All electrical and safety codes must be followed including the National Electrical Code and all applicable local codes.

SPECIFICATIONS

This alarm unit monitors liquid levels in lift pump chambers, sump pump basins, holding tanks, and other non-potable water applications (See Figure 

A). APak

 Outdoor High Water Alarm features a green Power On LED, red alarm LEDs, an audible buzzer, one set of normally closed and normally open 

Auxiliary contacts, and a Silence/Reset/Test toggle switch. The APak

 Outdoor High Water Alarm

 

can be wired to a 120 V, 60 Hz, electrical power 

source. This product is rated as NEMA 4X. To maintain rating, use only equivalent rated conduits and install in accordance with applicable standards. 

Tighten enclosure screws once a year, (recommended torque of 0.45 Nm or 4 in-lbs.) and perform any required maintenance to ensure protection. 15A 

household circuit breaker required. 

ALARM UNIT INSTALLATION / WIRING 

1) 

Drill openings on the bottom of the enclosure sufficient to accommodate the appropriate conduit adapter. Follow guidelines to ensure a water 

tight fit where applicable. 

2) 

Install unit in desired location using mounting flanges on enclosure.

3) 

Remove the 4 cover screws to access the terminal contacts and the auxiliary contacts.

4) 

Wire line and neutral to terminal contacts 1 & 2 and connect earth ground to the ground lug located on metal backplate (See Figure B).

5) 

Wire mechanical float switch to terminal contacts 3 & 4 (See Figure B).

6) 

Terminal contacts 5, 6, 7 are provided as an optional wiring junction point for the pump. 115/230V, 20A max. 

7) 

Auxiliary contacts may be used to control other alarm circuits and are rated for 115V, 60Hz, 5A resistive load.

APak

 Outdoor High Water Alarm

ELECTRICAL SHOCK HAZARD.

DISCONNECT POWER BEFORE SERVICING

Product information presented 

here  reflects  conditions  at  time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

MAIL TO: 

 P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO: 

 3649 Cane Run Road  • Louisville, KY  40211-1961

TEL:

 (502) 778-2731 • 1 (800) 928-PUMP • 

FAX

: (502) 774-3624

Visit our web site:

zoeller.com

FM3287

1220

Supersedes

New

ALARM UNIT

CONDUIT

ALARM “ON” LEVEL

ALARM “OFF” LEVEL

PUMP “ON” LEVEL

PUMP “OFF” LEVEL

Figure A

Содержание APak

Страница 1: ...fficient to accommodate the appropriate conduit adapter Follow guidelines to ensure a water tight fit where applicable 2 Install unit in desired location using mounting flanges on enclosure 3 Remove the 4 cover screws to access the terminal contacts and the auxiliary contacts 4 Wire line and neutral to terminal contacts 1 2 and connect earth ground to the ground lug located on metal backplate See ...

Страница 2: ...tallation by lifting the float manually The alarm unit will indicate an alarm condition by buzzer chirping and lighting the red LEDs The alarm may be silenced for 24 hours by briefly pressing the Silence toggle switch Once silenced the Red LEDs will remain on but the buzzer will not sound Once the high water condition is remedied the alarm should be reset by holding the Silence toggle switch for 2...

Страница 3: ...e of motion IN A LIFT PUMP Install float switch at a level above where the pump will energize If a pump failure causes high level condition the APak Outdoor High Water Alarm System will activate see Figure A IN A HOLDING TANK Suspend float switch into tank 7 17 8 cm below desired alarm level APak Outdoor High Water Alarm System will activate if float ascends to alarm level see Figure D Model Numbe...

Страница 4: ...accordance with Manufacturer s installation instructions that has been exposed to outside substances including but not limited to the following sand gravel cement mud tar hydrocarbons hydrocarbon derivatives oil gasoline solvents etc or other abrasive or corrosive substances wash towels or feminine sanitary products etc in all pumping applications The warranty set out in the paragraph above is LIM...

Отзывы: