Chapter 3: Configuration and commissioning
90
ZP2-A Series Installation Manual
System update
Caution:
Updating the control panel firmware may delete the current installation
configuration data. Always back up your configuration data before updating the
control panel firmware.
Select System update to load control panel firmware updates provided by the
manufacturer. The update application may only be available in English.
To update the firmware:
1. Select Panel setup from the Main menu, and then select System update.
2. When prompted, open the control panel door and install a jumper onto JP4 on
the control panel PCB (see Figure 25 below), and then press F3 (Reboot).
The control panel reboots. Follow the on-screen instructions.
3. When prompted, insert the USB flash drive with the firmware update into
either of the USB type A connectors, and then press F3 (Continue).
Use only FAT32 file system USB flash drives with a maximum capacity of
32 GB.
4. When prompted, remove the USB flash drive as described in “Removing a
USB device” on page 57.
Figure 25: USB and JP4 connectors on the control panel PCB
1. USB connectors
2. JP4
Содержание ZP2-AF2-P
Страница 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Страница 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Страница 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Страница 153: ...Chapter 5 Technical specifications ZP2 A Series Installation Manual 147 Figure 29 Large cabinet dimensions and views...
Страница 154: ...Chapter 5 Technical specifications 148 ZP2 A Series Installation Manual Figure 30 Small cabinet dimensions and views...
Страница 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Страница 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Страница 176: ......