Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
69
Display
Description
Value
Firenet repeater map
01 to 32
ON/OFF
On for nodes 1 and 2, off for the rest
Firenet analogue repeater remote node ON/OFF
Default: Off
Firenet remote output control
ON/OFF
Default: Off
Firenet extinguishing global controls
ON/OFF
Default: Off
[1] The basic configuration setting can be replaced by a customized set of specific panels for
communication, called a Firenet map, and a set of panels to be repeated, called a Firenet
repeater map. If the configuration is changed by modifying either map, the value displayed for
Firenet number of nodes is Cu (indicating a custom network configuration).
Firenet global controls
Use this menu to configure commands (for example, reset, silence/re-sound
sounders, panel silence, cancelling delays) as local or global.
By default, this is On (controls are local but also sent to the network).
Note:
Local or global controls does not apply to disable/enable and test
commands. These are always local and sent to the control panels being
repeated. This feature provides more flexibility to configure disable/enable and
test of zones, sounders, fire routing, and fire protection.
Examples: If we disable zone 1 in control panel 1 and control panel 1 repeats
control panel 2, the zone 1 in control panel 2 will also be disabled (shared zone
completely disabled). If we disable zone 1 in control panel 1 but control panel 2 is
not repeated, zone 1 in panel 2 will not be disabled. (This allows disabling only
part of the shared zone).
Firenet loop class
Use this menu to configure the loop class: class A (ring) or class B (bus).
Class A is recommended to provide redundancy in communication path. Class B
can only be used for repeaters without control requirements.
By default, the basic settings use class B for basic repeater functionality.
Содержание ZP1-X3E Series
Страница 1: ...ZP1 X3E Series Installation Manual P N 501 419503 1 20 ISS 20JUL21...
Страница 86: ...Chapter 4 Maintenance 80 ZP1 X3E Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 X3E Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 X3E Series Installation Manual...
Страница 113: ......
Страница 114: ......