VENESSE 

Comfort

 

VCV-B-25E, VCV-B-25F, 

VCV-B-25W, VCV-B-25S

Summary of Contents for VENESSE Comfort VCV-B-25E

Page 1: ...EN Full manual installation 2 VENESSE Comfort VCV B 25E VCV B 25F VCV B 25W VCV B 25S ...

Page 2: ...nd then adhere to them The manufacturer reserves the right to make changes including to technical documentation without prior notice Save this user manual for further use The instructions in this manual are a part of the product Conformity disclosure VCV air curtains adhere to the following European Norms EN EN 55014 1 EN 55014 2 EN 60335 1 EN 60335 2 30 EN 61000 3 2 EN 61000 3 3 EN 61000 6 3 You ...

Page 3: ...the supplier Never install a damaged air curtain If you do not unpack the air curtain immedi ately after delivery it must be stored in a dry indoor environment with an ambient temper ature between 0 C and 40 C 2 2 UNPACK THE AIR CURTAIN If the air curtain has been transported at temperatures below 0 C it will be neces sary to let it sit for at least 2 hours under nor mal operating conditions after...

Page 4: ...er Air curtain dimensions mm Service cover Anchor stand dimensions mm Locking bolt Anchor stand part 2 Anchor stand part 1 Anchor stand covers Exhaust grid 100 130 90 72 53 51 300 45 75 2457 180 40 9 288 521 521 212 300 68 606 130 5 x 1 2 ...

Page 5: ...equipment The value in parentheses is for two sided installation of the air curtain Two sided installation Acoustic pressure at a distance of 3 m from the air curtain With water temperature gradient of 90º 70 C and temperature of intake air at 18 C Air curtains with electrical heater Air curtains with a water coil for a water temperature gradient of 90º 70 C and at a suction air temperature of 18 ...

Page 6: ...air temperature of 18 C Type VCV B 25W 5100 33 8 37 6 0 41 7 Air output m h kW C l s kPa Heat output Output temperature Water flow Pressure loss Type VCV B 25W 5100 26 4 33 4 0 32 5 Air output m h kW C l s kPa Heat output Output temperature Water flow Pressure loss Type VCV B 25W 5100 19 29 0 23 4 Air output m h kW C l s kPa Heat output Output temperature Water flow Pressure loss The warm water te...

Page 7: ...hese mate rials should not block the intake or outlet openings For air curtains with an electric heater safe distances from building structural surfaces and flammable objects are as follows the safe distance for flammable materials in the direction of the main air flow i e behind the outlet louvers is 500 mm the safe distance for flammable materials above the air curtain is 500 mm the safe distanc...

Page 8: ...e corresponding size 6 1 5 Bolt the anchor stand part 2 to the air curtain At least 4 size M5 bolts included in delivery A No 10 wrench 6 1 6 Slide the air curtain onto its stand part 1 Slide the air curtain with one anchor stand part 2 onto the fastened anchor stand part 1 and immediately secure the air curtain in the anchor stand with 4 vertically placed size M8 bolts Included in delivery Keep t...

Page 9: ...s 100 C The maximum pressure is 1 6 MPa We recommend installing a stop valve on the intake and outlet of the heater to allow the water supply to be shut off The water coil is equipped with two air release valves which can also be used for bleeding and are located at each end of the water coil 6 2 1 Regulating the water coil with a ZV 3 three way valve Regulation of the VENESSE Comfort air cur tain...

Page 10: ... to installation check to see if the ter minal markings correspond to the mark ings on the electrical connections diagram When in doubt contact your supplier and do not connect the air curtain under any circumstances Never reach inside the air curtain unless the main electrical supply has been turned off If the product is connected to any con trol system other than the original one the regulation ...

Page 11: ... must be placed in the electrical supply network disconnecting all poles of the network The electrical enclosure of the curtain is IP20 VENESSE Comfort air curtains are equipped with an 8A rated fuse This safety fuse protects the electronic panel and fans It is located on the electrical board next to the connectors for the door contact switches and other switches 6 4 INSTALL THE CONTROL PANEL 15 1...

Page 12: ...cable through the passage you have cut and fasten the rear part of the panel to the wall 6 4 5 Connect the communication cable to the electronics board located in the front cover of the panel 6 4 6 Place the front cover with the electronics to the upper latches of the control panel box and snap the cover into the lower latches 6 4 7 Fasten the bolt on the under side of the control panel 6 4 8 Conn...

Page 13: ... circuiting The cable connector must not come into contact with water or any other liquid 6 5 CONNECT THE EXTERNAL COMPONENTS Optional accessories Wiring examples all types of air curtain When connecting external components the electricity to the air curtain must be turned off All external control components must be connected according to the electrical schematic The connectors must be connected t...

Page 14: ...aximum length 50 m Three conductor power cable with a diameter of 1 5 mm Connector on the air curtain 15 16 Not included in delivery The timer switch is modified for attachment on a DIN rack Placement in the distribution box is recommended The timer switch must be powered by its own supply Isolated switching contact with a maximum voltage of 12V Cable Dual core cable with a diameter of 0 5 mm Maxi...

Page 15: ...lve Switching contact without potential with max voltage 230 V CABLE Three core power cable with diameter of 1 5 mm 230 50Hz Air curtain clamps TER L N Not included Room thermostat for the switching of the device depending on the tem perature set in the measured location Switching contact without potential with max voltage 230 V CABLE Twin core cable with a diameter of min 0 5 mm Maximum length 50...

Page 16: ...e works for connecting the air curtains to one another and to the control panel DK Door Switch SH Time switch Chained air curtains can be supplemented with these components Timer switch SH Door switch DK 6 7 COVERING THE AIR CURTAIN After connecting the power supply the water intake and outlet and all external control elements close and secure the air curtain s service cover The timer switch is co...

Page 17: ...tion and maintenance guide 7 1 CONTROLS 7 1 1 Control panel VCV B 25S VCV B 25E VCV B 25F VCV B 25W 7 1 2Turningtheaircurtainonandoff Press the button to turn the air curtain on Press the same button to turn the air curtain off Settings are indicated by an illuminated LED above the button 7 1 3 Setting the fan speed Press the button to select one of three fan speeds or to turn the fan off The sett...

Page 18: ...TER P SMU OSMU etc 7 2 SET AIR FLOW DIRECTION This is set by tilting the air curtain s fan louvers in the desired direction 8 CONCLUSION After installing the air curtain thoroughly read the VENESSE Comfort Air curtain operation and maintenance guide as well as the Guide to air curtain safety If you have any doubts or questions do not hesitate to contact our sales or technical sup port department C...

Page 19: ...19 ...