Conventional Wireless Dual IO Unit Installation Guide

General

The Ziton conventional wireless dual IO (CWIO) unit  is 

available under the following part number:

PART NO            VARIANT TYPE

ZCR452            Ziton conventional wireless dual IO unit

Introduction

The address of the unit is set when programming the 

device to the Ziton conventional wireless communicator 

(see programming manual for details). The installation 

must conform to BS5839:Part 1 (or applicable local 

codes). 

 The Ziton CWIO unit is suitable for indoor use only. 

Ensure that all Ziton CWIO units are sited in accordance 

with the survey and design details. 

© 2018 EMS Ltd. All rights reserved

1 / 4

4 / 4

TSD145 Iss3  17/10/2018  AJM

© 2018 EMS Ltd. All rights reserved

TSD145 Iss3  17/10/2018  AJM

Prepare the back box

Remove the four front plate retaining screws. Retain 

these for re-assembly when installation is complete. 

Remove the front plate.  

Drill required cable entry points for the CWIO units cable 

connections.  Recommended cable entry points are 

shown in Figure 2. 

SOUNDER

START/STOP

PANEL

SILENCE

SUPPLY

FAULT

FIRE ALARM

SUPPLY FAULT

EARTH FAULT

OUT OF SERVICE

SYSTEM FAULT

SOUNDER FAULT/

DISABLE/TEST

SOUNDER

DELAY

NETWORK FAULT

EXPANS. I/O FLT/DIS

DISABLE

TEST

1

2

4

3

POWER

FAULT

CONVENTIONAL WIRELESS COMMUNICATOR

ZCR452

WIRELESS ZONE INTERFACE MODULE

0.6m 

0.6m 

2m 

Figure 1

LOGON

ANTENNA

KEEP CABLES AWAY FROM THIS AREA

LR6 

AA

LR6 

AA

LR6 

AA

LR6 

AA

LR6 

AA

LR6 

AA

JP9

LED

ENABLE

F-SAFE

1

2

4

8

16

32

64

CLOSED

FAULT

EXPAN 1

3VDC SET RST

N/O COM N/C

OUTPUT 1

INPUT 1

REL

A

Y ON

IP-  IP+

INPUT 1

PO

WER

ADDRESS0=ON

C     NO      NC

TAMPER

Cable

entry points

Cable

entry points

Figure 2

Specification

Operating 
temperature

 

-10 to +70°C (ambient)

Operating 
temperature

 

0 to +35°C

Humidity

  

Up to 95% non-condensing

Supply

   

6x AA Alkaline (Panasonic LR6AD  

 

 

Powerline / Varta 4006 Industrial) 

IP rating 

 IP65

Output rating

 

2A @ 24V DC

Operating 
frequencies

 

868 MHz

Output transmitter
power

 

 

Variable 0-14 dBm

Dimensions

 

120mm (H) 240mm (W) 50mm (D)

 

Weight 

 0.60kg

Regulatory information

Year of
manufacture

 

See serial number label inside unit

Certification

Certification body

 

CPR certificate

 0359-CPR-00437

DOP

Approved to

 

EN54-18

  EN54-25

Application

 

Type A. Indoor use only

European Union

directives 

 

EMS declares that the radio  

 

  equipment 

type 

Ziton Conventional  

 

 

Wireless Dual IO Unit is in  

 

 

 

compliance with Directive  

 

 

 

2014/53/EU. The full text of the EU  

 

 

declaration of conformity is  

 

 

 

available at the following internet  

  address: 

 

  

                 

                                   

www.utcfssecurityproducts.eu/dop/ 

 

  2012/19/EU (WEEE directive):  

 

 

Products marked with this symbol  

 

 

cannot be disposed of as unsorted  

 

 

municipal waste in the European  

 

 

Union. For proper recycling, return  

 

 

this product to your local supplier  

 

 

upon purchase of equivalent new  

 

 

equipment, or dispose of it at    

 

 

designated collection points. For  

 

 

more information see  

 

  www.recyclethis.info

 

Fit the back box to the wall

Position the Ziton CWIO unit in the required location and 

mark the four fixing positions.  These are shown in Figure 

2. 

Using suitable screws and fixings attach the device 

securely to the wall.

2m 

0359

14

Mounting location guidelines

  

To ensure the optimum range performance of the CWIO 

unit is achieved, the following should be considered:

Ensure the CWIO and CWC are seperated by a minimum 

of 0.6m.

Ensure that the CWIO is not installed within 2m of  the 

Control Panel or any other wireless or electrical 

equipment. See Figure 1.

Fixing

position 1

Fixing

position 2

Fixing

position 3

Fixing

position 4

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ZCR452

Страница 1: ...T OUT OF SERVICE SYSTEM FAULT SOUNDER FAULT DISABLE TEST SOUNDER DELAY NETWORK FAULT EXPANS I O FLT DIS DISABLE TEST 1 2 4 3 POWER FAULT CONVENTIONAL WIRELESS COMMUNICATOR ZCR452 WIRELESS ZONE INTERFACE MODULE 0 6m 0 6m 2m Figure 1 LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA LR6 AA LR6 AA LR6 AA LR6 AA LR6 AA LR6 AA JP9 LED ENABLE F SAFE 1 2 4 8 16 32 64 CLOSED FAULT EXPAN 1 3VDC SET RST N O COM...

Страница 2: ...onnect the power jumper across the PIN header on the PCB The location of header is shown in Figure 3 The Ziton CWIO unit is powered by 6 x AA alkaline batteries These are supplied fitted Should batteries require replacement only use specified batteries whilst observing correct polarity as shown in Figure 3 Connection wiring Refer to the conventional wireless communicator programming guide for full...

Страница 3: ...s Each input has an associated red closed LED that will illuminate if the input is closed alarm condition Figure 4 Relay LED Input LED s LED enable button LOGON ANTENNA KEEP CABLES AWAY FROM THIS AREA LR6 AA LR6 AA LR6 AA LR6 AA LR6 AA LR6 AA JP9 LED ENABLE F SAFE 1 2 4 8 16 32 64 CLOSED FAULT EXPAN 1 3VDC SET RST N O COM N C OUTPUT 1 INPUT 1 RELAY ON IP IP INPUT 1 POWER ADDRESS0 ON C NO NC TAMPER...

Страница 4: ... consideration upon installation The CIC is only to be fitted to the CWIO when connection is required to a Conventional fire alarm control panel The CIC should only be connected to designated zone and sounder circuits Refer to the Ziton conventional wireless communicator engineers guide TSD146 for full programming information Figure 5 Connect the CIC to the CWIO Ensure the pins line up with the ZI...

Страница 5: ...an be wired in two different ways Fault notification can either be monitored via the Conventional FAPs Sounder or Zone Circuit Refer to the Ziton conventional wireless communicator engineers guide TSD146 for full details Figure 6 Fasten the CIC into the CWIO As shown in Figure 6 SOUNDERS FAULT ZONE RESET EOL L1 L2 EOL L1 L2 ALARM RES EOL L1 L2 ...

Страница 6: ...re 0 to 35 C Humidity Up to 95 non condensing Supply 6x AA Alkaline Panasonic LR6AD Powerline Varta 4006 Industrial IP rating IP65 Output rating 2A 24V DC Operating frequencies 868 MHz Output transmitter power Variable 0 14 dBm Dimensions 120mm H 240mm W 50mm D Weight 0 60kg ...

Страница 7: ...s in compliance with Directive 2014 53 EU The full text of the EU declaration of conformity is available at the following internet address www utcfssecurityproducts eu dop 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon purchase of equivalent new e...

Отзывы: