MU1001K
12370-0707-01
Seite
6 / 12
www.ziehl.de
6.3 Setting a predefined range
•
Power off the device
•
Press Button
[Set]
and keep pressed
•
Power on the device, and keep pressed the button [Set]
After 5s flashes the green LED, release button [Set]
Parameterization
„input type“ >> LED ON flashes 1x
•
Select with button [Set] the input type (displayed by LEDs 300 V / 10 V / mV)
•
Press button [Down]
Parameterization
„range“ >> LED ON flashes 2x
•
Select with button [Set] the range of
the input
Number of
LED
flashes
300 V
10 V
mV
1 x
0 - 20 V
0 - 10 V
0 - 60 mV
2 x
0 - 50 V
2 - 10 V
0 - 150 mV
3 x
0 - 100 V
-
10…10 V
0 ... 300 mV
4 x
0 - 200 V
-
60…60 mV
5 x
0 - 300 V
-
150…150 mV
-
300…300mV
•
Press button [Down]
Parameterization
„output“ >> LED Power flashes 4x
•
Select with button [Set] the output range
Number of
LED
flashes
10 V + mV
1 x
0 - 10V / 0 - 20mA
2 x
2 - 10V / 4 - 20mA
•
Press button [Down]
End of parameterization, LED ON lights permanently
Attention:
•
When no button is pressed during scaling for 120 s, the process is cancelled automatically. Entered
values will be discarded.
•
When scaling is started, all parameters are reset to default. Parameters cannot be checked after
scaling has been finished.
•
In normal operating mode the selected input is displayed with LED.