ECI0016PA Data Capture Card User Manual V1.5
when the load circuit changes.
Due to the leak-type output, the shutdown of the output will be obviously
affected by the external load circuit, and the output frequency should not be set
too high in the application. For low-speed output, it is recommended to be lower
than 8HKz. If there needs higher speed, please contact us to adjust parameter or
custom hardware.
→
Wiring Reference
→
Wiring Note:
⚫
The wiring principle of low-speed digital output OUT (0-7) is shown in the figure
above. The external signal receiving end can be an optocoupler or a relay or solenoid
valve, all can be connected as long as the input current does not exceed 300mA.
⚫
For the connection of the public end, please connect the "EGND" port on the power
supply to the negative pole of the DC power supply of the external input device. If the
DC power supply of the external device and the controller power supply are in the
same power supply system, this connection can also be omitted.
3.3.2.
Basic Usage Method
(1)
Please follow the above wiring instructions to wiring correctly.
(2)
After powered on, please use ETHERNET or RS232 to connect to ZDevelop.
(3)
Open or close output port directly through “OP” command, also, it can be opened or
Содержание ECI0016PA
Страница 1: ......