background image

10

Troubleshooting Guide

Problem

Cause

Solution

Notes

Unit never produces 

RO water/only provides 

bypass water

Low Feed Water Pressure

Repair existing Booster 

Pump

Contact Dealer

Add Water Booster Pump

Only if Booster Pump is not 

installed.

Unit Runs Low  

or Out of Water

Low Feed Water Pressure

Repair Existing Booster 

Pump / System  

(If Applicable) 

Contact Dealer

Add Water Booster Pump

Only if Beverage Booster 

System is not installed

RO Membrane Fouled

Replace RO Membrane

Feed Water Pressure, 

Temperature, RO 

Membrane Flow Rate 

should be checked before 

replacing Membrane

Storage Tank Air Charge 

is Low

Drain Tank using Sample 

Valve, with Sample Valve 

Open, Pump Up Air Charge, 

8 to 10 psi, Close Sample 

Valve

Unscrew Blue Cap to 

Access Schrader Air Valve

Pre-Filter is Plugged by 

Sediment (Particles)

Replace Pre-Filter

A more frequent pre-filter 

change-out schedule may 

be needed or use  

HF60-CL or HF90-CL for 

high sediment load area

Slow Leak In the 

Distribution Line

Repair Leak

The unit produces water 

slowly. A dripping leak 

can prevent the tank from 

filling

Unit Never Shuts Off 

(Continually Runs to 

Drain)

RO Membrane Partially 

Fouled, Unit cannot produce 

enough water to keep up 

with demand

Replace RO Membrane

High levels of hardness 

minerals may be present 

in feed water, monitor 

reject flow for plugging, 

contact dealer to add a 

water softener

Product water check valve, 

within the RO Membrane 

allowed storage tank to 

flow backwards to drain

Check Reject Water flow 

to drain in the morning. 

Unit should be off and 

no flow to drain. If flow 

to drain exists, turn off 

the feed water valve and 

check for flow to drain in 

10 minutes. If flow to drain 

remains steady, replace 

RO Membrane.

Reject Water flow to drain 

should stop when the feed 

water valve is off.

Summary of Contents for SGLP100-CL

Page 1: ...ave this manual with owner operator SGLP100 CL SGLP200 CL SGLP200 CL BP 3MTM Water Filtration Products Installation and Operating Instructions for SGLP100 CL SGLP200 CL and SGLP200 CL BP REVERSE OSMOSIS FILTRATION SYSTEMS ...

Page 2: ...damage due to water leakage or flooding Read and follow Use Instructions before installation and use of this system Change the disposable pre filter at the recommended interval the disposable pre filter MUST be replaced every 12 months or sooner Change the disposable filter RO membrane at the recommended interval the disposable filter RO membrane MUST be replaced every 24 months or sooner Failure ...

Page 3: ...n to mount the bracket Mount filter in such a position as to prevent it from being struck by other items used in the area of installation Ensure that the location and fasteners will support the weight of the system when installed and full of water Ensure all tubing and fittings are secure and free of leaks FEEDWATER PARAMETERS These systems are intended for use on feedwater meeting the following p...

Page 4: ...tes listed are at a water pressure and temperature of 50 PSI and 77 F producing water at atmosphere PARTS LIST THE FOLLOWING PARTS ARE INCLUDED WITH THE SGLP100 CL SGLP200 CL and SGLP200 CL BP REVERSE OSMOSIS WATER FILTRATION SYSTEMS PLEASE UNPACK THE CONTENTS FROM THE PRODUCT BOX AND CHECK TO VERIFY THAT ALL OF THE PARTS LISTED BELOW ARE INCLUDED SHOULD ANY PARTS BE MISSING PLEASE CONTACT 3M PURI...

Page 5: ...ing one end of which is connected to the brine in port of the permeate pump Insert the other end of that 1 4 tubing with the flow control at the bottom of the RO Membrane cartridge 5b For SGLP200 CL and SGLP200 CL BP ensure that the blue flowcontrol is securely pushed into 1 4 tubing one end of which is connected to the brine in port of the permeate pump Insert the other end of that 1 4 tubing wit...

Page 6: ...nia_18965 File Name 18965_Figure2 ai Structure Illustration Date 07 13 15 This artwork has been created as requested by 3M 3M is responsible for the artwork AS APPROVED and assumes full responsibility for its correctness Scale 1 Inch To Drain Outlet To Equipment Water Inlet Inlet Optional Service Loop Water Valve not included Water Sample Valve Tank Shut Off Valve IF INSTALLING CLEANING BYPASS PLE...

Page 7: ... For SGLP100 CL remove the red cap from the RO membrane cartridge and moisten the o rings with water Insert the cartridge into the filter head Then turn the cartridge 1 4 turn to the right 2b For SGLP200 CL and SGLP200 CL BP remove the red caps from both the RO membrane cartridges and moisten the o rings with water Insert the RO membrane cartridges into the filter heads Ensure that the RO cartridg...

Page 8: ...o the filter head Be sure that the ears on the cartridge line up with the spaces in the head 10 Turn new cartridge 1 4 turn to the right 11 Repeat steps 5 12 from System start up Remove the tubing from the fitting before completely removing the RO membrane CARTRIDGE RO MEMBRANE CHANGE INSTRUCTIONS Pre filter Cartridge Replace every 12 months 1 Close tank shut off 2 Turn used pre filter cartridge 1...

Page 9: ...w the cap on the side of the tank to expose the Schrader Air Valve 3 Using a standard bicycle or automobile tire pressure gauge that is capable of reading pressure accurately from 0 10 psi Connect the air pressure gauge to the Schrader Air Valve on the water tank 4 Read the tank s air pressure 5 The air pressure should be between 8 and 10 psi 6 If the air pressure is below 8 psi or above 10 psi co...

Page 10: ...OUNTING HOLES 2X 1 2 8 X 5 8 2X 9 4X 1 4 CENTRALLY LOCATE AS SHOWN BY ISSUED SIZE CODE IDENT NO DRAWING NO D 15472 SCALE DO NOT SCALE D Apicella SHEET 1 OF 2 56362 DATE APRVD CHECKED UNLESS OTHERWISE SPECIFIED DATE FORM NO ENG 132 0110 04 21 15 DRAWN SYSTEM SGLPX00 CL BREAK EDGES MODEL 56362 MACHINED SURFACES 3M Purification Inc 12 7 8 44 22 5 8 3 5636203 SGLP200 CL BP 2 W AUTOBYPASS KIT 5636202 S...

Page 11: ... Sediment Particles Replace Pre Filter A more frequent pre filter change out schedule may be needed or use HF60 CL or HF90 CL for high sediment load area Slow Leak In the Distribution Line Repair Leak The unit produces water slowly A dripping leak can prevent the tank from filling Unit Never Shuts Off Continually Runs to Drain RO Membrane Partially Fouled Unit cannot produce enough water to keep u...

Page 12: ...11 5 8 4X 10 1 2 2X 3 4 4X 9 2X 3 8 8X 1 4 4X 7 6 5 4 Figure 5 ...

Page 13: ... EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OR CONDITION OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR ANY IMPLIED WARRANTY OR CONDITION ARISING OUT OF A COURSE OF DEALING CUSTOM OR USAGE OF TRADE This warranty does not cover labor If the 3M product does not conform to this warranty then the sole and exclusive remedy is at 3M s option replacement of the 3M pro...

Page 14: ...13 ...

Page 15: ...14 NOTES ...

Page 16: ...ree 866 990 9785 Worldwide 203 237 5541 Fax 203 238 8701 www 3Mfoodservice com www 3Mpurification com 3M is a trademark of 3M Company Schrader is a trademark of Schrader International Inc 34 8717 8351 9 2015 3M Company All rights reserved Please Recycle Printed in U S A ...

Reviews: