P/N 501-1789ZE-1-10 • REV 10 • ISS 16APR14
ZP755BV-4 Addressable Base Sounder with
Visual Indicator Installation Sheet
Description
The ZP755BV-4 is an addressable base sounder with visual
indicator, designed for use in Ziton analogue addressable fire
detection and alarm systems.
Note:
The visual indicator of this product does not comply with
EN 54-23 and must not be used in fire alarm installations
where fire notification beacons are required.
The sounder includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the analogue addressable
loop or an external supply. The device plugs into a base that is
purchased separately. See Table 1 for a list of model numbers.
Table 1: Models
Number
Description
Sounder,
ZP755BV-4P
Base sounder/Visual indicator, Polar white
Cover,
ZP755-COV-P
ZP755-COV-R
Cover for ZP755B Base sounder
with no detector, Polar white
Cover for ZP755B Base sounder
with no detector, Red
Base,
SPB–2P
Base, Polar white
Installation
To install the device:
1. Wire the base
2. Set the operating power
3. Set the address
4. Set the operating mode
5. Set the tone
6. Set the volume
7. Mount the sounder onto the base
The details of each step are given below
Wiring the base
Connect the loop wiring for the base as shown in Figure 1.
There is no wiring between the sounder and base.
Figure 1: Loop wiring for the base
1.
Ext. 24 VDC+ IN/OUT
4.
Ext. 24 VDC ground IN/OUT
5.
Loop+ IN/OUT
7.
Shield
8.
Loop − IN/OUT
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
8
4
5
1