A B B M E A S U R EM EN T & A N A LY T I C S | CO M M I S S I O N I N G I N S T R U C T I O N | C I/C M 10 - EN  R E V. C

ControlMaster CM10

Universal process controller, 1/8 DIN

Measurement made easy

Summary of Contents for ControlMaster CM10

Page 1: ...ABB ME ASUREMENT ANALY TICS COMMISSIONING INSTRUCTION CI CM10 EN REV C ControlMaster CM10 Universal process controller 1 8 DIN Measurement made easy...

Page 2: ...basic functionality ControlMaster CM10 CM30 and CM50 Universal process controllers 1 8 1 4 and 1 2 DIN IM CM B EN User guide standard functionality ControlMaster CM10 CM30 and CM50 Universal process...

Page 3: ...89 336 EEC 5 End of life disposal 5 Cleaning 6 Symbols 6 Restriction of Hazardous Substances RoHS 7 2 Specification 8 3 Installation 10 Siting 10 Mounting 11 4 Electrical connections 13 Accessing the...

Page 4: ...word NOTICE indicates potential material damage Note Note indicates useful or important information about the product Safety precautions Be sure to read understand and follow the instructions containe...

Page 5: ...nformation Safety standards This product has been designed to satisfy the requirements of IEC61010 1 2010 3rd edition Safety Requirements for Electrical Equipment for Measurement Control and Laborator...

Page 6: ...e symbol may not be disposed of in European public disposal systems after 12th August 2005 Cleaning The controller can be hosed down if it has been installed to IP66 NEMA 4X standards Warm water and a...

Page 7: ...n member states and other countries limits the use of six hazardous substances used in the manufacturing of electrical and electronic equipment Currently monitoring and control instruments do not fall...

Page 8: ...ical Power supply ranges 100 to 240 V AC 10 90 V min to 264 V max 50 60 Hz 10 to 36 V DC optional Power consumption 10 W max Inputs Outputs Analog inputs 1 universal 1 process Analog outputs 1 standar...

Page 9: ...100 mA max switched Conforms to IEC 61131 2 Update Rate 125 ms Environmental data Ambient operating temperature 0 to 55 C 32 to 131 F Ambient operating humidity 5 to 95 RH non condensing Storage tempe...

Page 10: ...and hail Select a location away from strong electrical and magnetic fields If this is not possible particularly in applications where mobile communications equipment is used use screened cables within...

Page 11: ...rotection a panel thickness of 2 5 mm 0 1 in is required Referring to Figure 3 1 Cut a hole of the correct size for the controller in the panel 2 Insert the controller into the panel cut out 121 4 8 1...

Page 12: ...inst the panel 2 Locate the panel clamp anchor B in slot C 3 Tighten the panel clamp anchor screw D until panel clamp A is lightly touching the panel 4 Repeat steps 1 to 3 to fit the remaining panel c...

Page 13: ...common mode voltages before accessing or making any connections Use cable appropriate for the current loads 3 core cable rated 3 A and 90 C 194 F minimum that conforms to either IEC 60227 or IEC 6024...

Page 14: ...nded metal conduit Use screened cable for signal inputs and relay connections Replacement of the internal battery type Varta CR1620 3V lithium cell must be carried out by an approved technician only A...

Page 15: ...2 Relay output 2 Relay output 3 Relay output 4 Refer to the Communications Supplement IM CM C EN for MODBUS connection details N O or N C contact selection is made via internal jumper links N O is th...

Page 16: ...med for use with millivolt inputs and the appropriate thermocouple linearizer is selected Analog input 2 can be used with THC inputs only if analog input 1 is also used as a THC input For mA input typ...

Page 17: ...ges are displayed within the Diagnostics View Prompts associated with active keys are displayed on each screen Diagnostic and display icon descriptions are included in this document Key functions for...

Page 18: ...us and menu options 3 Press to expand menu levels and to select menu options or press to return to the previous menu Autotune Used to start or stop an Autotune routine This menu is enabled only if Aut...

Page 19: ...f access basic or advanced then press Logout Displayed after basic or advanced level are accessed Logs the user out of basic or advanced level If passwords are set a password must be entered to access...

Page 20: ...rity diagnostics message are displayed in the status bar when in operator view A list of all currently active diagnostic alarm states are displayed in the diagnostic view Failure Maintenance Out of sp...

Page 21: ...t signal is outside permitted limits 222 014 CJ 1 Failed Error in Cold junction measurement associated with AIN1 Wiring fault or defective sensor Check cold junction device is correctly fitted Ensure...

Page 22: ...memory on communications board or permanent corruption of its data Acknowledge error Check communications board is correctly identified by controller If problem persists contact local service organiz...

Page 23: ...han configured time Check valve to identify reason for sticking Check correct travel time is entered in configuration 168 026 166 027 164 028 Tuner 1 Phase 1 3 Autotune is in progress Autotune can be...

Page 24: ...1 Cycle Time 2 Alarm 1 8 Trip Initial Setup App Template Loop 1 Output Type Loop 1 Split O P Instrument Tag Mains Freq Config Action Reset to Defaults Security Setup Basic Password Advanced Password...

Page 25: ...f Local SP s Local Setpoint 1 Track Mode RSP Ratio RSP Bias RSP Fault Action Default Setpoint Ramp Mode Ramp Rate Select Sources Loop 1 Control Control Type Control Action On Off Hysteresis Autotune P...

Page 26: ...Source Trip Hysteresis Time Hysteresis Display Enable Acknowledge Source Enable Source Refer to the Communications Supplement IM CM C EN for Communication parameter details Diagnostic History Source A...

Page 27: ...CONTROLLER 1 8 DIN CI CM10 EN RE V C 27 Exit Select Device Info Instrument Type I O Build No Analog Inputs No Analog Outputs No Relays No Digital I O Functionality Serial No Hardware Revision Software...

Page 28: ...rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden with...