P/N 10-5221-501-ZSU1-01 • ISS 05FEB15 

 

ZP752-2 Monitored Dual Output Module 
Installation Sheet

 

Description 

The ZP752-2 provides two conventional output circuits (Circuit 
1 and Circuit 2) for operating polarized sounders, visual 
indicators, and controls for ancillary equipment. Output 1 and 
Output 2 share the same address and therefore switch on and 
off at the same time. 

The module comprises a front plate and a backbox. The front 
plate houses the electronic components and plugs into the 
backbox. The backbox provides the screw terminals for 
connecting the field wiring. 

The bicolor LED on the front plate indicates the status of the 
module (off = normal condition, red = active condition, amber = 
fault condition). There is space provided next to the LED to 
attach an address label, if desired. 

WARNING: 

This module will NOT operate without electrical 

power. As fires frequently cause power interruption, we 
suggest you discuss further safeguards with your local fire 
protection specialist. 

Installation 

1.  Remove the front plate from the backbox. 

2.  Drill out center hole in the backbox and run wires into the 

module. 

3.  Remove appropriate knockouts on the backbox for 

mounting to a conduit box. Mount the backbox to the 
conduit box. 

4.  Make all wiring connections as shown in the wiring 

diagram (Figure 2). 

5.  Set the address switch for the module. See “Address 

switch settings” below (Figure 1). 

6.  Attach the address label to the indent that is on the front of 

the module. 

7.  Secure the front plate to the backbox with the two screws 

provided. 

Address switch settings 

SW1 is used to assign device addresses. Each switch segment 
has a decimal value as shown in Figure 1. 

The sum of all the switch segments in the ON position 
determines the device address. You can set the device 
address to any value between 001 and 127 that is not used by 
another device on the same loop. For example, to select a 
device address of 007 you must set SW1-1, SW1-2, and SW1-
3 to the ON position and the remaining switch segments to the 
OFF position. 

Figure 1: Address switch settings 

Address

ON

OFF

Front plate - rear view

6

4

3

2

1

6

8

4

2

1

FUSES 1.0 A

Device address = 007

ON

1

2

3

4

5

6

7

1

2

4

8 16 32 64

 

Wiring 

Field wiring connections are shown in Figure 2. 

Run the wires through a hole in the backbox and connect them 
to the screw terminals as shown. 

Specifications 

 

Application 

Indoor use 

Power supply requirements 
 

External power supply 

 

Loop power 

 

Max line drop 

 
22 to 30 VDC 
20 volt pulsed analogue loop 
2V 

Current 
 

Standby 

 

Activated 

 

600 µA

 

700 µA

 

IP rating 

42 

Mounting 

Surface 

Construction 

Moulded ABS 

Colour 

White 

Dimensions (W × H × D) 

120 × 120 × 40 mm 

Gross weight  

310 g 

Initiating device circuits (IDC) 
 

Output current 

 

EOL resistor value 

 
1 A at 24 VDC per circuit 
2.2 K

 

Operating environment
 

Temperature 

 

Relative humidity 

 
−10 to +70°C 
20 to 95% noncondensing 

Storage temperature 

−10 to +70°C 

 