Fig. Cleaning opening
1
IMD-0080 R1
Remove the cover plate (1) on the outer jacket (see the figure).
Undo the bolts.
Remove the cover and the gasket.
Inspect the tank and remove the loose scale deposits and contamination.
If the scale cannot be removed by hand, descale the water heater with a descaling
agent. Contact the supplier/manufacturer for advice on what descaling agent to use.
Close the cleaning opening. To avoid damage to the tank, tighten the bolts that
fasten the lid with a torque no greater than 50 Nm. Use suitable tools for this.
10.2.2
Clean the condensate drain
To prevent blockages, it is essential to clean the condensation water discharge and
condensation trap regularly.
10.3
Gas-side maintenance
Do gas side maintenance when the water heater does not operate correctly, the air
pressure differential is not correct and/or the CO
2
value is not correct.
To do gas side maintenance:
Clean the burner (see section 10.3.1)
Clean the heat exchanger (see section 10.3.2)
10.3.1
Clean the burner
Detach the burner.
Remove all contamination present on the burner.
Fit the burner.
10.3.2
Clean the heat exchanger
Detach the burner.
Clean the combustion chamber of the heat exchanger using a vacuum cleaner and a
soft brush.
Detach the chimney flue.
Clean the end of the heat exchanger using tap water.
Fit the burner.
Fit the chimney flue.
Note
Check the pressure differential again after cleaning. If the pressure differential is too low
following cleaning, please contact the supplier of the water heater.
1.
2.
3.
4.
5.
6.
•
•
1.
2.
3.
1.
2.
3.
4.
5.
6.
n
0311704_BFC_28-120_III_
ENEN_V2.4, 2022-10-17
87
Summary of Contents for BFC Cyclone 120
Page 6: ...6 ...
Page 13: ...User part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 13 ...
Page 14: ...14 ...
Page 16: ...16 User part ...
Page 18: ...18 User part ...
Page 24: ...24 User part ...
Page 41: ...Installation Maintenance and Service part 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 41 ...
Page 42: ...42 User part ...
Page 46: ...46 Installation Maintenance and Service part ...
Page 52: ...52 Installation Maintenance and Service part ...
Page 59: ...Fig Venting systems 0311704_BFC_28 120_III_ENEN_V2 4 2022 10 17 59 ...
Page 76: ...76 Installation Maintenance and Service part ...
Page 78: ...78 Installation Maintenance and Service part ...
Page 84: ...84 Installation Maintenance and Service part ...
Page 102: ...Fig Dimensions BFC 28 30 50 60 102 Installation Maintenance and Service part ...
Page 104: ...Fig Dimensions BFC 80 100 120 104 Installation Maintenance and Service part ...
Page 112: ...12 7 Declaration of conformity 112 Installation Maintenance and Service part ...
Page 113: ......
Page 114: ......
Page 118: ...116 Installation Maintenance and Service part ...