Ziton ZR432-2P Скачать руководство пользователя страница 1

Ziton Wireless Multisensor Detector Installation Guide

General

The Ziton wireless mutisensor detector and ancillary 

equipment are available under the following part 

numbers:

PART NO   

VARIANT TYPE

ZR432-2P                  Ziton multisensor wireless detector  

ZR401-3P                  Ziton wireless module only (no    

 

                detector head)

ZX432-2P                 Ziton multisensor detector head    

 

                only

The address of the unit is set when programming the 

device to the receiver (see programming manual for 

details). The installation must conform to BS5839: Part 1 

(or applicable local codes).  

Installation of Ziton wireless multisensor detector

Ensure that all detectors are sited in accordance with the 

survey and design details. Wherever practical, the red 

LED should face the main entrance to the room.

Remove the ceiling mounting plate by first disengaging 

the detector head by turning it counter clockwise. This 

exposes the wireless module (shown in Figure 2). 

Disengage the mounting plate by pressing down the 

locking pin (shown in Figure 2) and turning the wireless 

module counter clockwise whilst pushing it against the 

ceiling mount.

Mounting plate

     Wireless module

Detector head

Figure 1

SE

R

IA

L N

o

PRESS HERE TO

LOG ON

3.5 - 4.5V DC

0.2 - 300mA

1W Max

SE

R

IA

L N

o

PRESS HERE TO

LOG ON

3.5 - 4.5V DC

0.2 - 300mA

1W Max

Radio Detector Base

EN54-25: 2008

Technical Data refer to Installation guide

Part No: ZR401-3

0359-CPD-0128

Ident

Locking mechanism

Power jumper

Figure 2

This dis-assembles the mounting plate from the wireless 

module and head sections. (See Figure 1). The ceiling 

mount will now be available for fixing to the ceiling. 

Ensure that the detector head and wireless module is 

suitably stored so as to prevent the possibility of 

accidental damage.

Fix the ceiling mounting plate to the ceiling using 

suitable fixings and fasteners. A minimum of two 

mounting holes must be used. (See Figure 3).

It is important that fastener heads are flush or sub-flush 

with the internal surface of the ceiling mount to avoid 

the risk of damaging the battery PCB.  

Notes

www.acornfiresecurity.com

www.acornfiresecurity.com