![Ziton ZR432-2P Скачать руководство пользователя страница 1](http://html2.mh-extra.com/html/ziton/zr432-2p/zr432-2p_installation-manual_3858974001.webp)
Ziton Wireless Multisensor Detector Installation Guide
General
The Ziton wireless mutisensor detector and ancillary
equipment are available under the following part
numbers:
PART NO
VARIANT TYPE
ZR432-2P Ziton multisensor wireless detector
ZR401-3P Ziton wireless module only (no
detector head)
ZX432-2P Ziton multisensor detector head
only
The address of the unit is set when programming the
device to the receiver (see programming manual for
details). The installation must conform to BS5839: Part 1
(or applicable local codes).
Installation of Ziton wireless multisensor detector
Ensure that all detectors are sited in accordance with the
survey and design details. Wherever practical, the red
LED should face the main entrance to the room.
Remove the ceiling mounting plate by first disengaging
the detector head by turning it counter clockwise. This
exposes the wireless module (shown in Figure 2).
Disengage the mounting plate by pressing down the
locking pin (shown in Figure 2) and turning the wireless
module counter clockwise whilst pushing it against the
ceiling mount.
Mounting plate
Wireless module
Detector head
Figure 1
SE
R
IA
L N
o
PRESS HERE TO
LOG ON
3.5 - 4.5V DC
0.2 - 300mA
1W Max
SE
R
IA
L N
o
PRESS HERE TO
LOG ON
3.5 - 4.5V DC
0.2 - 300mA
1W Max
Radio Detector Base
EN54-25: 2008
Technical Data refer to Installation guide
Part No: ZR401-3
0359-CPD-0128
Ident
Locking mechanism
Power jumper
Figure 2
This dis-assembles the mounting plate from the wireless
module and head sections. (See Figure 1). The ceiling
mount will now be available for fixing to the ceiling.
Ensure that the detector head and wireless module is
suitably stored so as to prevent the possibility of
accidental damage.
Fix the ceiling mounting plate to the ceiling using
suitable fixings and fasteners. A minimum of two
mounting holes must be used. (See Figure 3).
It is important that fastener heads are flush or sub-flush
with the internal surface of the ceiling mount to avoid
the risk of damaging the battery PCB.
Notes