Table 3: Tone settings 

SW2-6 device mode 
switch setting 

Device mode 

SW2 switch setting 
-1 -2 -3 

Mapping input type 

Fast flash 

Steady 

Tone type 

Tone A primary/alert 

Tone B secondary/evac. 

OFF 

ZP755  

 

Intermittent 

Continuous 

OFF 

ZP755  

 

Continuous 

Intermittent 

OFF 

ZP755  

 

Continuous 

Two-tone 

OFF 

ZP755  

 

Two-tone 

Continuous 

OFF 

ZP755  

 

Two-tone 

Intermittent 

OFF 

ZP755  

 

Intermittent 

Two-tone 

OFF 

ZP755  

 

Not used 

 

ON 

ZP754  

 

Intermittent 

Continuous 

Setting the volume 

The sounder has a volume control potentiometer to adjust the 
volume. Refer to Figure 5. 

WARNING: 

To conform to EN 54 Part 3 sound output levels, 

the volume control 

must 

be set to the full clockwise position. If 

the volume is adjusted for any reason, it 

must 

be returned to 

the full clockwise position. 

Figure 5: Volume control 

 

1. 

Tone select 

2. 

SW2-6 on 

3. 

SW2-6 off 

4. 

Volume control  

Mounting the sounder onto the base 

Refer to Figure 6. Align the addressable sounder to the plug-in 
base. Push up (A), and then turn the sounder until it clicks into 
place (B). Push the sounder up once more to engage (C). 

Reverse the above procedure to remove the sounder from the 
base. 

Figure 6: Mounting 

 

1. 

Addressable sounder 

2. 

Release aid (3X) 

3. 

Release/lock catch 

4. 

Plug-in base 

Sounders per loop 

The sounder can be powered directly from the loop of a ZP5 or 
ZP3 panel. Use Figure 7 in conjunction with Table 4, to 
determine the quantity of detectors and sounders that can be 
connected to a two-core shielded loop. 

1
2
3

1

2

3

4

4

3

2

1

A

B

C

www.acornfiresecurity.com

www.acornfiresecurity.com