BG2000 Series Barrier Gate (APP Version)
User Manual
P a g e
| 24
Copyright©2022 ZKTECO CO., LTD. All rights reserved.
22EXXX
Open/Close Limit LED State
22E000:
Open limit green light
breathing,
Close
limit
red
light
breathing
22E001: Open limit green light always
on, Close limit red light always on
22E002: Open limit green light flashes,
Close limit red light breathing
22E000
22E000
22E000
22E000
23EXXX
Open/Close LED State
23E000: The red light flashes during the
whole process of opening and closing
the boom arm.
23E001: The red light is always on
during the whole process of opening
and closing the boom arm.
23E000
23E000
23E000
23E000
24EXXX
Remote Control Type
24E000: 433MHz frequency
24E001: 430MHz frequency
24E000
24E000
24E000
24E000
Error Code
Erro Code
Description
Solve
EL0002
Power-on Self-test failure, Hall limit detection
error.
Check the spring and boom arm blance.
EL0004
Run Timeout.
Restart the machine
EL0008
Clutch Locked.
Check the 20E parameter
EL016
The code disk detection failed.
Check the motor connect cable;
Check the 20E parameter.
EL032
Electric Motor Shaft Lock Protection failure.
Check the 20E parameter;
Restart the machine.
Remote Control Pairing and Unpairing(Support setting on the
ZKBarrier APP)
8.4.1
Pairing
Long press [Menu/save], then press [Stop/
▼
] flip down to [15EXXX]. Press [+/-] to set the parameter
value. At this time, the LED display value is "15EX0X", and then press any button on the remote control