Flue systems Cyclone BFC

Installation options

B23

C13

C33

C53

C43

A Cyclone BFC water heater should be installed according  
category B23, C13, C33, C43 or C53*.  

Concentric

Diameter (mm) 

80/125 

100/150  100/150  100/150  130/200  130/200

Max. length (m) 

40  

40  

40  

15  

15  

15 

Max. 45/90° bends 

3

Parallel (standard diameter)

Diameter (mm) 

80 

100 

100 

100 

130 

130

Max. length (m) 

25  

80  

45  

25  

115  

60 

L

equivalent

/bend 90° (m)  3,9  

4,6  

4,6  

4,6  

2,4  

2,4

L

equivalent

/bend 45º (m)  1,1  

1,2  

1,2  

1,2  

1,4  

1,4 

Parallel (larger diameter for more length)

Diameter (mm) 

100 

130 

130 

130 

150 

150

Max. length (m) 

100 

100 

100 

100 

100 

100

L

equivalent

/bend 90º (m)  4,6  

2,4  

2,4  

2,4  

2,6  

2,6 

L

equivalent

/bend 45º (m)  1,2  

1,4  

1,4  

1,4  

1,6  

1,6 

*   All Cyclone BFC are also approved for installations where the unit is supplied 
  without venting materials (C63).

Concentric flues

It is 

not

 permitted to use more than the specified number of 

bends, even when the duct is shorter than the maximum 
length. A 45° bend is equivalent to a 90° bend.

Parallel flues

-  The maximum permissible length should be reduced by the 
  equivalent length of each bend. (Note: for a parallel installation 
  this means that 3 changes in direction amount to 6 bends 
  (3 in the supply duct and 3 in the flue). 
-   The maximum length also applies if a parallel installation has 
  different supply and flue duct lengths (B23, C53).
-   Combined flues (C43) shall be fitted with a condensate drain. 

Note: horizontal flue runs must be installed with a fall of at least 
5 mm per metre.

Flue systems Cyclone BFC

Minimum space requirements

BFC 28

BFC 30

BFC 50

BFC 60

BFC 80

BFC 100

Minimal space for wall duct (mm)   

 

 

550 

550 

550 

550 

640 

640

725 

790 

790 

790 

940 

940

1535 

2075 

2075 

2075 

2230 

2230

1460 

1480 

1480 

1480 

1620 

1620

Y * 

1010 

1030 

1030 

1030 

1170 

1170

Minimal space for roof duct (mm)   

 

 

1305 

1500 

1500 

1500 

1730 

1730

680 

1035 

1035 

1035 

1120 

1120

2965 

3325 

3325 

3325 

3620 

3620

X ** 

2015 

2375 

2375 

2375 

2670 

2670

1575 

1415 

1415 

1415 

1560 

1560

Y ** 

625 

465 

465 

465 

610 

610

For the parts numbers of components and flue gas ducts, etc.
please refer to the “Maintenance and accessories” chapter.

Ø80/125  Ø100/150  Ø100/150  Ø100/150  Ø130/200  Ø130/200

*  Distance without concentric pipe between bend and wall duct. 
**  Distance without concentric pipe between appliance and roof duct. 

BFC 28-60

BFC 80-100

BFC 28

BFC 30

BFC 50

BFC 60

BFC 80

BFC 100