Commissioning the field level
LM-CIRIA operating and commissioning manual 2.0 | 06. 2012 | en
100
Assigning group and building service type
Figure 156:
GROUP - TYPE
settings level
–
Start point:
GROUP - TYPE
settings level
1. Select
GROUP
.
=
GROUP
illuminates.
2. Run your finger along the touchring until the desired group address appears.
3. Select
TYPE
.
=
TYPE
illuminates.
4. Run your finger along the touchring until the desired number appears.
5. Select
SAVE
to save the settings.
=
The message
SAVED
briefly appears.
=
Group and building service type are assigned and saved.
=
SWITCH ENTRY
selection level appears.
Parameter
Value range
GROUP
Available group address in the room to which the LM-CIRIA
control unit is assigned
Table 56:
GROUP
setting options
Building service type
Building service type number
COMMON (all building services)
1
Brightness
2
Blind position
3
Slat angle
4
Screen
10
Colour temperature
13
Window
65
Curtain
64
Temperature
11
Air exchange
39
Table 57: Selection of
TYPE
setting options
Notes
•
Settings are only saved if
SAVE
is selected.
• Selecting
SAVE
automatically saves all values displayed on the touchscreen.