Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
111
Notes
•
Settings are only saved if
SAVE
is selected.
•
Selecting
SAVE
automatically saves all values displayed on the touchscreen.
•
To switch to the
WAITING TIME
settings level directly (without saving), select
NEXT STEP
.
Parameter
Value range
SCENE
0 – 20
Table 70:
SCENE
setting options
Setting the fade speed and assigning a building service type
Figure 174:
FADE - TYPE
settings level
–
Start point:
FADE - TYPE
settings level
1. Select
FADE
.
=
FADE
illuminates.
2. Run your finger along the touchring until the desired number appears.
3. Select
TYPE
.
=
TYPE
illuminates.
4. Run your finger along the touchring until the desired number appears.
5. Select
SAVE
to save the settings.
=
The message
SAVED
briefly appears.
=
Fade speed and building service type are saved.
=
ROOM - GROUP
settings level appears.
Notes
•
Settings are only saved if
SAVE
is selected.
•
Selecting
SAVE
automatically saves all values displayed on the touchscreen.
•
To switch to the
WAITING TIME
settings level directly (without saving), select
NEXT STEP
.
=
Next scene is saved.
=
FADE - TYPE
settings level appears.
FADE parameter
Value range (in seconds)
Factory setting
FADE
0, 1, 3, 5, 7, 10, 15, 30, 60
0 seconds
Table 71:
FADE
setting options