TECHNICAL INFORMATION
For installation of the AC version of the regulator onto the wall, we recommend separating the internal section (electronics and trans-
former) from the regulator box for easier handling.
1.
2.
6.3. INSTALLATION AND ASSEMBLY OF ELECTRONICS
CAUTION!
•
The regulator must always be disconnected from the main power supply prior to opening the unit.
•
The installation can be carried out only by a professional with qualifications in electronics.
•
The manual must be followed, along with the laws and regulations applicable in the given country.
•
The unit must be connected to the main power source with an insulated cable with heat resistance compliant with the diameter and
applicable laws and regulations of the given country.
•
All phases of the electrical intake to the regulator must be connected via a protective power breaker corresponding to the current and
model.
•
The distance between disconnected contacts must be greater than 3 mm.
•
The nominal values of the electrical parameters of the unit are listed on the manufacturer’s label.
•
The main intake of electrical power, switching elements, accessories should be connected according to the connection schematic.
•
The connected fans may not exceed the nominal value of current of the control unit!
•
Opening and modifying the internal connection of the control unit is prohibited and can void the warranty.
•
In case of fire, it is necessary to extinguish the device with power or CO2 fire extinguisher.
•
The unit must be connected in such a way that it can be disconnected from the power supply with one piece.
Recommended breakers:
Table of minimum sizes of breakers according to the regulator model.
The suitability of the breaker always depends on the specific conditions at the site of installation. The following table is for orientation purposes only!!!
AC-C
SC-C-AC5-04
6A
SC-C-AC5-07
10A
SC-C-AC5-16
20A
AC-S
SC-S-AC5-04
6A
SC-S-AC5-07
10A
SC-S-AC5-16
20A
EC
SC-C-EC
16A
SC-S-EC
16A
•
To mount the regulator, use the corresponding anchors and
screws.
•
To preserve the IP cover of the box, use screws and washers
provided
•
Drill
•
4x screws
•
4x anchors
•
4x washers with sealing rings (included)
The regulator must be installed as shown in the pictures, i.e. with
bushing downward.
Activating remote control
1.
2.
3.
4.
5.
6.
CANL (30)
CANH (29)
+12 V
(27)
GND (28)