Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
98
Note
•
The condition under which a specified scene is to be recalled is defined here. The scene is only re-
called if the condition is met at the set start time.
Defining the condition
Figure 154:
SCENE CALL
settings level
–
Start point:
SCENE CALL
settings level
1. Select
CONDITION
.
=
CONDITION
illuminates.
2. Run your finger along the touchring until the desired setting appears.
3. Select
SCENE
.
=
SCENE
illuminates.
4. Run your finger along the touchring until the desired number appears.
5. Select
SAVE
to save the settings.
=
The message
SAVED
briefly appears.
=
The condition and scene to be recalled are saved.
=
SWITCH TIME - FADE
settings level appears.
Parameter
Value range
HOUR
0 – 23
MINUTE
0 – 59
Table 51:
START TIME
setting options
CONDITION parameter
Description
ALL
The set scene is recalled regardless of which scene is enabled
at the start time.
PRESENCE
The set scene is only recalled if the presence scene is enabled
at the start time.
ABSENCE
The set scene is only recalled if the absence scene is enabled
at the start time.
1 – 20
The set scene is only recalled if the scene with the selected
number is enabled at the start time.
Table 52:
CONDITION
setting options
Notes
•
Settings are only saved if
SAVE
is selected.
• Selecting
SAVE
automatically saves all values displayed on the touchscreen.