A6V10328217_en--_f

MXL Line Card

Installation Instructions
Model MLC

INTRODUCTION

The Model MLC MXL Line Card loop driver from Siemens
Industry, Inc., is a module that allows MXL intelligent
addressable smoke detectors, manual stations, monitor
devices, and control devices to interface to the FireFinder-
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
System. The  MLC  uses two consecutive addresses on the
HNET network. The application program that is loaded into
the on-board microprocessor controls the MLC operation. An
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular
system can support a maximum of 2500 MXL intelligent
field devices using up to 25 MLC cards.

The MLC contains nine diagnostic LEDs. Ground fault
detection is provided. A USB port is included to allow
firmware upload via the front panel.

All field devices connected to the MLC are addressed and
tested using the Device Programming Unit (DPU) or the
FPI-21 Programmer/Tester. The select system setting on
the DPU and FPI-32 must be set to MXL.

OPERATION

The MLC initializes, operates, and maintains all devices
residing on the loop. The MLC communicates all relevant
device and event information, such as alarms and troubles,
to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3 (Cerberus PRO Modular).
The sensitivity of any intelligent smoke detector and the
logic functions of any intelligent output devices can be
checked and adjusted from the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) through the MLC. All information
about the devices on the loop can be displayed on the PMI/
PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety
Modular), FCM2041-U3 (Cerberus PRO Modular). To see
the available information for each device on the loop, refer
to the FireFinder-XLS IOM Manual, P/N 315-033744, the
Desigo Fire Safety Modular IOM, Document ID A6V11231620,
 or the Cerberus PRO Modular IOM, Document ID A6V11231627.

The MLC supports two separate circuits of MXL intelligent field devices. Each circuit
can monitor and control up to 60  intelligent devices as well as device accessories
(relay bases, audible bases, and remote lamps) in any combination. Each circuit has a
separate address on the HNET network. The installer sets the address on the module
for the first circuit which can be either odd or even. A consecutive address is auto-
matically assigned to the second circuit internally.

MLC

ALARM

TROUBLE
GND FAULT

TROUBLE

EXP CIRCUITS

CARD FAIL
HNET FAIL

RESET

POWER

HNET

HUNDREDS

TENS

ONES

TROUBLE
GND FAULT

MAIN CIRCUITS

USB

Figure 1

MLC Line Card

Summary of Contents for MLC

Page 1: ...ates and maintains all devices residing on the loop The MLC communicates all relevant device and event information such as alarms and troubles to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the PMI PMI 2 PMI 3...

Page 2: ...IL Yellow Normally OFF When illuminated indicates hardware failure on the card or unsuccessful firmware upload During firmware upload this LED should blink HNET FAIL Yellow Normally OFF When illuminated indicates that the HNET communica tion with the MLC has terminated ALARM Red Normally OFF When illuminated indicates that the MLC has detected an alarm TROUBLE Yellow Normally OFF When illuminated ...

Page 3: ...d cage Refer to Figure 2 Insert the MLC card into the card guides rightside up lettering on the front panel is legible Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage aligned properly The card can only plug in one direction to the card cage if it does not align DO NOT FORCE the card Place thumb...

Page 4: ...rrent version of MLC software in an installed MLC go to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular and press the Menu button select Report press the More Info button and select the MLC at that address Press the Configuration soft key press Appl Rev for the Application Version and press View WIRING All field wiring to the MLC is connected to the te...

Page 5: ... DCLA LOOP 1 INITIATING DEVICE CC 5 CC 2 LOOP 2 OPERATES IN FULL CONFORMANCE WITH STYLE 4 ULC DCLB INITIATING DEVICE Connect 24V from the PSC 12 PSX 12 to terminal 17 and 24V from the PSC 12 PSX 12 to terminal 18 of the slot in the CC 5 CC 2 where the MLC will be installed Refer to Figure 3 Each device loop circuit can be wired Class B or Class A MLC field circuit wiring does not require twisted s...

Page 6: ...N P 0 3 1 1 P F T P D A B D h t i w S R 3 X B D S 3 B D r o 1 1 X B D A S R 1 1 X B D 1 1 B D 1 2 9 5 9 0 5 1 3 N P 1 2 9 5 9 0 5 1 3 N P 0 6 1 1 T P F T P D A B D h t i w S R 3 X B D S 3 B D r o 1 1 X B D A S R 1 1 X B D 1 1 B D 1 2 9 5 9 0 5 1 3 N P 1 2 9 5 9 0 5 1 3 N P 0 6 P C I 1 7 4 2 9 0 5 1 3 N P 2 1 6 B P C I 6 0 3 5 9 0 5 1 3 N P 2 1 H 1 1 I L I S R 3 X B D S 3 B D 7 8 3 5 9 0 5 1 3 N P ...

Page 7: ...o n n a c e g a s u y t i r u c e s h t i w s e c i v e d I R T 8 4 6 8 L U o t d e t s i l y l s u o i v e r p s e c i v e d h t n o i t i d E CZM 1 1B6 Compatibility Table 3 contains compatibility data for the CZM 1 1B6 when the CZM 1 1B6 is configured to perform alarm verification Each detector model is listed with the allowable Zeus alarm verification delay range in seconds This setting is mad...

Page 8: ...ion feature but can be used when alarm verification is disabled Each detector is assigned a category Do not mix detectors from different categories on the same circuit ELECTRICAL RATINGS t n e r r u C e n a l P k c a B V 4 2 A m 8 2 t n e r r u C V 4 2 l a n i m r e T w e r c S e c i v e d r e p A m 5 1 A m 0 9 t n e r r u C e n a l P k c a B 2 6 A m 5 1 t n e r r u C y b d n a t S V 4 2 e c i v e...

Page 9: ...ce and this paragraph are duplicated in all such forms and that any documentation advertising materials and other materials related to such distribution and use acknowledge that the software was developed by Carnegie Mellon University The name of the University may not be used to endorse or promote products derived from this software without specific prior written permission THIS SOFTWARE IS PROVI...

Page 10: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V10328217_en _f P N A5Q00066395 ...

Reviews: