H32P Uni-Zone
™
Model H32P
for use with Plug-In Dampers Only
Installation and Operating Instructions
Controlling Your Comfort Room By Room
Страница 1: ...H32P Uni Zone Model H32P for use with Plug In Dampers Only Installation and Operating Instructions Controlling Your Comfort Room By Room...
Страница 2: ...or ZPS are wired When installing the H32P panel it is important to pick a central location where it is most convenient to bring all the wires Most often this is at the furnace or air handler It is oft...
Страница 3: ...l heat pump with electric back up heat or fossil dual fuel mode FAN IN HEAT YES or NO This switch will activates the Fan on a call for Heat in the Yes position In Off the heating unit must activates t...
Страница 4: ...all calls for a particular mode are satisfied or when the Changeover Timer requires a changeover due to opposing calls After all calls are satisfied or the changeover timer activates the Purge Timer...
Страница 5: ...of thermostat WIRING DIAGRAM 1 Conventional Thermostats WIRING DIAGRAM 4 HVAC Equipment Dual Fuel Heat Pump with Fossil Fuel Back Up ZONE THERMOSTAT C W R Y G E G Y R W OB C WIRING DIAGRAM 5 Single S...
Страница 6: ...rmostat To check the zone on the panel place jumper from R to Y R to W or R to G to see that the panel is operating properly Zone s Will Not Shut Off If a zone will not stop calling the Zone LED shoul...