SPECIFICATIONS

Supply Voltage:

24 to 240 VAC/VDC

Supply Fusing:

Supply to be fused at 500mA maximum. Note: fuse must be 1500A capable. 

1 fuse per sensor MUST be used.

Switching Capacity:

50 mA maximum

Saturation Voltage:

5.5 Volts maximum (output on)

Leakage Current:

1 mA maximum (output off)

Ambient Temperature:

5°F (-15°C) to +122°F (+50°C)

Output State:

FET

Contact closed above 0% set speed 

Contact opens when zero speed detected

Sensing Range:

6 mm (15/64”) maximum on ferrous metal at 77°F (25°C)

5 mm (13/64”) 

maximum on non-ferrous metal at 77°F (25°C)

Input Pulse Range: 

From 20 to 3,600 pulses per minute (PPM)

Start-Up Delay:

4 seconds

Trip Point: 

When no pulse is detected for more than 4s (zero speed condition)

Enclosure:

Nylon - ISO threaded 18 mm by 1.0 mm pitch

Relative Humidity:

90% RH

LED Indicators:

Blue - Target Sensed, Green - Speed Present

Connections:

2 wire; 3m long cable.

Protection:

IP66

WARNING

• Rotating machinery can cause serious injury or death

• Always lockout and tagout the machine prior to installation

The M100 Stopswitch is a simple inductive proximity shaft speed monitoring device.  The self-contained 

unit has a single set point, which signals when the shaft has stopped rotating.  It can be used for process 

control, motion detection and stopped shaft indication.
An inductive sensing device located in the nose of the M100 enclosure will detect a metal target. Ideally, 

the target should be a ferrous metal, but non-ferrous metal will be detected at a shorter range. Maximum 

range for ferrous targets is 6 mm (15/64 in.) and for non-ferrous targets it is 5 mm (13/64 in.), assuming 

a 19 mm (3/4 in.) diameter target.  Smaller targets may be used but operating distances will be reduced.
The M100 Stopswitch requires no calibration and provides an output when the shaft has stopped rotating.

The unit incorporates a start-up delay of 4 seconds to allow moving parts to achieve correct speed, 

thereafter, if a pulse is not received within 4 seconds an output stopped motion signal is indicated.

Summary of Contents for M100

Page 1: ...www go4b com M100 Stopswitch STOPPED MOTION MONITOR INSTALLATION INSTRUCTIONS OPERATION MANUAL Part No s M1003V10AI...

Page 2: ...ENSIONS Page 7 INSTALLATION Page 7 8 STANDARD WIRING DIAGRAM Page 8 9 TESTING COMMISSIONING Page 9 10 TROUBLESHOOTING GUIDE Page 10 PRODUCT WARRANTY Page 11 TABLE OF CONTENTS Rotating parts can crush...

Page 3: ...esponsibility of the user unless you have asked 4B to perform these tasks B All installation and wiring must be in accordance with Local and National Electrical Codes and other standards applicable to...

Page 4: ...ction work at the facility hours of operation animal or insect infestation and the real world experience of knowing how your employees perform their jobs The personnel or person you select to install...

Page 5: ...ARNING Rotating machinery can cause serious injury or death Always lockout and tagout the machine prior to installation The M100 Stopswitch is a simple inductive proximity shaft speed monitoring devic...

Page 6: ...ALS ATEX Baseefa14ATEX0115X Ex II 2G Ex mb IIC T5 Gb Ex II 2D Ex mb IIIC t100 C Db Tamb 15 C to 50 C Ex I M2 Ex mb I Mb IECEx IECExBAS14 0061X Ex mb IIC T5 Gb Ex mb IIIC t100 C Db I M2 Ex mb I Mb Tamb...

Page 7: ...tch to a motor starting coil It is not recommended to wire the M100 Stopswitch in series with other sensors The cable on the M100 Stopswitch can be extended to virtually any length in ordinary 2 wire...

Page 8: ...otect the sensor cables Use rigid metal conduit to protect the cables from the sensors to the control unit Conduit systems can channel water due to ingress and condensation directly to sensors and sen...

Page 9: ...e problem has been diagnosed and corrected TESTING AND COMMISSIONING 1 Check that the unit is correctly installed see standard wiring diagram 2 Check that the distance between the target stud or bolt...

Page 10: ...et and check the target size as specified under INSTALLATION Blue LED input Stays on Permanently Either increase the gap between the target and the shaft or between the target and the sensor face PART...

Page 11: ...the user unless you have asked 4B to perform these tasks B All installation and wiring must be in accordance with Local and National Electrical Codes and other standards applicable to your industry T...

Page 12: ...ca Tel 27 0 11 708 6114 Fax 27 0 11 708 1654 4B AUSTRALIA Building 1 41 Bellrick Street Acacia Ridge Queensland 4110 Australia Tel 61 0 7 3216 9365 Fax 61 0 7 3219 5837 4B COMPONENTS LTD 625 Erie Aven...

Reviews: