A.O. Smith BTX-80 Instruction Manual Download Page 12

12

in an alcove or closet, the entire floor must be covered by the panel. 

Failure to heed this warning may result in a fire hazard.

Minimum  clearances  between  water  heater  and  combustible 

construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the 

front and 12” (30.5 cm) from  top. (Standard clearance.) If clearances 

stated on the heater differ from standard clearances, install water 

heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should 

be considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access 

to replaceable parts such as thermostats, drain valve, relief valve 

and condensate drain.
When installing the heater, consideration must be given to proper 

location. Location selected should be as close to the wall as practicable 

and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount 

of air for combustion. Do not install in a confined area such as a closet, 

unless you provide air as shown in the “Locating The New Water 

Heater” section. Never obstruct the flow of ventilation air. If you have 

any doubts or questions at all, call your gas supplier.  Failure to provide 

the proper amount of combustion air can result in a fire or explosion 

and cause death, serious bodily injury, or property damage.

fIGure 5.

If  this  water  heater  will  be  used  in  beauty  shops,  barber  shops, 

cleaning establishments, or self-service laundries with dry cleaning 

equipment, it is imperative that the water heater or water heaters 

be installed so that combustion and ventilation air be taken from 

outside these areas.  
Propellants  of  aerosol  sprays  and  volatile  compounds,  (cleaners, 

chlorine based chemicals, refrigerants, etc.) in addition to being highly 

flammable in many cases, will also react to form corrosive hydrochloric 

acid when exposed to the combustion products of the water heater.  

The results can be hazardous, and also cause product failure.

InsulatIon BlanKets

Insulation blankets are available to the general public for external 

use on gas water heaters but are not necessary with these products. 

The purpose of an insulation blanket is to reduce standby heat loss 

encountered with storage tank heaters. Your water heater meets or 

exceeds the Energy Policy Act standards with respect to insulation and 

standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you 

should  follow  these  instructions  (For  identification  of  components 

mentioned below, see Figure 1). Failure to follow these instructions can 

restrict the air flow required for proper combustion, potentially resulting 

in fire, asphyxiation, serious personal injury or death.

•  Do not apply insulation to the top of the water heater, as this will  

interfere with safe operation of the blower assembly.

•  Do not cover the outer door, thermostat or temperature & pressure  

relief valve.

•  Do not allow insulation to come within 2” (5.1 cm) of the floor to  

prevent blockage of combustion air flow to the burner.

•  Do not cover the instruction manual.  Keep it on the side of the  

water heater or nearby for future reference.

•  Do obtain new warning and instruction labels from the manufacturer  

for placement on the blanket directly over the existing labels.

•  Do  inspect  the  insulation  blanket  frequently  to  make  certain  it  

does not sag, thereby obstructing combustion air flow.

aIr requIreMents

For safe operation an adequate supply of fresh uncontaminated 

air for combustion and ventilation must be provided.
An insufficient supply of air can cause recirculation of combustion 

products resulting in contamination that may be hazardous to life. 

Summary of Contents for BTX-80

Page 1: ... MODEL BTX 80 SERIES 100 ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER COMMERCIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER 500 Tennessee Waltz Parkway Ashland City TN 37015 Low Lea...

Page 2: ...y alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California...

Page 3: ...3 GENERAL SAFETY INFORMATION ...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk ...

Page 5: ...ad Cleveland OH44131 NFPAdocumentsarealsoavailablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local codes the National Electrical Code NFPA 70 or the Canadian Electrical Code C22 1 4 If after reading this manual you have any questions or do not understand any ...

Page 6: ... feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructions Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation...

Page 7: ...F Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K Outer Door L Union M Inlet Water Shut Off Valve N Cold Water Inlet O Inlet Dip Tube P Temperature Pressure Relief Valve HH Bushing II Nipple JJ Condensate Tee KK Adapter LL Plug MM Vent Pipe Assembly ...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued ...

Page 9: ...nship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use then special precautions must be taken In addition to using lowest possible temperature setting that satisfies demand of application a Mixing Valve should be installed at w...

Page 10: ...ics All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynamic conditions Recovery Capacities U S Gallons Hr and Liters Hr at Temperature Rise Indicated Recovery capacity based on 90 thermal efficiency ...

Page 11: ...stalled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mount...

Page 12: ...orine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater The results can be hazardous and also cause product failure INSULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary w...

Page 13: ...ne the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is installed in the same space with a water heater sufficient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan Undersized op...

Page 14: ... a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 19 26 for complete venting installation instructions FIGURE 9 The confined space shall be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing withi...

Page 15: ...de requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the water system to be a closed system CHEMICAL VAPOR CORROSION CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS SUCH CORROSION MAY RESULT IN FAILURE ...

Page 16: ...f the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized Temperature Pressure Relief Valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death This water heater is provided with a pro...

Page 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Thermal Expansion on page 15 16 If you do not understand these instructions or have any questions regardingtheTemperature PressureReliefValvecallthetollfreenumber listed on the back cover of t...

Page 18: ...g system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13 FIGURE 12 GAS PIPING WITH FLEXIBLE CONNECTOR FIGURE 13 GAS PIPING WITH ALL BLACK IRON...

Page 19: ...ructions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may be rotated to a different orientation as needed for the specific installation requirements Note the rotational orientation of each part by marking a line several inches long across the joints The lon...

Page 20: ...30 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm L Clearance above paved sidewalk or paved driveway located on public property 7 feet 2 13 m 7 feet 2 13 m F Clearance to outside corner 2 feet 60 cm 2 feet 60 cm M Clearance under veranda porch deck...

Page 21: ...rrectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or fractures particularly at joints between elbows and other fittings and straight runs of vent pipe Check system for signs of sagging or other stresses in joints as a result of misalignment of any compone...

Page 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower housing 6 Make sure the ON OFF switch is in the OFF position and that the outer harness is connected from the blower control box to the connector on the bottom side of the gas valve 7 If the outer har...

Page 23: ...line This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLATIONS FIGURE 18 Cut a length of PVC pipe about 3 5 inches 8 9 cm longer than wall thickness at the opening Glue vent terminal to this section of pipe Slide the wall plate over the pipe to stop agains...

Page 24: ...highest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with the additional vent pipe when calculating maximum equivalent feet of venting INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof Th...

Page 25: ... cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA 4 Make sure the VAA and vent pipe is supported securely to a permanent fixture stud or wall Use standard support straps not supplied with kit that may be found at a local hardware store Failure to pro...

Page 26: ...A and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for Vertical Vent with 3 or 4 inch Pipe Installation of VAA with 3 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths...

Page 27: ... and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight virgin PVC m...

Page 28: ...d make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solvent cement Apply...

Page 29: ...ER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all electric power to the appliance if service is to be performed BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES 1 STOP Read the safety information above on this labe...

Page 30: ...ic does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting water heater temperature at 120 F 49 C Approx mark on temperature setting of gas valve will red...

Page 31: ...ocal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chlorination treatment we can only suggest that chlorination or aeration of the water supply be considered to eliminate the water problem Do not remove the anode leaving the tank unprotected By doing so...

Page 32: ...ould be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner operation through the Viewport on the Inner Door see Figure 1 The main burner should provide complete combustion of gas ignite rapidly give reasonably quiet operation and cause no excessive flame lifting...

Page 33: ... have a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE OPENING THIS CAN CAUSE PROPERTY DAMAGE SERIOUS INJURY OR DEATH Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized Temperature Press...

Page 34: ...oose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances water lines or ground seepage should also be checked To check where threaded portion enters tank insert cotton swab between jacket opening and fitting If cotton is wet follow Draining instructions in th...

Page 35: ... control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the air pressure switch sensing tube is properly connected not kinked or damaged 3 Check continuity of vent temperature limit switch replace switch if contacts remain open under 160ºF 71 C 4 Ensure the ...

Page 36: ...off for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is positioned to provide consistent ignition 6 Check for any cracks in ignitor assembly ceramic insulators replace ignitor assembly if damaged 7 Check resistance of ignitor at room temperature 77ºF 25 C ...

Page 37: ...hin tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent temperature limit switch is opening its contacts at normal operating temperatures during heating cycle replace the vent temperature limit switch 3 Ensure water heater is not over firing 3 1 Check burn...

Page 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES ...

Page 39: ...o unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but ar...

Page 40: ...40 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com Copyright 2010 A O Smith Corporation All rights reserved ...

Reviews: