background image

2

3

2VV.

 Creating innovative solutions for you and your business since 1995.

1. BEFORE YOU START  

This manual includes important instructions for correct installation of 

SAVANA

 Heat units. 

Before installation of the heater unit, please read and follow all the instructions below! The 

manufacturer reserves the right to make changes to the technical documentation without pre-

vious notification. Please save the manual for further use. Instructions in this manual should 

be considered integral part of the product

EC DECLARATION OF CONFORMITY

This manual includes important instructions for correct connection of the ventilation unit. Before connect-

ing the unit, please read and follow all the instructions below! The manufacturer reserves the right to make 

changes, including the technical documentation, without previous notification. Please save the manual for 

further use. Instructions in this manual should be considered integral part of the product

For current and full version of the EC Declaration of Conformity see www.2vv.cz.

Symbols are used in the text for better orientation in the user’s manual.

Following table includes their illustration and meaning:

Symbol

Meaning

 ATTENTION!

Warning or notification

 NOTE WELL!

Important instructions 

 YOU WILL NEED

Practical tips and information

 TECHNICAL INFORMATION

Detail technical information 

Link to other section/part of the manual

Summary of Contents for SAVANA SAV-1

Page 1: ...SAVANA AC SAV 1 SAV 2 SAV 4 SAV 6 EC SAV 1 SAV 2 SAV 4 INSTALLATION AND OPERATION EN ver 3 20 04 22...

Page 2: ...rect connection of the ventilation unit Before connect ing the unit please read and follow all the instructions below The manufacturer reserves the right to make changes including the technical docume...

Page 3: ...and report the fault to the supplier immediately After unpacking please check the condition of the heater unit and other accessories In case of doubt contact your supplier Never install damaged heater...

Page 4: ...VV Creating innovative solutions for you and your business since 1995 3 MAIN PARTS 4 DIMENSIONS Water exchanger Fan Heater body A D B C Air flow direction Exhaust various Typees Heater body without co...

Page 5: ...of the attachment Dimensions in the table are in mm Type A B C D E F SAV 1 AC 455 455 350 100 408 383 SAV 2 AC 555 555 350 100 508 483 SAV 4 AC 755 755 350 100 708 683 SAV 6 AC 855 855 350 100 808 78...

Page 6: ...16 267 34 SAV 6 2R AC 5850 230 50 3 00 690 45 SAV 1 2R EC 1720 230 50 60 0 90 111 16 SAV 2 2R EC 2550 230 50 60 1 40 174 22 SAV 4 2R EC 4260 230 50 60 1 30 309 34 Type Air output Voltage Current Inpu...

Page 7: ...unit may be installed on the wall or ceiling It must be operated in indoor covered and dry premises with the ambient temperature from 5 C to 35 C and relative humidity up to 90 Heater unit is not des...

Page 8: ...8 2VV Creating innovative solutions for you and your business since 1995 6 INSTALLATION INSTALLATION OF COVERS 1 2 3 4...

Page 9: ...9 2VV Creating innovative solutions for you and your business since 1995 6 INSTALLATION INSTALLATION OF COVERS 5 1 2 3 4...

Page 10: ...he heater units and must be ordered separately For any manipulation with the heater unit protective gloves must be used to avoid injury 6 1 2 1 Allocate the wall installation point Mark wholes for fix...

Page 11: ...ews to the heater and leave holders space for holder insertion ca 1 3 of the screw length 3 Put the unit on holders and screw it in 4 Screw lower screws on and check tightness of all screws 6 1 2 2 In...

Page 12: ...be ordered separately For any manipulation with the heater unit protec tive gloves must be used to avoid injury by sharp edges 6 1 3 1 Allocate the ceiling installation point 6 1 3 2 Install the unit...

Page 13: ...let and outlet positions are marked on the heater unit shell Maximum water temperature is 110 C Maximum pressure is 1 6 MPa We suggest installation of stop valves on water inlets and outlets of the ex...

Page 14: ...sind in der Anleitung dargestellt Main electrical supply Elektrische Zuleitung KEY TO CODING SAV 4 V V rigid silver cover made of aluminium with V TECHNOLOGY lamellas D silver cover with Jet system KE...

Page 15: ...to the heater unit must be connected through a protective power circuit breaker of corresponding current and type Distances between disconnected contacts must be higher than 3 mm The heater unit must...

Page 16: ...er exchanger first followed by motor turn off when the unit is switched off Failing that there is a risk of reduced service life of the motor or its damage Should this procedure not be observed a clai...

Page 17: ...her the heater unit is duly covered Whether the regulation is connected correctly 7 1 ACTIVATION Verify basic functions of the device fan operation heating by first activation Verify other possible se...

Page 18: ...UH G2 SAV 2 1 SAV 4 FI PYTEL KRUH G2 SAV 4 1 SAV 6 FI PYTEL KRUH G2 SAV 6 1 1 3 2 4 7 3 FILTER INSTALLATION Dust filters may be added to units It is a special filtration medium from synthetic fibres K...

Page 19: ...ssary to wear protective gloves to avoid injury from sharp edges spanner size 10 mm vacuum cleaner hand brush rag non aggressive cleaning agent soap water It is recommended to carry out periodic check...

Page 20: ...It is recommended to carry out periodic checks of the unit after each 500 hours of operation and also before and after the heating season water exchanger contamination check fan condition check in pa...

Page 21: ...not fully open Open fully the stop valves Damaged fan bearings Impeller shows clearance or cannot rotate freely It is necessary to dismantle the fan and replace bearings in an authorised service or r...

Page 22: ...service intervention it is necessary to provide fault specification unit type on the label and place of installation 10 2 PRODUCT DISCHARGE FROM OPERATION DISPOSAL Before you discard the product make...

Page 23: ...NCLUSION For correct and safe use of the unit it is necessary to read this manual and comply with the above men tioned For any inquiry or request for explanation please do not hesitate to contact our...

Page 24: ...24 2VV Creating innovative solutions for you and your business since 1995 CONTACT 2VV s r o F blovka 568 533 52 Pardubice Czech Republic Website http www 2vv cz...

Reviews: