Ziton ZP755B-2 Скачать руководство пользователя страница 1

 

ZP755B-2 Addressable Sensor Base Sounder 
Installation Sheet 

 

Description 

The ZP755B-2 is an addressable sounder designed for use on 
Ziton analogue addressable fire detection and alarm systems. 

The sounder includes a volume control, an address-setting 
switch, programmable tone settings, and a pair of jumpers to 
select the operating power — from the analogue addressable 
loop or an external supply. The sounder plugs into a base that 
is purchased separately. See Table 1 for a list of model 
numbers. 

Table 1: Models 

Model number 

Description 

Sounder: 
 

ZP755B-2P 

 
Addressable sensor base sounder, Polar white 

Base: 
 

SPB–2P 

 
Plug-in base, Polar white 

Installation 

To install the device, follow these general steps. 

1.  Wire the base. 

2.  Set the operating power. 

3.  Set the address. 

4.  Set the mode of operation. 

5.  Set the tone. 

6.  Set the volume. 

7.  Mount the sounder onto the base. 

The details of each step are given below. 

Wiring the base 

Connect the loop wiring for the plug-in base as shown in 
Figure 1 below. There is no wiring between the sounder and 
plug-in base. 

Figure 1: Loop wiring for the plug-in base 

 

1. 

Ext. 24 VDC+ IN/OUT  

2. 

Ext. 24 VDC ground IN/OUT 

5. 

Loop+ IN/OUT 

6. 

Loop − IN/OUT 

7. 

Shield 

 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 
and J2. To select the source of the sounder operating power, 
position the jumpers as show in Figure 2. 

Figure 2: Power-selection jumper configuration 

 

1. 

Loop powered 

 

2. 

External 24 VDC 

Note: 

When using an external power supply, use only one that 

is CE and EN 54-4 compliant to power all the sounders on the 
same loop. 

6

2

5

1

J1

J1

J2

J2

2

1

www.acornfiresecurity.com