12 VOLT DC BATTERY BACKUP PUMP

INSTALLATION INSTRUCTIONS

PREINSTALLATION CHECKLIST 

1.  Inspect your pump. Occasionally, products are damaged during shipment. If the unit or any of the parts are damaged, contact your dealer before using.

2.  Carefully read the literature provided to familiarize yourself with specific details regarding installation and use. These materials should be retained for future 

reference.

SEE BELOW FOR 

LIST OF WARNINGS

1.  Testing for ground. As a safety measure each electrical outlet should 

be checked for ground using an Underwriters Laboratory listed circuit 

analyzer, which will indicate if the power, neutral and ground wires are 

correctly connected to your outlet. If they are not, call a qualified, licensed 

electrician.

2.  For your protection, always disconnect the power supply from its power 

source before handling the components of your DC backup pump or the 

primary pump.

3.  Installation and servicing of electrical circuits and hardware should be 

performed by a qualified, licensed electrician. 

4.  All electrical and safety codes must be followed including the National 

Electrical Code and all applicable local codes. 

5.  

It is the owner’s responsibility to check the battery and battery 

connection at least once a month. Batteries contain acid, and 

caution must be taken when handling.

6.  Risk of electric shock. These pumps have not been investigated 

for use 

in swimming pools and marine areas.

7.  According  to  the  state  of  California  (Prop  65),  this  product  contains 

chemicals known to the state of California to cause cancer and birth 

defects or other reproductive harm.

1.  Make sure there is a properly grounded 115 V receptacle available. Do 

not use primary pump circuit.

 The location must be within 6' (1.8 m) of 

the control box and battery. The power supply for your DC control system 

plugs directly into the 115 V outlet. 

DO NOT USE AN EXTENSION CORD.

2.  Make sure the 115 V electrical supply circuit is equipped with fuses or 

circuit breakers of proper capacity.

3.  DC emergency pumps are designed for handling clear water. Do not use 

in septic tanks to pump effluent or in sewage pits to pump sewage.

4.  Repair and service of your DC backup system should be performed by 

an authorized service station.

5.  The installation of DC automatic backup pumps requires the use of a 

variable level float switch for operation. It is the responsibility of the 

installing party to ensure that the float switch will not hang up on the 

pump apparatus or pit peculiarities and is secured so the pump will turn 

“on” and “off”. It is recommended that the pit be 18" (45.7 cm) in diameter 

or larger to accommodate both a primary and a DC backup pump.

6.  For indoor use only.

CAUTION

SEE BELOW FOR 

LIST OF CAUTIONS

REFER TO WARRANTY ON PAGE 2.

CAUTION

    Turbulence  caused  by  high-velocity  incoming 

water can cause sump pumps to airlock. If this condition exists, 

the incoming water must be baffled to avoid excessive turbulence.

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

MAIL TO:  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO:  3649 Cane Run Road  • Louisville, KY  40211-1961

(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624

visit our web site:

www.zoeller.com

®

Your Peace of Mind is Our Top Priority

 

®

ANY

 CHANGES MADE 

TO 

THIS DOCUMENT

 ALSO MA

Y

 AFFECT

 

FM131

1f & FM131

1s, HF1312, FM1

139 & FW0477 FOR F&W

.

© Copyright 2016 Zoeller

®

 Co. All rights reserved.

Real Time Peace of Mind.™

Содержание AqyaNot 508 Active

Страница 1: ...and birth defects or other reproductive harm 1 Make sure there is a properly grounded 115 V receptacle available Do not use primary pump circuit The location must be within 6 1 8 m of the control box and battery The power supply for your DC control system plugsdirectlyintothe115Voutlet DO NOTUSEANEXTENSIONCORD 2 Make sure the 115 V electrical supply circuit is equipped with fuses or circuit breake...

Страница 2: ...Plug the controller and the primary pump into the wall outlet a The primary pump will come on lower the water to the normal operating level and shut off b The battery light will flash yellow when charging The charger is replacing the energy consumed during the test The green light will come on after the charger has replaced the energy consumed during the test Wet cell batteries should be checked e...

Страница 3: ...8 Active controller 1 153477 9 Battery box asm box and cover 1 10 0764 10 Hardware pak charger switch mode 1 152864 11 Fitting asm clamp 508 service part 1 152969 12 Flapper asm service part 1 152970 SK3047 The DC emergency pump system requires a good quality 12 volt battery to obtain maximum pumping time during a power outage A deep cycle 12 volt 105 amp hour marine battery or larger is recommend...

Страница 4: ...to ensure the hose clamp screws will not interfere with the float operation of the primary pump 8 Assemble the operation float assembly per Figure 6 Install float switches as seen in Figure 1 9 The low water switch terminals have a jumper wire installed on the unit so no low water switch is necessary If you would like to use a low water switch install the low water float switch with the off level ...

Страница 5: ...W WYE CAN BE USED AS WELL DO NOT USE DWV FITTINGS IF YOU PREFER TO USE THE LOW WATER FLOAT THE SUPPLIED JUMPER CAN BE REMOVED AND THE LOW WATER FLOAT INSTALLED IN ITS PLACE BATTERY BOX CHARGER OUTLET AQUANOT ACTIVE CONTROLLER Z CONTROL GATEWAY FIGURE 2 OPERATIONAL FLOAT SWITCH HIGH WATER FLOAT SWITCH SHOWN FOR CLARITY 1 1 2 INLINE CHECK VALVE LOW WATER CUT OUT FLOAT SWITCH OPTIONAL 1 2 5 cm MIN IM...

Страница 6: ...OAT SWITCH OPTIONAL 1 SCH 40 PVC PIPE PROVIDED BY OTHERS LOW WATER CUTOFF FLOAT SWITCH CLAMP CLAMP CLAMP FLOAT CLIP DC PUMP BATTERY BOX 12 VOLT DEEP CYCLE BATTERY AQUANOT ACTIVE CONTROLLER OPERATIONAL FLOAT SWITCH HIGH WATER FLOAT SWITCH OPTIONAL OPTIONAL ETHERNET CABLE Z CONTROL GATEWAY 1 5 PVC TEE SCH 40 1 5 INLINE CHECK VALVE 30 AMP FUSE OPTIONAL Copyright 2016 Zoeller Co All rights reserved ...

Страница 7: ... test the pump every 24 hours for 10 seconds Holding the self test button for 10 seconds will start the 24 hour timer for self testing Solid Green Flashing Yellow Flashing Red Fast flashing Red System Ready Ready AC power No AC power Battery Charging Disconnected or fault DC pump Pump running Pump fault Low water Pit low on water Float fault Pump running continuously Operational switch System cycl...

Страница 8: ...e done to prevent the alarm activation MAIL TO P O BOX 16347 Louisville KY 40256 0347 SHIP TO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Your Peace of Mind is Our Top Priority visit our web site www zoeller com There are millions of batteries manufactured each year so it is impossible to guarantee consistent quality A defective battery will never becom...

Страница 9: ...a descarga a tierra No use el circuito de la bomba primaria Su ubicación debe estar dentro de 1 8 m 6 de la caja de control y de la batería El suministro eléctrico de su sistema de control de CD se enchufa directamente en el receptáculo tomacorriente de 115 V NO USE UN CORDÓN ALARGADOR 2 Asegúresedequeelcircuitodesuministroeléctricode115Vestéequipado con fusibles o interruptores automáticos de cap...

Страница 10: ...gando El cargadorestáreemplazandolaenergíaconsumidadurantelaprueba La luz verde se encenderá después de que el cargador haya reemplazado la energía consumida durante la prueba Las baterías húmedas deberían ser revisadas cada mes 1 La bomba CD no funciona a Verifique que las conexiones estén correctas b Verifique todas las puntas de los terminales de alambre Limpie si es necesario c Verifique si la...

Страница 11: ...8 8 Controlador activo 1 153477 9 Conjunto de caja la batería caja y tapa 1 10 0764 10 Paquete de herrajes cargador modo de conmutación 1 152864 11 Conector conjunto y abrazadera 508 pieza de repuesto 1 152969 12 Conjunto de charnela pieza de repuesto 1 152970 SK3047 El sistema de bomba de emergencia de CD requiere una batería de 12 V de buena calidad para obtener el tiempo de bombeo máximo durant...

Страница 12: ...y pegue con soldadura en frío cualquier tubería de descarga restante por encima del codo NOTA Compruebe el funcionamiento del flotador para garantizar que los tornillos de la abrazadera de la manguera no interfieran con el funcionamiento del flotador de la bomba principal 8 Monte los componentes del flotador de funcionamiento según se ve en la Figura 5 Instale interruptores de flotador como se ve ...

Страница 13: ...DE AGUA EL PUENTE SUMINISTRADO PUEDE SER RETIRADO Y EL FLOTADOR DE NIVEL BAJO DE AGUA PUEDE INSTALARSE EN SU LUGAR INTERRUPTOR DE FLOTADOR DE CORTE POR NIVEL BAJO DE AGUA OPCIONAL IMPORTANTE EL NIVEL DE APAGADO DEBE CONFIGURARSE POR ENCIMA DE LA ENTRADA DE LA BOMBA PRINCIPAL INTERRUPTOR DE FLOTADOR DE NIVEL ALTO DE AGUA FIGURA 2 2 5 cm 1 pulg MIN IMPORTANTE EL NIVEL DE APAGADO DE LOS COMPONENTES D...

Страница 14: ...CH 40 DE DN40 1 PULG PROPORCIONADO POR TERCEROS INTERRUPTOR DE FLOTADOR DE CORTE POR NIVEL BAJO DE AGUA OPCIONAL ABRAZADERA ABRAZADERA ABRAZADERA GRAPA DE FLOTADOR BOMBA DE CC CAJA DE BATERÍA BATERÍA DE CICLO PROFUNDO DE 12 VOLTIOS AQUANOT ACTIVE INTERRUPTOR DE FLOTADOR DE FUNCIONAMIENTO INTERRUPTOR DE FLOTADOR DE NIVEL ALTO DE AGUA OPCIONAL CABLE DE ETHERNET Z CONTROL GATEWAY T DE PVC SCH 40 DE D...

Страница 15: ...iene programado de fábrica para realizar un autodiagnóstico de la bomba cada 24 horas durante 10 segundos El mantener presionado el botón de autodiagnóstico durante 10 segundos iniciará el temporizador de 24 horas para el autodiagnóstico Verde fijo Amarillo parpadeante Rojo parpadeante Rojo parpadeante rápido Sistema listo Listo Alimentación de CA Sin alimentación de CA Batería Cargando Desconecta...

Страница 16: ...rma Su tranquilidad es nuestra mayor prioridad visite a nuestro sitio web www zoeller com CORREO A P O BOX 16347 Louisville KY 40256 0347 USA ENVÍOS A 3649 Cane Run Road Louisville KY 40211 1961 USA 1 502 778 2731 FAX 1 502 774 3624 Cada año se fabrican millones de baterías por lo que es imposible garantizar una calidad constante Una batería defectuosa nunca llegará a cargarse completamente y pued...

Страница 17: ...nt les pompes automatiques en courant continu doivent être équipée d un interrupteur à flotteur à niveau variable L installateur doit vérifier que l interrupteur à flotteur ne s accroche pas à la pompe ni aux aspérités du puisard et qu il est fermement installé pour permettrelamisenemarcheetl arrêtdelapompe Ilestrecommandéd avoir un puisard d au moins 45 cm 18 de diamètre pour permettre l installa...

Страница 18: ...yer si nécessaire d Vérifier si la batterie est déchargée Faire de l entretien sur la batterie selon le besoin 2 La pompe fonctionne mais pompe très peu ou pas d eau sans courant alternatif a Vérifier si la batterie est déchargée La batterie doit se charger quand le voyant vert de marche est allumé indiquant que le système est sous tension et que l interrupteur à flotteur est en position d arrêt b...

Страница 19: ... de matériel chargeur technologie d interrupteur 1 152864 11 Raccord ASM et collier 508 pièces de rechange 1 152969 12 Battant ASM pièce de rechange 1 152970 SK3047 Le système de pompe de secours doit être équipé d une batterie de 12 V de bonne qualité pour obtenir le meilleur pompage possible en cas de panne de courant Il est recommandé d utiliser une batterie marine à décharge poussée de 12 V 10...

Страница 20: ...iliser cette mesure afin de couper le tuyau d évacuation Fixer cette pièce au coude à l aide de colle à solvant Mesurer couper et coller au solvant tout autre tuyau d évacuation restant au dessus du coude REMARQUE Vérifier le fonctionnement du flotteur afin de s assurer que les vis du collier du flexible n interfèrent pas avec le fonctionnement du flotteur de la pompe principale 8 Assembler le flo...

Страница 21: ...IRETOUR ALIGNÉ 3 8 CM 1 5 PO INTERRUPTEUR À FLOTTEUR POUR ARRÊT EN CAS DE NIVEAU D EAU FAIBLE EN OPTION IMPORTANT LE NIVEAU D ARRÊT DOIT ÊTRE DÉFINI AU DESSUS DE L ENTRÉE DE LA POMPE PRINCIPALE SI VOUS PRÉFÉREZ UTILISER LE FLOTTEUR DE NIVEAU D EAU FAIBLE LE CAVALIER FOURNI PEUT ÊTRE RETIRÉ ET LE FLOTTEUR INSTALLÉ À SA PLACE FIGURE 2 2 5 cm 1 po MIN IMPORTANT LE NIVEAU D ARRÊT DU FLOTTEUR DOIT ÊTRE...

Страница 22: ...ON TUYAU PVC DN40 1 1 2 PO SCH 40 FOURNIS PAR D AUTRES INTERRUPTEUR À FLOTTEUR POUR ARRÊT EN CAS DE NIVEAU D EAU FAIBLE EN OPTION COLLIER COLLIER COLLIER ATTACHE DE FLOTTEUR POMPE À COURANT CONTINU BOÎTIER DE BATTERIE BATTERIE 12 V À DÉCHARGE PROFONDE AQUANOT ACTIVE CONTRÔLEUR INTERRUPTEUR À FLOTTEUR OPÉRATIONNEL INTERRUPTEUR À FLOTTEUR DE NIVEAU D EAU ÉLEVÉ EN OPTION CÂBLE ETHERNET Z CONTROL GATE...

Страница 23: ... d effectuer des autoévaluations de la pompe toutes les 24 heures durant 10 secondes Maintenir le bouton d autoévaluation pendant 10 secondes pour démarrer la minuterie de 24 heures de l autoévaluation Vert fixe Jaune clignotant Rouge clignotant Rouge clignotant rapidement Système prêt Prêt Alimentation c a Pas d alimentation c a Batterie En charge Déconnectée ou défaillante Pompe à courant contin...

Страница 24: ...priorité absolue Visitez notre site internet www zoeller com ADRESSE POSTALE P O BOX 16437 Louisville KY 40256 0347 USA ADRESSE PHYSIQUE 3649 Cane Run Road Louisville KY 40211 1961 USA TÉL 1 502 778 2731 FAX 1 502 774 3624 Chaque année des millions de batteries sont fabriquées et il est donc impossible de garantir une qualité constante Une batterie défectueuse ne va jamais charger entièrement et p...

Отзывы: