4.1.3.
FAULT
Indicates that the system is in the FAULT state (general fault indicator), where at least one device in the
system is reporting a fault.
Continuous: when a local fault is detected
Blinking slow: when a local device is healthy and at least one remote device is reporting fault state
4.1.4.
POWER SUPPLY
Indicates a power supply fault of the local C500 unit, where at least one of following faults is reported:
Continuous: mains fault
Blinking slow: battery-related fault:
o
Loss of battery
o
Loss of charger
o
Battery resistance too high
o
Temperature fault
o
Charger communication fault
4.1.5.
SYSTEM FAULT
Indicates system fault of the C500 main unit, where:
-
The CPU or program execution is stopped or malfunctioning,
-
Corruption of storage memory containing config settings and audio files (SD card).
-
Front panel is not communicating with main board
Where a system fault is caused by a CPU or memory fault, the C500 remains in “safe state”, where critical
functions (including audio transmission, reaction on control inputs, etc.) are stopped until the fault
is removed.
Continuous:
o
CPU / program fault
o
front panel fault
Blinking slow:
o
SD card fault
o
Config file not compatible
o
Wrong ID setting
4.1.6.
NETWORK
Indicates when any device or link in the network is missing.
Blinking slow:
Global ring is broken (any place in the ring)