A.O. Smith BT- 80 Installation & Operating Instructions Manual Download Page 5

5

Drain pans suitable for these heaters are available from your
distributor or A. O. Smith Water Products Company, 500 Tennessee
Waltz Parkway, Ashland City, TN 37015.

Water heater life depends upon water quality, water pressure and the
environment in which the water heater is installed.  Water heaters are
sometimes installed in locations where leakage may result in property
damage, even with the use of a drain pan piped to a drain.  However,
unanticipated damage can be reduced or prevented by a leak detector
or water shutoff device used in conjunction with a piped drain pan.
These devices are available from some plumbing supply wholesalers
and retailers, and detect and react to leakage in various ways:

• Sensors mounted in the drain pan that trigger an alarm or turn off

the incoming water to the water heater when leakage is detected.

• Sensors mounted in the drain pan that turn off the water supply

to the entire home when water is detected in the drain pan.

• Water supply shutoff devices that activate based on the water

pressure differential between the cold water and hot water pipes
connected to the water heater.

• Devices that will turn off the gas supply to a gas water heater

while at the same time shutting off its water supply.

For appliance installation locations with elevations above 2000'
(610m), refer to HIGH ALTITUDE INSTALLATIONS section of this
manual for input reduction procedure.

HIGH ALTITUDE INSTALLATIONS

 WARNING

INSTALLATIONS ABOVE 2000' (610m) REQUIRE REPLACEMENT
OF THE BURNER ORIFICE IN ACCORDANCE WITH SECTION
8.1.2 OF THE NATIONAL FUEL GAS CODE (ANSI Z223.1). FOR
CANADIAN INSTALLATIONS CONSULT THE NATURAL GAS AND
PROPANE INSTALLATION CODE CAN/CSA-B149.1. FAILURE TO
REPLACE THE ORIFICE WILL RESULT IN IMPROPER AND
INEFFICIENT OPERATION OF THE APPLIANCE RESULTING IN
THE PRODUCTION OF INCREASED LEVELS OF CARBON
MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD
RESULT IN SERIOUS PERSONAL INJURY OR DEATH.

You should contact your gas supplier for any specific changes which
may be required in your area.

As elevation above sea level is increased, there is less oxygen per
cubic foot of air. Therefore, the heater input rate should be reduced
at high altitudes for satisfactory operation with the reduced oxygen
supply. Failure to make this reduction would result in an overfiring
of the heater causing sooting, poor combustion and/or unsatisfactory
heater performance.

U.S. REQUIREMENTS

Ratings specified by manufacturers for most appliances apply for
elevations up to 2000 feet (610m). For elevations above 2000 feet
(610m), ratings must be reduced at the rate of 4% for each 1000 feet
(305m) above sea level. For example, if a heater is rated at 75,100
Btu/Hr (22.0 kW) at sea level, to rate the heater at 4000 feet (1219m),
you subtract 4 (once for each thousand feet) x 0.04 (4% input
reduction) x 75,100 Btu/Hr (original rating) from the original rating.
Therefore, to calculate the input rating at 4000 feet (1219m): 4 x 0.04
x 75,100 Btu/Hr = 12,016 Btu/Hr (3.5 kW); 75,100 Btu/Hr (22.0 kW) -
12,016 Btu/Hr (3.5 kW) = 63,084 Btu/Hr (18.5 kW). At 6000 feet
(1829m) the correct input rating should be 57,076 Btu/Hr (16.7 kW).

CANADIAN REQUIREMENTS

Appliances with inputs up to and including 400,000 BTU (117.1 kwh)
must be factory equipped with orifices for operation at specific
elevations. Standard (sea level) orifices permit operation up to 2000'
(610m) elevation. For operation between 2000' (610m) and 4500'
(1370m) specify "HIGH ALTITUDE OPERATION" when ordering the
heater(s). For operation above 4500' (1370m) consult factory before
ordering. Field conversion for operation at altitudes other than that

specified on the heater rating plate is not permitted.

The input reduction is primarily achieved by reducing the size of
the main burner orifices.  To do this, the main burner orifices require
replacement with orifices sized for the particular installation
elevation.  Correct orifice sizing and parts may be obtained from
A.O. Smith Water Products Company.  When ordering, be sure to
state the model number and the altitude of the location where the
water heater is being installed.

Upon completion of derating of the heater, adjustment to the gas
pressure regulator may be required.  See CHECKING THE INPUT
section in this manual for inlet and manifold pressure requirements.

Also due to the input rating reduction required at high altitudes, the
recovery rating of the appliance is also reduced and should be
compensated for in the sizing of the equipment for application.

CLEARANCES

These heaters are approved  for installation on combustible flooring
in a closet having a ceiling 12" (30.5cm) above top cover and with
clearances to combustible construction of 6" (15.2cm) from flue or
vent connector, 0" (0cm) at the sides and rear and 4" (10.1cm) to
front to prevent a possible fire hazard condition.  A minimum of 4"
(10.1cm) shall be allowed for installation of serviceable parts.

HARD WATER

Where hard water conditions exist, water softening or the threshold type
of water treatment is recommended. This will protect the dishwashers,
coffee urns, water heaters, water piping and other equipment.

See PREVENTIVE MAINTENANCE section for details of tank
cleanout procedure.

AIR REQUIREMENTS

REFER TO THE CURRENT EDITION OF THE NATIONAL FUEL
GAS CODE  ANSI Z223.1/NFPA 54.

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS
AND LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.

 WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTION AND VENTILATION.  AN INSUFFICIENT SUPPLY OF
AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS
RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUS
TO LIFE.  SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW,
LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING
OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES
AND CREATES A RISK OF ASPHYXIATION.

Where an exhaust fan is supplied in the same room with a heater,
sufficient openings for air must be provided in the walls.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO
THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION.  SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick, or stone construction,
unconfined spaces may provide adequate air for combustion,
ventilation and draft hood dilution.

If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping, heavy

Summary of Contents for BT- 80

Page 1: ...er INSTALLATION OPERATION SERVICE MAINTENANCE LIMITED WARRANTY Thank you for buying this energy efficient water heater from A O Smith Water Products Company We appreciate your confidence in our produc...

Page 2: ...ional Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CAN CSA B149 1 These documents are available from the Canadian Standards Association 8501 East Pleasant Valley...

Page 3: ...12 Check Venting 12 13 High Temperature Limit Switch 13 SERVICE INFORMATION 13 14 Pilot and Main Burner 13 Checking Gas Input 13 14 Vent System 14 Relief Valve 14 Hot Water Odor 14 Anode Rod Inspectio...

Page 4: ...ly all bronze circulators are used with commercial water heaters Although circulators are oiled and operated by the manufacturer some circulators must be oiled again before operating Please refer to m...

Page 5: ...tu Hr 16 7 kW CANADIAN REQUIREMENTS Appliances with inputs up to and including 400 000 BTU 117 1 kwh must be factory equipped with orifices for operation at specific elevations Standard sea level orif...

Page 6: ...ain or well Excessive pressure may develop in such closed systems causing premature tank failure or intermittent relief valve operation This is not a warranty failure An expansion tank or a similar de...

Page 7: ...VE AND TANK Your local code authority may have other specific relief valve requirements A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID SCALDING OR W...

Page 8: ...0 556 878 1552 3192 15 21 44 83 170 264 492 776 1391 2840 18 19 40 76 155 237 445 703 1259 2577 21 18 37 70 143 220 410 659 1142 2372 24 17 35 64 135 202 381 600 1083 2196 27 16 32 60 126 190 357 571...

Page 9: ...VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER DO NOT ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET VALVE CLOSED TO OPERATE THE WATER HEATER 1 Close the heater drain valve by turning...

Page 10: ...10...

Page 11: ...ghtly and turn clockwise to OFF Figure A NOTE Gas control knob CANNOT be turned from PILOT to OFF unless it is pushed down slightly Do not force 4 Remove the inner and outer burner doors located below...

Page 12: ...and windows and all doors between the space in which the water heater s connected to the venting system are located and other spaces of the building Turn on all appliances not connected to the venting...

Page 13: ...PETENT SERVICE PERSON USERS OF THIS APPLIANCE SHOULD BE AWARE THAT GAS COMPONENTS WEAR OUT OVER A PERIOD OF TIME THE GAS CARRYING COMPONENTS OF THIS APPLIANCE SHOULD BE INSPECTED FOR PROPER OPERATION...

Page 14: ...PPLIANCE HOT WATER ODOR On occasion hot water may develop a strong odor If this occurs drain the heater completely flush thoroughly and refill If the problem persists chlorination of the heater and re...

Page 15: ...e obtained from your dealer distributor or the A O Smith Product Service Division Order part no 4763 1 gal packed 4 gallons per case or part no 4813 5 gallon container Hydrochloric base acids are not...

Page 16: ...t UN LIME remain in the heater for 5 minutes and then lower the container to the Drain Position see Figure 9 9 Deliming activity is indicated by foaming on the surface of the UN LIME If there is delim...

Page 17: ...ssures or temperatures in the system or to a faulty relief valve Your dealer or a qualified service technician should be called to determine the cause of the problem and to correct it 4 If you cannot...

Page 18: ...xpansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty th...

Page 19: ...19...

Page 20: ...20 A O SMITH WATER PRODUCTS COMPANY 500 Tennessee Waltz Parkway Ashland City TN 37015 PHONE 1 800 527 1953 www aosmithwaterheaters com E MAIL parts hotwater com...

Reviews: