Using the same tank calibration table for different sensors
To save time, you could use the same tank calibration table for the sensors of the
equal length installed in the ‘identical’ tanks.
ATTENTION!!!
We strongly recommend you not to use the same table for
different sensors as doing so will likely increase the margin of error of the
sensors.
No tanks are actually identical
. Although the total capacity of two tanks could be
stated as 500 liters for example, the capacity of one of them could in fact be 489 liters
and the capacity of the other could in fact be 511 liters. This will lead to the tank
calibration table made for one tank be inaccurate if applied to the second.