Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
37
Fire sounders delay
Use this menu to configure a fire sounders delay of up to 10 minutes. The default
setting is 00 (no delay). For more information on delay operation, see “Fire delay
operation” on page 38.
To configure a fire sounders delay:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Delay LED flashes fast to indicate that the sounder delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at the operator user level.
To enable a configured delay:
1. Exit the installer user level.
2. Enter the operator user level password.
3. Press the Sounder Delay button.
A steady Sounder Delay LED indicates that the delay is enabled.
Fire routing delay
Use this menu to configure a fire routing delay of up to 10 minutes. The default
setting is 00 (no delay). For more information on delay operation, see “Fire delay
operation” on page 38.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes fast to indicate that the fire routing delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Содержание ZP1-X3E Series
Страница 1: ...ZP1 X3E Series Installation Manual P N 501 419503 1 20 ISS 20JUL21...
Страница 86: ...Chapter 4 Maintenance 80 ZP1 X3E Series Installation Manual...
Страница 106: ...Appendix A Configuration presets 100 ZP1 X3E Series Installation Manual...
Страница 110: ...Appendix B Regulatory information 104 ZP1 X3E Series Installation Manual...
Страница 113: ......
Страница 114: ......