Installation
16
Instruction manual ADM
3
is
Air humidity and ambient temperature specifications
3.3.2
Maximum floor load
In connection with the appliance's weight, take account of the maximum floor
loading, refer to the table.
3.3.3
Water composition
The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
The table gives an overview of the specifications.
Water specifications
Note
If the water specifications deviate from those stated in the table, then the
tank protection cannot be guaranteed
(13 "Warranty (certificate)")
.
3.3.4
Working clearances
For access to the appliance, it is recommended that the following clearances
are observed (see figure):
•
AA: around the appliance's control column and cleaning openings: 100 cm.
•
BB: all sides of the appliance: 50 cm.
•
Above the appliance (room to replace the anodes):
-
100 cm if using fixed anodes, or
-
50 cm if using flexible anodes.
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered.
Note
When installing the appliance, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, the appliance should be
installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least
5cm deep with a length and width at least 5cm greater than the diameter of the
appliance.
Air humidity and ambient temperature
Air humidity
max. 93% RV at +25°C
Ambient temperature
Functional: 0 < T < 60°C
Weight of the appliance filled with water
ADM 40
ADM 50
ADM 60
ADM 80
ADM 90
ADM 115
ADM 135
504 kg
578 kg
507 kg
573 kg
522 kg
523 kg
581 kg
Water composition
Hardness
(alkaline earth ions)
> 1.00 mmol/l:
•
German hardness> 5.6° dH
•
French hardness > 10.0° fH
•
English hardness > 7.0° eH
Conductivity
> 125 µS/cm
Acidity (pH value)
7.0 < pH value < 9.5
Summary of Contents for ADM - 115
Page 1: ......
Page 2: ......
Page 4: ...4 Instruction manual ADM gis ...
Page 10: ...Introduction 10 Instruction manual ADM 1 gis ...
Page 32: ...Installation 32 Instruction manual ADM 3 is ...
Page 40: ...Conversion to a different gas category 40 Instruction manual ADM 4 is ...
Page 46: ...Draining 46 Instruction manual ADM 6 gis ...
Page 50: ...Status of the appliance 50 Instruction manual ADM 8 gis ...
Page 52: ...Starting and running 52 Instruction manual ADM 9 gis ...
Page 54: ...Shutting down 54 Instruction manual ADM 10 gis ...
Page 60: ...is Instruction manual ADM 60 ...
Page 72: ...Appendices 72 Instruction manual ADM 14 is ...
Page 74: ...0306 132 4 0 UK Index Instruction manual ADM ...