Ziton Wireless Manual Call Point Installation Guide
General
The Ziton wireless manual call point is available under
the following part number:
PART NO
VARIANT TYPE
ZR485-3
Ziton wireless manual call point
The address of the unit is set when programming the
device to the system (see programming manual for
details). The installation must conform to BS5839:Part 1
(or applicable local codes).
Installation of Ziton wireless manual call point
Loosen the back plate fixing screw. Insert flat bladed
instrument into the removal slot and remove the back
plate from the transmitter/battery section. (See Figure 1).
Mount the back box 1.4m from the floor, using suitable
fixings and fasteners. A minimum of two mounting holes
must be used. Countersunk head screws must be used to
avoid the possibility of damage to the internal
components. (See Figure 2).
Figure 1
Power jumper
Figure 2
Figure 3
Wall mounting positions
To ensure correct operation, connect the power jumper
across the PIN header on the battery PCB located on the
rear of the call point as shown in Figure 3.
Specification
Operating
Temperature
-10 to +70°C (ambient)
Storage
Temperature
0 to +35°C
Humidity
Up to 95% non-condensing
Supply
6x AA Alkaline (Panasonic LR6AD
Powerline / Varta 4006 Industrial)
IP Rating
IP24
Operating
Frequencies
868 MHz
Output Transmitter
Power
Variable 0-14 dBm
Dimensions
89mm (W) 92mm (H) 70mm (D)
Weight
0.40kg
Regulatory information
Manufacturer
EMS Ltd.
Technology House, Sea Street,
Herne Bay, Kent, CT6 8JZ,
United
Kingdom
Year of
manufacture
See serial number on unit
Certification
Certification body
CPD Certificate
DOP
0359-CPR-0168
Approved to
EN54-11
EN54-25
Application
Intended for use in fire detection
and fire alarm systems in and
around buildings. Indoor use only.
European Union
directives
EMS declares that the radio
equipment
type
Ziton Wireless
Manual Call Point is in compliance
with Directive 2014/53/EU. The full
text of the EU declaration of
conformity is available at the
following internet address:
www.utcfssecurityproducts.eu/dop/
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon purchase of equivalent new
equipment, or dispose of it at
designated collection points.
For more information see
www.recyclethis.info
Dispose of your batteries in an
environmentally friendly manner
according to your local regulations.
Contact information
For contact information, see www.utcfireandsecurity.com
12