background image

31

Q-15 

Select  dialing type (0-1)

DEFAULT: Touch tone (0)

The digital communicator can dial using tones or pulse.

•  The default (0) is for touch tone (DTMF) dialing.
•  For rotary dialing, select pulse (1).

Q-16 

Select  police emergency key (0-2)

DEFAULT: Audible (1)

The Control Panel’s panic emergency button action can be programmed. The panic 
emergency button is displayed by pressing the Control Panel’s 

 button.

•  The default (1) allows the panic emergency 

button to sound an audible alarm.

•  For silent activation, select silent panic (2).
•  To disable and not display the panic emergency button, select disabled (0).

 

NOTE: Setting this programming question for silent panic (2) 
will make the POLICE button on all RF keypads silent also.

Q-17 

Select  fi re emergency key (0-1)

DEFAULT: Audible (1)

The Control Panel’s fi re emergency button can be enabled or disabled. The fi re 
emergency button is displayed by pressing the Control Panel’s 

 button.

•  The default (1) allows the fi re emergency button to sound an audible alarm.
•  To disable and not display the fi re emergency button, select disabled (0).

Q-18 

Select  emergency key (0-1)

DEFAULT: Audible (1)

The Control Panel’s emergency button can be enabled or disabled. The panel’s 
emergency button is displayed by pressing the Control Panel’s 

 button.

•  The default (1) allows the emergency button to sound an audible alarm.
•  To disable and not display emergency button, select disabled (0).

 

NOTE: If all three emergency buttons are disabled, pressing the Control Panel’s

 

 

button will display a message that the emergency buttons are disabled.

Q-19 

Select  quick arming (0-1)

DEFAULT: Enabled (1)

Quick arming allows the subscriber to arm the system without having to enter 
their User Code. (Quick arming reports as User 0 if open/close reports are sent.)

•  The default (1) allows quick arming.
•  To turn off quick arming, select disabled (0).

Q-20 

Select  swinger shutdown count (1-6)

DEFAULT: Two trips (2)

 (Required SIA CP-01 Default)

An unwanted series of multiple faults (usually caused by a bad contact or sensor) 
is called a “swinger”. Swinger shutdown sets the maximum number of alarms that 
any sensor or hardwire loop can trigger during a single arming period.

 

NOTE: CO and smoke detector alarms are not limited 
by the swinger shutdown count. Other types of 24-hour 
zones are limited by the swinger shutdown count.

•  The default (2) sets the swinger shutdown count at two trips.
•  To change the swinger shutdown count, select (1-6).

 

NOTE: This default can be changed without affecting SIA CP-01 compliance.

Q-21 

Select  siren supervision time (0-3)

DEFAULT: Disabled (0)

The wiring connection to the external sounder can be supervised. If the wiring to 
the sounder is cut for 15, 30, or 45 seconds, a bell trouble report can be sent to 
the Central Station.

•  The default (0) disables external sounder supervision.
•  To supervise the external sounder wiring, select (1) for 

15 seconds; (2) for 30 seconds; or (3) for 45 seconds.

Q-22 

Enter  CS lack of usage notifi cation time (0-255)

DEFAULT: Seven days (7)

Inactivity reports can be sent to the Central Station if the system has not been 
armed for a period of days.

•  The default (7) sets the lack of usage feature at seven days.
•  To change the lack of usage feature duration, select (1-255) days.
•  To turn off the lack of usage feature, select disabled (0).

Q-23 

Enter  radio modem network failure time (0-255)

DEFAULT: 30 minutes

 

NOTE: GSM Module must be installed to use this function.

Sets the amount of time required for triggering a trouble condition if the system 
detects that the optional GSM radio modem has lost its cellular connection. (After 
cellular service has been restored for fi ve minutes, the trouble condition will clear.)

•  The default (30) sets the failure detection time at 30 minutes.
•  To disable radio modem failure detection, select disabled (0).
•  To choose a different failure detection time, select (1-255) minutes.

Q-24 

Select  radio modem network failure causes trouble (0-1)

DEFAULT: Enabled (1)

 

NOTE: GSM Module must be installed to use this function.

Selects whether the control panel will sound and display trouble if the optional 
GSM radio modem has lost its cellular connection. The trouble sounder can be 
silenced by the user at the Control Panel (GSM trouble is logged regardless of 
this setting). When the GSM radio modem connection is restored, the trouble 
indications will automatically clear.

•  The default (1) allows radio modem failure trouble indications.
•  To turn off radio modem failure trouble indications, select disabled (0).

Q-25 

Select  radio modem network failure reports (0-1)

DEFAULT: Enabled (1)

 

NOTE: GSM Module must be installed to use this function.

If the optional GSM radio modem loses its cellular connection, the Control Panel 
can report the fault and restore via land-line if telephone reporting is enabled.

•  The default (1) allows radio modem failure/restore reporting.
•  To turn off radio modem failure/restore reporting, select disabled (0).

Q-26 

Select  auto stay (0-1)

DEFAULT: Enabled (1)

 (Required SIA CP-01 Default)

When auto stay is enabled and the system is armed in the Away Mode, if an exit/
entry sensor is not violated during the Exit Delay, the system will arm in the Stay 
Mode.

•  The default (1) enables the auto stay feature.
•  To turn off the auto stay feature, select disabled (0).

 

NOTE: The auto stay feature will not switch the system to Stay 
Mode if the system is armed to Away Mode using a key fob 
remote or remotely armed via telephone or computer.

Installer Programming

Summary of Contents for 2GIG-NTRL2

Page 1: ...Wireless Security System Installation Programming Instructions 2GIG CNTRL2 2GIG CP2 ...

Page 2: ...he ceiling Do not install smoke alarms where normal ambient temperatures are above 100 F 37 8 C or below 40 F 4 C Also do not locate alarm in front of air conditioners heating registers or other locations where normal air circulation will keep smoke from entering the detector A 2 5 2 1 Smoke Detection Are More Smoke Alarms Desirable The required number of smoke alarms might not provide reliable ea...

Page 3: ...Sounder Disable Icon 14 Backup Battery Status Icon 14 Test Mode Icon 14 Touch Screen Keypad Traffic Icon 14 GSM Radio Icon 14 Interior Sensor Open Icon 14 Programming Navigation 15 Navigation Arrows Go To Button 15 Questions without Sub options 15 Questions with Sub options 15 Questions with Data to Enter 15 Other Buttons Displayed 15 Programming Outline 16 SIA CP 01 Defaults 16 Programming Questi...

Page 4: ... requirements to qualify for a discount For an ETL smoke alarm system use only approved model smoke detectors with this Control Panel NOTE Some cities and municipalities may require an alarm system permit Check with the local authorities before installing this system NORMALLY CLOSED CONTACT NORMALLY OPEN CONTACT 2 2 K END OF LINE RESISTORS ARE OPTIONAL ON HARDWIRE LOOPS 2 2 K HARDWIRE LOOPS CAN BE...

Page 5: ...r subscribers can query and control their system using a computer browser from anywhere in the world The Alarm com server can also send messages time corrections and software updates to the Control Panel Special messages from the server are displayed to the subscriber on the Control Panel s color touch screen For home control the Control Panel s built in Z Wave radio module allows controlling and ...

Page 6: ...Flashes ORANGE when ANY sensor is open not ready to arm Flashes RED while system is armed HOME BUTTON INDICATOR THIRD HAND HANGER STRAP Hooks onto mounting plate during installation to hold the Control Panel while wiring TELEPHONE LINE MONITOR TERMINALS Terminals for connecting lineman s buttset for monitoring the telephone line MAIN RECEIVER MODULE 345 MHz receiver for wireless sensors Optional M...

Page 7: ...tery connector into the connector on the Control Panel s circuit board 14 Swing the Control Panel up placing the bottom over the lip of the mounting bracket Push the top of the Control Panel into the mounting bracket until it snaps into place then secure it with the retaining screw 15 Plug the power supply into the un switched 120 VAC wall outlet 16 Program the system as described in this manual a...

Page 8: ... second button lockout Lithium battery 345 MHz ETL Listed 2GIG GB1 Glass Break Detector Monitors for the sound of breaking glass Two test LEDs Dual shatter recognition technology thud then crash Lithium battery 345 MHz ETL Listed 2GIG SMKT2 Smoke and Heat Detector Photoelectric type detector with rate of rise and fixed 135 heat sensors Status indicator Built in 85 dBA sounder Lithium battery 345 M...

Page 9: ...M module Locking connector 2GIG ANT4X External In wall GSM Antenna Antenna installs in the wall behind Control Panel 2 foot cable Plugs into GSM module Locking connector 2GIG BATT1 Standard Battery Pack Standard battery supplied with Control Panel Also available as a replacement item Nickel metal hydride NiMH battery 2GIG BATT1X Extended Battery Pack Optional extra capacity battery Replaces standa...

Page 10: ...ormally open N O or normally closed N C End of line resistors EOLR can also be used to supervise the loops Only contacts should be used with the hardwired loops The Control Panel does not support powering external devices PIR s etc NOTE HARDWIRED LOOPS CANNOT BE USED FOR A CO OR FIRE SENSOR LOOP 1 If either of the two hardwired loops are going to be used install the contacts and route the loop wir...

Page 11: ...LCO INPUT DROP SIDE OFTHE BOX OR ANY EARTH GROUNDS 3 At the demarcation box connect the RED cable wire to the box RING and the GREEN cable wire to the box TIP 4 At the demarcation box connect the BLACK cable wire to the house telephone RING wire s and the YELLOW cable wire to the house telephone TIP wire s 5 At the Control Panel connect the cable s RED wire to the RJ31X jack s RING IN terminal and...

Page 12: ...nas simply plug the antenna connector into the GSM module The antenna will drop into the wall or mount in the attic with the cable passing through the slot in the Control Panel s mounting plate See Figures 14 15 NOTE The GSM SIM card should have been pre activated by the factory if not contact your service provider For the GSM module to function with the system it will have to be activated before ...

Page 13: ...lug the backup battery pack s connector into the connector on the Control Panel s circuit board The Control Panel will not recognize that the battery is connected until AC power is connected to the power supply IMPORTANT Applicable regulatory agencies require installation of the extended life backup battery P N 2GIG BATT1X inside the Control Panel for UL985 Household Fire applications Control Pane...

Page 14: ...re displayed To arm the system without an entry delay un check the ENTRY DELAY check box To arm silently without sounding the Exit Delay beeps check the SILENT EXIT check box Stay Mode arming always has a silent exit Menu Screen The Menu Screen shows the system status and offers buttons for ARM and TOOLBOX If any of the 24 hour emergency options are enabled an EMERGENCY button is displayed Two opt...

Page 15: ...l shortcut to help the installer access the Installer Toolbox quickly Pressing the lower right corner of the Home Screen while the system is disarmed will immediately display a code entry screen When the correct Installer Code is entered the system will go directly to the Installer Toolbox InstallerToolbox Screen The Installer Toolbox Screen displays system setup and testing buttons Main programmi...

Page 16: ...the system is being tested in Walk Test Mode the test mode icon will be displayed on the status bar Touch Screen KeypadTraffic Icon When the Control Panel is communicating to a touch screen keypad the up arrow icon is displayed When a touch screen keypad communicates to the Control Panel the down arrow icon is displayed GSM Radio Icon If the system s optional GSM radio modem is installed the GSM r...

Page 17: ...button advances to the next programming question section The arrows select the next or previous programming sub question The arrows choose values for the question or move the cursor left and right along the white data entry field Questions with Data to Enter Some of the programming questions require entering numeric or alphabetic data For devices that can be named the Control Panel contains a larg...

Page 18: ...tallation The volume setting DOES NOT affect the volume of alarm sounds 9 Press to view the second toolbox screen 10 Press BACKLIGHTTIMEOUT and set the display lighting timeout 11 Press SET DATE and SETTIME and set the calendar and clock If the GSM module is installed the date and time are set automatically 12 Press the button to return to the Home Screen After all setup and programming refer to t...

Page 19: ...t delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select cancel display 0 1 1 enabled Q 33 Select cross sensor 47 48 0 1 0 disabled Q 34 Enter cross sensor timeout in seconds 10 120 10 seconds Q 35 Select abort window dialer delay 0 2 1 30 seconds Q 36 Select bu...

Page 20: ...tion trouble report but not an alarm when the system is disarmed 06 24 hour Silent Alarm This sensor type is active independent of the system arming status The code for silent panic is sent to the Central Station but for safety there are no visual or audible indications locally that this sensor type has been triggered 07 24 hour Audible Alarm This sensor type is continuously armed 24 hours a day A...

Page 21: ... LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU 144 MIDDLE 145 MONITOR 146 MOTION 147 MOTION DETECTOR 148 MUD 149 NINE 150 NINETEEN 151 NINETY 152 NORTH 153 NOT 154 NOT READY 155 NO DELAY 156 NO ENTRY DELAY 157 NURSERY 158 OFF 159 OFFICE 160 ON 161 ONE...

Page 22: ...number 01 48 Sensor Type Exit entry perimeter interior etc Sensor Equipment Type Certain sensor types will ask for equipment type Sensor Equipment Code Sensor model door window PIR smoke detector etc Sensor Other Equipment Code Enter special equipment code only shown for sensors set as other Sensor Serial Serial number labeled on sensor manually enter or learn by sending signal Sensor Equipment Ag...

Page 23: ...R ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR insert PRESS FOR EACH WORD ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR ENTER ON KEYPAD OR PRESS TO SELECT FROM LIST OR skip edit next TO FINISH FOR THIS SENSOR THEN PRESS FOR NEXT SENSOR OR FOR Q2 CONSTRUCT R...

Page 24: ... arrows or enter the equipment type number directly on the keypad Select RF sensor equipment code DEFAULT 0000 other The equipment code is a 4 digit code that is assigned to the model of sensor being used The Control Panel will display a list of sensor models and their associated 4 digit equipment code Select the model of RF sensor being programmed for this sensor number using the or arrows or ent...

Page 25: ...E button can be used to recall the last programmed sensor s serial number The sensor number will be filled in automatically if LEARN is used Select RF sensor dialer delay 0 1 DEFAULT Enabled 1 Required SIA CP 01 Default RF sensors can trigger the communicator immediately or after a delay The delay time is set by the abort window dialer delay programming question Q 35 the default delay is 30 second...

Page 26: ... announcement and chime options for the sensor Wired Sensor Summary Screen After setting all the options for a sensor the wired sensor summary screen is displayed The screen can also be displayed for programmed sensors during wired sensor program editing by pressing the SUM button The and arrow buttons step through the wired sensor numbers The EDIT CURRENT and EDIT NEXT buttons return to sensor pr...

Page 27: ...rol Panel can be used with new or existing wired sensors If this wired sensor is new for the installation leave the default of new 0 If this wired sensor is already installed select existing 1 Select wired sensor normal state DEFAULT Not used 0 The two hardwired loops can be wired for normally open N O or normally closed N C contacts or for end of line EOL resistor The default 0 disables this wire...

Page 28: ... button RF Key Fob Summary Screen After setting all the options for a sensor the key fob summary screen is displayed The screen can also be displayed for programmed key fobs during key fob program editing by pressing the SUM button The and arrow buttons step through the key fob numbers The EDIT CURRENT and EDIT NEXT buttons return to key fob programming Pressing SKIP goes to question Q 4 RF keypad...

Page 29: ...equipment age 0 1 DEFAULT New 0 The Control Panel can be used with new or existing key fobs If this fob is new for the installation leave the default of new 0 If this fob is already installed select existing 1 Select fob emergency key 0 4 DEFAULT Disabled 0 Pressing the and buttons on a key fob at the same time for five seconds can trigger an emergency alarm The default 0 disables the emergency fu...

Page 30: ...reen After setting all the options for a sensor the RF keypad summary screen is displayed The screen can also be displayed for programmed RF keypads during RF keypad program editing by pressing the SUM button The and arrow buttons step through the RF keypad numbers The EDIT CURRENT and EDIT NEXT buttons return to RF keypad programming Pressing SKIP goes to question Q 5 Control Panel programming KE...

Page 31: ...d the Control Panel will learn the RF keypad s serial number TS1 WirelessTouch Screen Keypads For 2GIG TS1 Wireless Touch Screen Keypads press LEARN The Control Panel will display Pair with TS 1 Initiating learning process Press the TS1 keypad s PAIR WITH PANEL button Both the TS1 and the Control Panel will display The learn operation succeeded when complete The Control Panel will display RF keypa...

Page 32: ...SHIFT button accesses the pound and star symbols The P button adds a 3 second pause to the dialing NOTE If a second Central Station telephone number is programmed with question Q 41 the Control Panel will alternate between the two Central Station telephone numbers After two failed telephone dialing attempts the Control Panel will try to connect using the GSM radio module if it is installed If the ...

Page 33: ...be supervised If the wiring to the sounder is cut for 15 30 or 45 seconds a bell trouble report can be sent to the Central Station The default 0 disables external sounder supervision To supervise the external sounder wiring select 1 for 15 seconds 2 for 30 seconds or 3 for 45 seconds Q 22 Enter CS lack of usage notification time 0 255 DEFAULT Seven days 7 Inactivity reports can be sent to the Cent...

Page 34: ...r information on setting the cancel report trigger time NOTE This default can be changed without affecting SIA CP 01 compliance Q 33 Select cross sensor 47 48 0 1 DEFAULT Disabled 0 The Control Panel can be programmed so sensors 47 and 48 must both be violated during a set time to trigger an alarm This is called cross sensor verification When enabled if only one sensor 47 or 48 is violated the ala...

Page 35: ...esses B C D E and F characters Q 42 Select remote control phone 0 3 DEFAULT Data and voice 3 This setting controls remote telephone access to the system The data option is for the installer It allows access for programming and operating the system with custom PC downloader software The voice option is for the subscriber It allows the subscriber to call the system from an off site phone to get the ...

Page 36: ...s trouble beeps from sounding from 10 pm to 9 am The trouble s will still be displayed and immediately reported to the Central Station and can be acknowledged but they won t sound beeps until after 9 am If the trouble condition s self clear or are acknowledged before 9 am no trouble beeps will sound after 9 am the conditions will still be recorded in the event log The default 1 suppresses trouble ...

Page 37: ... shutdown until the time of disarm and the sensor is closed The default 0 prevents alarm restore reports To allow alarm restore reports select enabled 1 Q 58 Select trouble restore reports to CS 0 1 DEFAULT Enabled 1 Trouble restore reports can be sent to the Central Station when any sensor trouble condition clears The default 1 allows trouble restore reports To turn off trouble restore reports se...

Page 38: ...ylight saving end week Q 71 Select system tamper causes trouble 0 1 DEFAULT Enabled 1 The Control Panel s case has a tamper switch that detects if the case has been opened The system can be programmed so that a tamper switch activation will cause a trouble indication if the system is disarmed and an alarm if the system is armed The default 1 allows the Control Panel tamper switch to trigger troubl...

Page 39: ...visible 1 The Z Wave home services feature can be enabled or disabled with various remote control access options The default 1 displays the SERVICES button but will show a message that the feature is currently disabled and the user should call the installer To hide the SERVICES button select disabled and hidden 0 To show the SERVICES button and disable off site remote control select 2 To show the ...

Page 40: ...0 1 DEFAULT Disabled 0 This setting enhances system operation in personal emergency applications and also provides the dealer with the option of the siren sounding until the bell cut off or to the end of a two way voice session The default 0 will cause the siren to resume after two way audio if the bell cut off timer has not expired Enable 1 will cause the siren to shut off after a two way audio s...

Page 41: ...t permitted 4 Setup each User Code with the User Access Option Screen Each User Code can be set to be currently valid or not or to have conditional validity depending on a time and date schedule Refer to the User s Guide for details on setting User Code Access Schedules 5 Press BACK when finished 6 Press BRIGHTNESS VOLUME Set the level for the display brightness Set the chime voice volume Press OK...

Page 42: ...come active again To re enable the sounder manually follow these steps 1 From the Installer Toolbox Screen press ENABLE SOUNDER 2 A confirmation screen will be displayed Press OK Zone ReportingTest To verify that the Central Station will correctly receive reports from each zone type perform the following tests 1 Inform the Central Station that test signals will be sent 2 Trigger a 24 hour fire sen...

Page 43: ...test report to the Central Station Exiting the Walk Test Mode will send a stop test report to the Central Station To perform a walk test follow these steps 1 From the Installer Toolbox screen press WALKTEST 2 The icon will display on the Control Panel s status bar and a beep will sound every 30 seconds to indicate that the system is in Walk Test Mode 3 Each of the sensors and their status will be ...

Page 44: ...e Installer Toolbox TelephoneTest The telephone test checks the land line connection to the Central Station through the Control Panel s built in digital communicator The test is accessed through the User Toolbox screen 3 Follow these steps to test the digital communicator 1 On toolbox screen 3 press the TELEPHONETEST button 2 Enter the Master User Code and the system will display the Telephone Tes...

Page 45: ...es Industry Canada Notices NOTICE The ringer equivalence number REN assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the ringer equivalence numbers of all the devices does not exceed 5 NO...

Page 46: ...t exit delay restart 0 1 1 enabled Q QUESTION DEFAULT Q 28 Select quick exit 0 1 1 enabled Q 29 Enter periodic test in days 0 255 30 days Q 31 Enter cancel time in minutes 5 255 5 minutes Q 32 Select cancel display 0 1 1 enabled Q 33 Select cross sensor 47 48 0 1 0 disabled Q 34 Enter cross sensor timeout in seconds 10 120 10 seconds Q 35 Select abort window dialer delay 0 2 1 30 seconds Q 36 Sele...

Page 47: ...N 126 LAUNDRY 127 LEFT 128 LEVEL 129 LIBRARY 130 LIGHT 131 LIGHTS 132 LIQUOR 133 LIVING 134 LOADING 135 LOCK 136 LOFT 137 LOW WORD 138 MAIN 139 MAINTENANCE 140 MASTER 141 MEDICAL 142 MEDICINE 143 MENU 144 MIDDLE 145 MONITOR 146 MOTION 147 MOTION DETECTOR 148 MUD 149 NINE 150 NINETEEN 151 NINETY 152 NORTH 153 NOT 154 NOT READY 155 NO DELAY 156 NO ENTRY DELAY 157 NURSERY 158 OFF 159 OFFICE 160 ON 16...

Page 48: ...46 Notes ...

Page 49: ...47 Notes ...

Page 50: ... panel internal features 4 Control panel location 5 Control panel location height 5 Control panel mounting 11 Control panel mounting plate 8 Control panel wiring 11 Control panel wiring diagram 2 Cross sensor 32 Cross sensor timeout 32 CS Lack of usage notification time 31 D Daylight saving end month 36 Daylight saving end Sunday 36 Daylight saving scheme 36 Daylight saving start month 36 Daylight...

Page 51: ...J31X telephone jack 9 S Saving programming 39 Security screen 12 Select keyfob remote arming mode on system not ready 38 Select siren mode 38 Sensor signal loss through materials 5 Sensor types 18 Sensor zones 18 Services menu requires master code 38 Set date time 39 SET TIME button 39 SHIFT button 15 Signal strength indicators 41 Silent burglary sensor type 18 Silent panic burglary listen only 30...

Page 52: ...v1 9 233497 E Copyright 2012 ...

Reviews: