background image

T.M.  •  Rev. 9-91  •  ©Honeywell Inc. 1991  •  Printed in U.S.A.  •  Form Number 63-2287—1

ST7700

Keyboard and Display Module

Boiler Control System 7700

CONTENTS

Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 3
Checkout ......................................................... 8

The Honeywell BCS 7700 is a microprocessor

based integrated control system for gas, oil, or
combination fuel single burner applications. The
BCS 7700 consists of a Chassis Module, Pro-
gram Module, Keyboard and Display Module,
Flame Amplifier, Solid State Sensors (Fuel Oil
and Water Temperature, Steam Pressure, Gas
Pressure, and Oil Pressure) and a Firing Rate
Motor. The BCS 7700 provides levels of safety,
functional capability and features beyond the
capacity of conventional controls. Functions of
the BCS 7700 include automatic burner sequenc-
ing, flame supervision, system status indication
and system diagnostics.

The Keyboard and Display Module is the pri-

mary user interface to the BCS 7700. The Key-
board and Display Module is used to configure
the system modules, adjust system operating pa-
rameters, and monitor system status.

2 row x 40 character Liquid Crystal Display.

3 Status LEDs.

Manual Firing Rate Control.

Alarm Silencing Switch.

Summary of Contents for ST7700

Page 1: ... Fuel Oil and Water Temperature Steam Pressure Gas Pressure and Oil Pressure and a Firing Rate Motor The BCS 7700 provides levels of safety functional capability and features beyond the capacity of conventional controls Functions of theBCS7700includeautomaticburnersequenc ing flame supervision system status indication and system diagnostics The Keyboard and Display Module is the pri mary user inte...

Page 2: ...GS Voltage and Frequency 24 Vac 20 15 50 60 Hz Power Dissipation VA Consumption 2 watts maxi mum 2 2 VA maximum TERMINAL RATINGS Power 24 Vac 20 15 Earth Ground ControlBus a b c 5 Vdc 250 mA maximum ENVIRONMENTAL RATINGS Ambient Temperature Operating 32 F to 130 F Storage 30 F to 150 F Humidity Operating 85 RH continuous noncondensing Vibration Continuous 0 5G environment Dimensions See Fig 1 Weig...

Page 3: ...PLAY MICROCOMPUTER A B C A B C KEYBOARD 120VAC 24VAC 40VA INDICATES FEEDBACK SENSING TO OPTOISOLATORS WIRING SHOWN FOR INFRED FLAME DETECTOR FOR C7027 ULTRA VIOLET FLAME DETECTOR WIRE AS NOTED BELOW ULTRA VIOLETDECTECTOR BLUE LEAD TERMINAL 31 ULTRA VIOLET DETECTOR WHOTE LEAD TERMINAL 30 THE ULTRA VIOLET FLAME DETECTOR WIRING IS POLARITY SENSITIVE REVERSING THE LEDS WIRES MAY DAMAGE THE SENSOR FOR ...

Page 4: ... 8 9 10 11 12 13 14 15 J2 J1 J4 J3 J9 BMSI CAPS LMTS LWCO MOV BS MGV BURNER MOTOR STARTER 120V LINE HOT LINE COMMON 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 G T Y CHASSIS MODULE IGNITOR GAS PILOT VALVE OIL MAIN VALVE GAS MAIN VALVE A B C OIL GAS PURGE VALVE ATOMI ZING AIR COMP 56 55 54 53 52 51 50 49 48 UNUSED L2 TERMINAL 50 TERMINAL 51 OIL SELECT GAS SELECT OIL LINE PURGE VALVE L1 ATOMIZIN...

Page 5: ...and Display Module can be mounted on the door panel of an electrical enclosure 2 Select the location on the door panel be aware that the Keyboard and Display Module extends 1 4 inches behind its mounting surface 3 Using the Keyboard and Display Module as a tem plate mark the four screw locations Drill the pilot holes Provide for an opening on the panel door for mounting see Fig 1 4 Secure the Keyb...

Page 6: ...peration The AUTO MANUAL key function has control of the BCS 7700 only when in the Operate mode When in the Program mode the AUTO MANUAL key has no func tion AUTO automatic control allows the BCS 7700 to sequence the burner based on safety sequence logic and rate control of the BCS 7700 The system starts and stops the burner automatically see Fig 8 MANUAL manual control allows manual adjust ment o...

Page 7: ... AUTO MANUAL KEY FlameSignal 2 5V OperSetPoint 185 PSI Man 190 PSI Run 30 Rate M1454 IN AUTO AND OPERATE MODE PLACE SYSTEM IN AUTOMATIC MODE AUTO MANUAL KEY Auto 190 PSI Run 30 Rate IN MAN AND OPERATE MODE CHANGE FROM MANUAL CONTROL TO AUTOMATIC CONTROL FlameSignal 2 5V OperSetPoint 185 PSI FlameSignal 2 5V OperSetPoint 185 PSI MOVE CURSOR TO RATE TO ADJUST FIRING RATE Man 190 PSI Run 30 Rate Flam...

Page 8: ...en 0 00V Standby GAS Auto 190 PSI OperSetPoint 185 PSI Auto 190 PSI Standby GAS DiagnosticInfo Yes OperSetPoint 185 PSI Auto 190 PSI Standby GAS DiagnosticInfo No M1117 OperSetPoint 185 PSI IN OPERATE MODE DIAGNOSTIC INFORMATION PARAMETER ACCESSED ACCESS DiagnosticInfo VALUE NO KEY SELECT DiagnosticInfo FILES KEY Auto 190 PSI Standby GAS DiagnosticInfo No ENTER Diagnostic FILES ENTER KEY OperSetPo...