background image

P32509-10-0G0-01

Software-Version

ZTMOD.01.0V02.xx

Subject to change

without notice

2014-05-07

Mounting and Connection Instructions

Door module, 12V DC, RS485

Door module, 230V AC, RS485

Item no. 026593.10 / 026594.10

Summary of Contents for 026593.10

Page 1: ...09 10 0G0 01 Software Version ZTMOD 01 0V02 xx Subject to change without notice 2014 05 07 Mounting and Connection Instructions Door module 12V DC RS485 Door module 230V AC RS485 Item no 026593 10 026594 10 ...

Page 2: ... ...

Page 3: ...t mounting diagram 13 4 Mounting 14 4 1 Mounting of Door module RS485 026593 10 14 4 2 Mounting of Door module RS485 026594 10 14 5 Technical data 15 5 1 Technical data 026593 10 Door module 12V DC RS485 15 5 2 Technical data 026594 10 Door module 230V AC RS485 15 6 General connection diagram 16 6 1 Description of fuse jumpers and LEDs 17 6 1 1 Fuse SI1 17 6 1 2 Jumpers for level definition 17 6 1...

Page 4: ... only in accordance with regulations and in technically perfect and orderly installed condition according to the technical information The manufacturer is not liable for damage caused by improper use The accompanying documents and specific system documentation are to be deposited and kept in a safe place Installation programming as well as maintenance and repair work may only be carried out by aut...

Page 5: ...y even if MultiAccess for Windows is not running When the software is restarted stored events are downloaded automatically The door module is used to control one door or two doors only with IQ MultiAccess beginning with V3 All peripheral door devices are connected to the door module The door module uses the module bus and communicates with the ACS 8 via the integrated RS 485 interface The ACS 8 co...

Page 6: ...same reading technology magnetic card reader contactless reader or chip card reader The door module recognizes by means of the door monitoring contact in the door strike whether the door was open too long or the door was opened by force 1 2 1 Example MultiAccess for Windows With MultiAccess for Windows the door module can administrate one door Configuration example 1 Just the access to a room is c...

Page 7: ... zone makes it possible to release the door lock manually Configuration example 2 Room access and exit are controlled by two readers The antipassback option can be activated Thus the present location of each person can be identified Configuration example 3 a Just the access to two rooms is controlled via a reader each It is possible to exit the room without identification b A room with tow doors T...

Page 8: ... equiped with a protective diode 2 2 Grounding shielding Use shielded cable and a suitable shielding connection for protection against electromagnetic interference couplings occurring for example when switching electric appliances on and off Make sure that the cable shields in the distribution boxes are connected so that there are no links to other potentials In the door module all shields should ...

Page 9: ... bus capability Up to 32 devices can be connected which can be transmitters as well as receivers The max cable lenght of the RS 485 bus data line can be up to 1200m The door module has no electrically isolated RS485 interface If problems with data transmission to the ACS 8 should occur a potential separation module Item No 026595 10 should be used see chapter 10 note the additional installation in...

Page 10: ...rth potentials distributed on the system 2 6 Cable lengths types External readers 20 200 m J Y St Y 4x2x0 8i Connection tamper reader TC 40 m J Y St Y 2x2x0 8i Door strike with monitoring contact 40 m J Y St Y 2x2x0 8i Door strike key 40 m J Y St Y 2x0 6i or YV St Y 2x0 5i Interface circuits RS 485 3 wire bis 40 m J Y St Y bis 1200 m Cat 5e or better Power supply 230V AC NYM J 3 x 1 5 mm2 3 Power ...

Page 11: ...he Velcro fastening tape Use the red and black red cable of the pcb for connecting the battery to the pcb The end of charging voltage of the battery charging unit is set in the factory for Sonnenschein batteries of the A500 series If it is necessary to change the setting proceed as described in the chapter Adjusting the end of charging voltage 3 4 Integriertes Netzteil Fully electronic power suppl...

Page 12: ...ging current is monitored and tracked depending on the temperature by means of an NTC resistor The end of charging voltage of the battery charging unit is correctly set in the factory for Sonnenschein batteries of the A500 series If it is necessary to change the setting proceed as described in the chapter Adjusting the end of charging voltage Not stabilized power supply Uext A not stabilized direc...

Page 13: ...below Note the battery type Warning Destruction of device possible The end of charging voltagemust only be modified 1 after having exactly measured the temperature 2 if the battery voltage deviates by 200mV from the nominal value according to the table below 3 4 3 Connection component mounting diagram Current drain output I12V max 400mA Current drain PL1 Uext Uext 9 17 5 V DC Iext max 900mA I12V I...

Page 14: ...ith notch slightly downwards and remove the pcb from the mounting pillars To attach the plastic housing on a wall there are three mounting screws required After mounting the plastic housing set up the pcb in the mounting pillars and snap it into the retainer Now the peripheral devices can be connected Observe the connection diagrams and the terminal assignments Then attach the housing cover and cl...

Page 15: ...re range 5 C to 55 C Storage temperature range 25 C to 70 C Environmental class according to VdS II Color of the plastic housing grey white similar to RAL 9002 Dimensions W x H x D 163 x 152 x 40 mm 5 2 Technical data 026594 10 Door module 230V AC RS485 The performance features are the same as for Item no 026593 10 Battery support 1 x 018002 2 0 Ah In addition Power supply unit with battery chargi...

Page 16: ...ted by a separate power supply unit 6 General connection diagram with Item no 026593 10 bridge the connection terminal S to 0V otherwise failure message power suppy unit If only one reader is used this reader is to be connected as Reader 1 If install one door with exterior reader and interior reader the exterior reader is to be connected to termial Reader 1 und der interior reader is to be connect...

Page 17: ...ar off contact Jumper J1 Setting of JP1 will switch off bypass the cover contact With door module Item no 026594 10 the cover contact of the housing is located to this terminal Jumper J2 JumperJ2 factory setting 6 1 4 Jumper for RS 485 interface Jumper J4 and J5 set the RS 485 terminating resistors They are to be set only when door module is installed as last bus user of the bus data line 6 1 5 Co...

Page 18: ...Address 4 1 0 1 0 0 Address 5 0 1 1 0 0 Address 6 1 1 1 0 0 Address 7 0 0 0 1 0 Address 8 1 0 0 1 0 Address 9 0 1 0 1 0 Address 10 1 1 0 1 0 Address 11 0 0 1 1 0 Address 12 1 0 1 1 0 Address 13 0 1 1 1 0 Address 14 1 1 1 1 0 Address 15 0 0 0 0 1 Address 16 1 0 0 0 1 Address 17 0 1 0 0 1 Address 18 1 1 0 0 1 Address 19 0 0 1 0 1 Address 20 1 0 1 0 1 Address 21 0 1 1 0 1 Address 22 1 1 1 0 1 Address...

Page 19: ...coding in the corresponding Novar access control software Wiegand esser var DIN Wiegand 26 Bit card System no Start 1 Digits 4 ID no Start 5 Digits 5 Version no Start 10 Digits 1 Wiegand esser var DIN Wiegand 34 Bit card System no Start 1 Digits 5 ID no Start 6 Digits 5 Version no Start 11 Digits 2 Wiegand var DIN System no Start 0 Digits 0 ID no Start 5 Digits 16 Version no Start 0 Digits 0 Wiega...

Page 20: ...ng a door strike 7 1 Connecting a door strike with load current function Strike with load current function the door is released if the coil is energized 7 2 Connecting a no load current door strike No load current door strike the door is blocked if the coil is energized ...

Page 21: ...oftware IQNetEdit Observe the operating voltage range and current consumption of the electric safety lock Use an external power supply or connection 12 V DC of the power supply unit 8 1 Door monitoring The interior door handle contact effects a door release via the door module The door can be passed without the error message Unauthorized door release ...

Page 22: ...22 Mounting and Connection Instructions Door module RS485 9 Connection diagram with Module potential separation ...

Page 23: ...er OUT 3 EN RS 485 Power supply S power supply mains 0V 0V Input 2 Door strike key Input 1 Door strike key Input 3 12k1 end of line resistor Input 4 12k1 end of line resistor 0V 0V Input 5 12k1 end of line resistor Input 6 12k1 end of line resistor Relay 1 normally closed contact Relay 2 normally closed contact common contact common contact normally open contact normally open contact Connection te...

Page 24: ...Honeywell Security Group Novar GmbH Johannes Mauthe Straße 14 D 72458 Albstadt www honeywell com security de P032509 10 0G0 01 2014 05 07 2014 Novar GmbH ...