Do not cover or obstruct visual alarm LED. Doing so may adversely affect product performance and 

result in sickness or 

death.

TROUBLE INDICATOR

Internal failure of the CM-16A will cause an open circuit in the normally closed (NC) Trouble Relay to provide for actuation of 
the control panel circuits. The status LED will flash AMBER. See ERRORS section. The CM-16A microprocessor continuously 
monitors various detector parameters. Failure of the CM-16A’s internal power supply or a lack of power to the detector will 
result in the status light remaining OFF (not illuminated). In this case, the most common cause of detector trouble would be a 
break in the wiring between the control panel and the CM-16A.

ERRORS

The CM-16A continuously monitors various internal operating parameters. If a problem is found, the unit will switch to Trouble 
mode. See TROUBLE INDICATOR section. To reset the unit for normal operation, press the TEST/RESET switch, or remove 
power to the unit, wait a few seconds, then re-apply unit power. If this problem persists, your detector requires repair; contact 
the alarm panel installer or 3M™ Macurco™ Tech Support for advice. If repair is required, return the unit to manufacturer to 
comply with warranty.

MAINTENANCE

Do not disassemble unit or attempt to repair or modify any component of this detector. This detector contains no user 
serviceable parts, and substitution of components may adversely affect product performance and 

result in sickness  

or death.

The CM-16A has a long life solid state sensor. The CM-16A will go into a Trouble Fault when the sensor has expired. All 
maintenance and repair of products manufactured by 3M™ Macurco™ are to be performed at the 3M Macurco Service Center. 
3M™ Macurco™ does not sanction any third-party repair facilities.

TESTING

The CM-16A should be tested monthly by pushing the TEST/RESET switch; see TEST/RESET switch. Normally this will be the 
only test required for the CM-16A and is the recommended way to test the unit or units after installation. All CM-16A units are 
factory calibrated and 100% tested for proper operation. The unit also has the ability to automatically self test and does so 
every 2 1/2 minute cycle. If the unit detects an improper voltage or inoperable component it will default into Trouble mode. See 
TROUBLE INDICATOR section. Check that the CM-16A status indicator light is illuminated (GREEN) continuously. If not, do not 
proceed with the tests. Though there is no field calibration procedure for this unit, there is an optional field test procedure

.

 

CLEANING

The CM-16A should be cleaned using the soft brush attachment of your vacuum cleaner. The CM-16A should be tested after 
cleaning to ensure the unit is operating normally. 

SENSOR POISONS

The gas sensor in the detector is designed with extreme sensitivity to the environment. As a result, the CO sensor may be 
damaged if it is exposed to a direct spray from aerosols such as paints, silicone vapors, etc., or to a high density of corrosive 
gases such as hydrogen sulfide or sulfur dioxide for an extended period of time. The sensor may react to chemicals such as 
ammoniated cleaning agents, volatile solvents and hydrogen gas. In sufficient concentration, these chemicals may cause a 
false alarm.

CAUTION:

 This detector will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may 

be present in other areas. Accommodation spaces should be well ventilated when household cleaning supplies or similar 
contaminants are used.

3M FIXED GAS DETECTION PRODUCTS LIMITED WARRANTY

3M™ Macurco™ warrants the CM-16A gas detector will be free from defective materials and workmanship for a period of 
two (2) years from date of manufacture (indicated on the inside cover of the CM-16A), provided it is maintained and used in 
accordance with 3M™ Macurco™ instructions and/or recommendations. If any component becomes defective during the 
warranty period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below. 
This warranty does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, 
accidental or otherwise. The above warranty is in lieu of all other express warranties, obligations or liabilities. THE IMPLIED 
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF FIVE (5) YEARS 
FROM THE PURCHASE DATE. 3M™ Macurco™ shall not be liable for any incidental or consequential damages for breach 
of this or any other warranty, express or implied, arising out of or related to the use of said gas detector. Manufacturer or its 
agent’s liability shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of 
the goods and repayment of the price, or repair and replacement of non-conforming goods or parts.

W

 WARNING

W

 WARNING

Summary of Contents for Macurco CM-16A

Page 1: ...ser Instructions may adversely affect product performance and result in sickness or death For proper use see User Instructions or call 3M in U S A 1 800 243 4630 In Canada call Technical Service at 1 800 267 4414 Important Keep these User Instructions for reference FOR MORE INFORMATION In United States contact Website www 3M com OccSafety Technical Assistance 1 800 243 4630 For other 3M products 1...

Page 2: ...ot Use For 4 General Description 4 Features 5 Specifications 5 INSTALLATION AND OPERATION INSTRUCTIONS 5 Location 5 Installation 6 Power Up 8 Operation 8 Alarms 8 Reset Silence Switch 9 Trouble Indicator 10 Errors 10 MAINTENANCE 10 Testing 10 Cleaning 11 Sensor Poisons 11 3M GAS DETECTION PRODUCTS WARRANTY 11 TABLE OF CONTENTS ...

Page 3: ...l Safety and Health Administration OSHA commercial or industrial standards To help avoid false alarms the CM 16A is not intended for low level detection below 30 ppm of carbon monoxide per UL 2034 Individuals with certain medical problems may consider using warning devices that provide audible and visual signals for carbon monoxide concentrations below 30 ppm The following symptoms are related to ...

Page 4: ...Monoxide CO The CM 16A is NOT designed to detect smoke fire or any other gas Do NOT mount the unit in the garage Do NOT mount the CM 16A where the normal ambient temperature is below 40 F 4 4 C or exceeds 100 F 37 8 C or within 5 feet 1 5 meters of a cooking or heating appliance The Alarm Control Panel must be dedicated to CO detection or have alarm devices that provide a distinctive alarm for car...

Page 5: ...two screws inside the CM 16A s mount on a two gang old work box or a 4 X 4 electrical box provided by the installer 2 The detector may be installed on either a ceiling or a wall If installed on a peaked gabled or sloped ceiling it should be located about 3 feet from the highest point The unit can be placed vertically or horizontally on a wall so the information on the front of the CM 16A can be re...

Page 6: ...are aware they are not well they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance Young children and household pets may be the first affected Transient CO situations can occur 1 Excessive spillage or reverse venting of fuel burning appliances caused by outdoor ambient conditions such as a Wind direction and or velocity including high...

Page 7: ... CM 16A status indicator light is illuminated GREEN continuously If not do not proceed with the tests Though there is no field calibration procedure for this unit there is an optional field test procedure CLEANING The CM 16A should be cleaned using the soft brush attachment of your vacuum cleaner The CM 16A should be tested after cleaning to ensure the unit is operating normally SENSOR POISONS The...

Reviews: