7. 

SWITCH CONFIGURATION 

 

Switch 

Name 

Pin switch 

Definition of Behaviour 

SW1

 

1 & 2 

Switches 1 and 2 set the CAN communication speed: 

 

3 to 8 

The logic address is composed by 2 elements: the module 
identification and the hardware address. The module identification is 
set on firmware and cannot be changed. The hardware address is 
selected by switches 3 to 8, being 3 the least significant bit (LSB) and 
8 the most significant bit (MSB): 

ON

1  2  3  4  5  6  7  8

ON=1

OFF=0

LSB

MSB

Board  Address

 

 

SW1 behaviour 

 
 

Switch ID 

Description 

Definition of Behaviour 

SW2 

BOOT0 

Factory use.

 Must be OPEN on operation. 

SW3 

RESET 

Must be OPEN on operation. A temporary bridge causes a reset of the board.

 

SW4 

CAN-END 

Placing jumper adds a 120 Ohm resistor between the CAN-High and CAN-Low 
signals of CAN-Bus. 

 

Switches description 

 
 

 

 

 

00 = 50 kbps 
10 = 100 kbps 
01 = 125 kbps 
11 = 250 kbps 

Summary of Contents for YAV90304

Page 1: ...04 Note Before you begin complete the software and hardware installation procedures applicable to your application Note the guidelines in this document are specific to the YAV90304 The other components in the system might not meet the same safety ratings Refer to the documentation of each component in the system to determine the safety and EMC ratings for the entire system ...

Page 2: ... J5 CAN Power Supply JST B04B EH A Type connectors 6 6 1 2 J3 Inputs connector JST B10B EH A Type connector 6 6 1 3 J1 Outputs connector JST B10B EH A Type connector 6 6 1 4 J2 Outputs connector JST B10B EH A Type connector 6 7 SWITCH CONFIGURATION 7 8 HARDWARE SPECIFICATIONS 8 9 OPERATION 9 9 1 PHI6 EXPLORER soft interface 9 10 LOW LEVEL CAN COMMANDS 10 ...

Page 3: ...t when such failure is due to the parameters incorrect programming The product described in this manual can be configured to comply with the ruling of different countries The manufacturer does not hold any responsibility if the company installing it does not configure it according to the legal commercial or security prescriptions that may be in force in the place of installation or otherwise agree...

Page 4: ...ts switches or PNP sensors and or driving inputs and actuators Thanks to the distributed CAN bus only 4 wires will be needed to control the module which makes it an easy to use and flexible module Its reduced form factor permits the module to be placed inside the fixture 4 LAYOUTAND DIMENSIONS All dimensions are in millimetres ...

Page 5: ...OUT P3 2 5K6 1K J1 I O s diagram UB Output 5K6 Input ADDRESS 5V OUT P3 0 OUT P3 1 J5 J2 J3 OUT P3 7 UB OUT P3 5 OUT P3 3 OUT P3 4 OUT P3 6 CAN H CAN L J4 OUT P5 3 OUT P5 1 OUT P5 0 OUT P5 2 OUT P5 6 OUT P5 5 OUT P5 4 OUT P5 7 IN P2 3 IN P2 1 IN P2 0 IN P2 2 IN P2 6 IN P2 4 IN P2 5 IN P2 7 ...

Page 6: ... 3 Input 3 4 Input 4 5 Input 5 6 Input 6 7 Input 7 8 Input 8 9 GND 10 24Vdc 6 1 3 J1 Outputs connector JST B10B EH A Type connector Pin Description 1 Output 1 2 Output 2 3 Output 3 4 Output 4 5 Output 5 6 Output 6 7 Output 7 8 Output 8 9 GND 10 Not connected 6 1 4 J2 Outputs connector JST B10B EH A Type connector Pin Description 1 Output 1 2 Output 2 3 Output 3 4 Output 4 5 Output 5 6 Output 6 7 O...

Page 7: ... is selected by switches 3 to 8 being 3 the least significant bit LSB and 8 the most significant bit MSB ON 1 2 3 4 5 6 7 8 ON 1 OFF 0 LSB MSB Board Address SW1 behaviour Switch ID Description Definition of Behaviour SW2 BOOT0 Factory use Must be OPEN on operation SW3 RESET Must be OPEN on operation A temporary bridge causes a reset of the board SW4 CAN END Placing jumper adds a 120 Ohm resistor b...

Page 8: ...y Min Typ Max Units Control Voltage 22 24 26 Vdc Output Voltage 22 24 26 Vdc Output maximum current 500 mA Minimum input voltage for level High 8 5 Vdc Maximum input voltage for level Low 5 5 Vdc CAN Bus operation speed 50 250 kbps Operation specifications ...

Page 9: ...system maintenance on site Activate relays By clicking a relay in the panel the relay closes and its status in the panel is updated Reset Reset button will put all relays in Open status Config tags To operate with Phi6 driver each relay must be given a tag name By clicking this button the panel will change its background color from grey to yellow and tag name can be modified ...

Page 10: ...Pag 10 10 www 6tlengineering com 24 06 2022 YAV90304 10 LOW LEVEL CAN COMMANDS ...

Reviews: