Code and description
Cause
Measure
S02 (blocking error)
Open circuit from sensor 1
of temperature sensor T
1
at the top of tank
(1).
Sensor is not (correctly) connected
Connect the sensor lead to JP5
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S03 (blocking error)
Open circuit in sensor 2 of
temperature sensor T
1
at
the top of the tank
(1)
.
Sensor is not (correctly) connected
Connect the sensor lead to JP5
Damaged cable and/or defective sensor
Replace the cable and/or sensor
S04 (blocking error)
Open circuit from
dummy 1.
Dummy is not (correctly) connected
Connect the dummy sensor (dummy sensor
1 and 2) leads to JP4.
Defective dummy
Replace the dummy sensor
S05 (blocking error)
Open circuit from
dummy 2
Dummy is not (correctly) connected
Connect the dummy sensor (dummy sensor
1 and 2) leads to JP4.
Defective dummy
Replace the dummy sensor
S11 (blocking error)
Short circuit in
temperature sensor T
2
at
the bottom of the tank.
Short circuit in sensor circuit
Replace the cable and/or sensor.
S12 (blocking error)
Short circuit in sensor 1 of
temperature sensor T
1
at
top of tank
(1)
Short circuit in sensor circuit
Replace the cable and/or sensor.
S13 (blocking error)
Short circuit in sensor 2 of
temperature sensor T
1
at
the top of the tank
(1)
.
Short circuit in sensor circuit
Replace the cable and/or sensor.
S14 (blocking error)
Short circuit from
dummy 1
Short circuit in sensor circuit
Replace the cable dummy sensor
(2)
.
S15 (blocking error)
Short circuit from
dummy 2
Short circuit in sensor circuit
Replace the cable dummy sensor
(2)
.
F01 (blocking error)
Defect in power supply
circuit
Live and neutral connected wrong way
around.
Be sure to connect the live and neutral
correctly (see section 7.7); the water heater
is phase-sensitive
Condensation on the flame probe
Disconnect the lead at the flame probe
Ignite the water heater three times, with
an interrupted ionisation circuit
Reconnect the ionisation lead to the
flame probe
Ignite the water heater again
The repeated ignition attempts will have
caused the condensation to evaporate
•
•
•
•
•
Floating neutral
Install an isolating transformer (see section
7.7.3.1)
92
Installation, Maintenance and Service part
Summary of Contents for BFC Cyclone 28
Page 6: ...6...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13...
Page 14: ...14...
Page 16: ...16 User part...
Page 18: ...18 User part...
Page 24: ...24 User part...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41...
Page 42: ...42 User part...
Page 46: ...46 Installation Maintenance and Service part...
Page 52: ...52 Installation Maintenance and Service part...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59...
Page 76: ...76 Installation Maintenance and Service part...
Page 78: ...78 Installation Maintenance and Service part...
Page 84: ...84 Installation Maintenance and Service part...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part...