background image

Liquid 

Outlet 

or Inlet

Vacuum or 

Sweep Gas

Vacuum or 

Sweep Gas

Liquid 

Outlet 

or Inlet

Liquid 

Outlet 

or Inlet

Vacuum or 

Sweep Gas

Vacuum or 

Sweep Gas

Liquid 

Outlet 

or Inlet

Steps:

1.  Mount contactor as shown below.
2.  Refer to start-up procedures below for each mode of operation.

Notes:

• 

The liquid pressure should always be higher than the gas pressure inside the contactor.

• 

Liquids entering the membrane contactor should be prefiltered at 5 micron absolute at 

99.9% removal (beta 1000).

Correct Mounting Position and Port Identification

Start-up Procedures

 | 3M

 Liqui-Cel

 MM 0.5x1 and 0.75x1 Series Membrane Contactors

MM-0.5x1 Series

Polycarbonate Housing

Polyethylene Housing 

Sweep (Strip) Gas with Vacuum (Combo)  

Mode 

(applies only to the 0.5 x 1 Contactor)

1.  Set the gas delivery pressure to the 

contactor at ≤ 1 psig (0.07 barg).

2.  Connect sweep gas to contactor via one of 

the ports marked Vacuum or Sweep Gas.

3.  Start sweep flow and adjust flow rate by 

adjusting the appropriate valve. Typical 

sweep flow rate range for 0.5x1 in 

combo mode is 10-100 Std cc/min.

4.  Connect vacuum to the contactor via 

the second port marked Vacuum or 

Sweep Gas.

5.  Start vacuum pump.
6.  Adjust absolute gas pressure on vacuum 

side to desired level. 

Vacuum Only Mode

1.  Start vacuum pump following vacuum 

pump manufacturer's instructions.

2.  Apply vacuum to the membrane 

contactor by opening the appropriate 

valve. For MM-0.5x1 series membrane 

contactors, vacuum can be applied to 

both gas ports together, or to one port 

while keeping the other port capped off.

3.  Adjust absolute gas pressure on the 

vacuum side to the desired level at the 

vacuum port on the contactor.

Vacuum or 

Sweep Gas

Liquid Outlet 

or Inlet

Liquid Outlet 

or Inlet

Vacuum or 

Sweep Gas

Vacuum or 

Sweep Gas

Liquid Outlet 

or Inlet

Liquid Outlet 

or Inlet

Vacuum or 

Sweep Gas

Start-up Procedures
A.   General start-up instructions for the  

liquid phase. 

Note: 

Liquid flows on the shellside. The liquid 

pressure should always be higher than the gas 

phase pressure inside the contactor. 

1.  Connect the liquid in/out ports and the 

vacuum/sweep ports as shown in the 

diagrams above.

2.  Slowly introduce liquid to the contactor, 

making sure that the liquid inlet pressure 

and liquid flow rate through the 

contactor never exceed the respective 

maximum operating limits.

B.   General start-up instructions for the 

sweep (strip) gas and vacuum phase.
Sweep (Strip) Gas Mode 

(applies only to the 0.5 x 1 Contactor)

1.  Set the gas pressure in the contactor to the  

lowest possible level by adjusting the 

appropriate valve in the gas delivery system.

2.  Set the recommended sweep flow rate 

by adjusting the appropriate valves. The 

typical sweep gas flow rate range for the 

0.5 x 1 is 50-500 std. cc/min.

3.  Introduce sweep gas into the contactor.

 Note:

 If using compressed air, make sure  

it is oil free and air temp is < 35°C. A 0.2  

micron filter is recommended with any gas.

• 

Gas entering the contactor should be filtered at 0.2 micron absolute at 99.9% removal  

(beta 1000) for high-purity applications. Filtration at 1 micron absolute at 99.9% removal  

(beta 1000) may be sufficient for industrial applications.

• 

Upon initial start-up, flush all pipes to drain prior to introducing liquid into the membrane 

contactors. 

• 

The vacuum pump and/or sweep gas should be on at all time unless the membrane 

contactors are completely drained.

• 

Liquid flows on shell side and sweep or vacuum are applied to the lumen side for these  

3M Liqui-Cel MM-Series Membrane Contactors.

Liquid Inlet or 

Outlet

Liquid Outlet 

or Inlet

Vacuum

MM-0.75x1 Series 

(Can only be operated in vacuum mode.)

Product

Maximum Pressure*

Maximum Flow Rate

0.5 x 1

3.1 barg, 25°C  

(45 psig, 77°F)

30 ml/min

0.75 x 1

3.1 barg, 25°C  

(45 psig, 77°F)

200 ml/min

* using 50 torr (mm Hg) vacuum on lumenside.

Summary of Contents for Liqui-Cel MM 0.5x1 Series

Page 1: ...ors dry at temperatures 50 C 122 F but preferably at lower temperature such as 35 C 95 F to not risk reduced lifetime Membrane contactors should always be stored above freezing temperatures and if stored at low temperature they should be allowed to equilibrate to room temperature before use Do not allow membrane contactors containing microporous hollow fiber membranes to come into contact with sur...

Page 2: ... Liquid Outlet or Inlet Vacuum or Sweep Gas Start up Procedures A General start up instructions for the liquid phase Note Liquid flows on the shellside The liquid pressure should always be higher than the gas phase pressure inside the contactor 1 Connect the liquid in out ports and the vacuum sweep ports as shown in the diagrams above 2 Slowly introduce liquid to the contactor making sure that the...

Page 3: ... Liquid Outlet or Inlet Vacuum or Sweep Gas Start up Procedures A General start up instructions for the liquid phase Note Liquid flows on the shellside The liquid pressure should always be higher than the gas phase pressure inside the contactor 1 Connect the liquid in out ports and the vacuum sweep ports as shown in the diagrams above 2 Slowly introduce liquid to the contactor making sure that the...

Page 4: ...ors dry at temperatures 50 C 122 F but preferably at lower temperature such as 35 C 95 F to not risk reduced lifetime Membrane contactors should always be stored above freezing temperatures and if stored at low temperature they should be allowed to equilibrate to room temperature before use Do not allow membrane contactors containing microporous hollow fiber membranes to come into contact with sur...

Reviews: