LER and HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Tur...

Page 14: ...temperature settings to reduce scald hazards Valves for reducing the point of use temperature by mixing cold and hot water are available See figure 2 Also available are inexpensive devices that attac...

Page 15: ...t if necessary to keep burner in operation C CHECKINGTHE DRAFT Operate the water heater for several minutes and check to see if it is venting properly by passing a lit match or paper near the opening...

Page 16: ...d above If you are having a problem with your water heater before calling for service please refer to the following TROUBLESHOOTING sections If service becomes necessary contact your dealer installer...

Page 17: ...lower back into 115 vac outlet Repair service to outlet Replace switch Replace control harness Replace blower and motor Replace switch Check for low voltage less than 102 vac have service checked and...

Page 18: ...water heater off for 10 seconds and then back on 2 Replace gas control valve Problem with the internal circuit 1 Turn power to the water heater off for 10 seconds and then back on 2 Replace gas contr...

Page 19: ...NDLABORRESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLYAREPLACEMENTWATERHEATERORPARTTHEREOF THEOWNER IS RESPONSIBLE FOR ALLOTHER COSTS Such costs may include but are not limi...

Page 20: ...20 A O SMITH WATER PRODUCTS CO INC 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 1 800 821 2017 Website www hotwater com...

Reviews: