Commissioning 

 

Before switching on the mains voltage make sure that it matches the 
specification on the type plate. 

 

 

 

Attention! 
Observe chapter 15.8 Safe separation.
 

 

  After the supply voltage is switched on and when the thermistors are correctly connected the green 

LED „ON“ must light-up and the relay contacts 11, 14 must close. 

  The correct function of the device must be checked by resistance simulation at terminals T1, T2 

according to chapter 16 Proof testing of the safety functions. This check must be repeated after 
changes to the installation. 

 
 

11 

Operation instructions 

The device must be manually reset after a fault signal (red = alarm). For this purpose, the built-in reset 
button or an external button (remote reset terminals Y1, Y2) can be used. 
 
 

12 

Troubleshooting and remedies 

Relay contacts 11, 14 do not close: 

  Check the supply voltage Us at terminals A1, A2 (green LED lights-up). 

  Check the thermistors at terminals T1, T2. In case of a fault the red LED lights-up. 

  The resistance of the thermistor 

circuit must be 50 Ω < R < 1500 Ω. The terminal voltage T1, T2 must 

be < 2.5 VDC with connected thermistors and temperature below TNF. 

  Push 

the button “Reset”. A fault signal can be reset at R < 1.65 kΩ. The status LED changes from 

red to green. Alternatively, a reset can be done with closing an external contact at terminals Y1, Y2 
or with voltage recovery. 

 
Relay contacts 11, 14 do not open: 

  With no connection at terminals T1, T2 the device must indicate a fault and the relay contacts 11, 14 

must open. The terminal voltage T1, T2 must be approximately 8 VDC. 

 
In case of any other malfunctions, replace the device. Please add a description of the occurred 
malfunction when sending it back for repair. 
 
 

13 

Technical data 

Power supply (A1, A2) 

 

Power supply Us 

AC 220-240 V 

Voltage tolerance 

AC 0.

9 Us …1.1 Us 

Frequency 

50 / 60 Hz 

Frequency tolerance 

45 Hz … 65 Hz 

Power consumption 

< 2 W 

Voltage dip buffer time 

max. 20 ms 

PTC thermistor 

“TP” input (T1, T2) 

according to DIN VDE V 0898-1-401 

Number 

1 (

not allowed for explosive atmospheres

) 3 or 6 in series 

Rated response temperature TFS 

60 °C … 180 °C 

Response tolerance 

±6 °C 

Collective resistance cold thermistor 

≤ 1.65 kΩ 

Terminal voltage (thermistor) 

≤ 2.5 VDC at R ≤ 3.65 kΩ, ≤ 2 V at R ≤ 1.65 kΩ 

Open-circuit voltage 

≤ 9 VDC at R = 

 

Terminal current (thermistor) 

≤ 1 mA 

 

 

 

 

Содержание U-EK230E

Страница 1: ...l elements 2 3 Pre Adjustment 2 4 Application and brief description 3 5 Summary of features 3 6 Connecting diagram 3 7 Function diagram 4 8 Important notes 4 9 Installation 4 10 Commissioning 5 11 Operation instructions 5 12 Troubleshooting and remedies 5 13 Technical data 5 14 Dimensions Design V2 7 15 Safety instructions and references for putting into operation 7 16 Proof testing of the safety ...

Страница 2: ...e loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specifications 2 Display and control elements 1 Alarm red 2 ON green 3 Reset button blue 3 Pre Adjustment No settings have to be made The tripping temperature is determined solely by the response temperature of the connected thermistors Dep...

Страница 3: ...ure 5 Summary of features 1 thermistor circuit for 1 not allowed for explosive atmospheres 3 or 6 PTC thermistors TP Short circuit detection within the thermistor circuit Output relay with 1 change over contact co Operating status display A current monitors continuously the resistance of the thermistor circuit In cold state the resistance is 250 Ω per thermistor thermistor circuit 1 5 kΩ The devic...

Страница 4: ... Before commencing work on the system the power must be disconnected 9 Installation The applicant must observe safety rules and standards The device can be mounted on 35 mm rail according EN 60715 or with screws M4 Option Design V2 width 35 mm 2 M The device must be installed in an enclosure of class IP 5X or better Terminals maximum tightening torque 0 5 Nm When installing the device into the swi...

Страница 5: ...rcuit must be 50 Ω R 1500 Ω The terminal voltage T1 T2 must be 2 5 VDC with connected thermistors and temperature below TNF Push the button Reset A fault signal can be reset at R 1 65 kΩ The status LED changes from red to green Alternatively a reset can be done with closing an external contact at terminals Y1 Y2 or with voltage recovery Relay contacts 11 14 do not open With no connection at termin...

Страница 6: ... voltage AC 15 Ie 3 A Ue 250 V DC 13 Ie 2 A Ue 24 V DC 13 Ie 0 4 A Ue 120 V DC 13 Ie 0 2 A Ue 250 V UL electrical ratings 250 VAC 3 A general use C300 Test conditions IEC EN 60947 8 Rated impulse voltage 4000 V Overvoltage category III Pollution degree 2 Rated insulation voltage Ui 320 V Transformer EN 61558 2 6 VDE 0570 Proof Test Voltage 2500 VAC 50 Hz EMC Immunity EN 61000 6 2 EMC Emission N a ...

Страница 7: ... safety rules and regulations for prevention of accidents as well as the standard EN 60079 14 VDE 0165 1 All work for the connection for putting into operation and maintenance is to be implemented by qualified responsible technical personnel Inappropriate behaviour can cause heavy personal damage and damages to property The response of the device must directly switch off the motor also when used t...

Страница 8: ...3D EPL Gc Dc Zone 2 Zone 22 Zone 1 Zone 21 Zone 0 Zone 20 The device thus is suitable as safety device for Equipment Under Control EUC with HFT 0 category 3 in Zone 1 and Zone 21 The combined equipment shall comply with the relevant standards EN 60079 0 according to the categories to match 15 7 Wiring The lines of the thermistor circuit must be routed as separate control lines as far as to the mot...

Страница 9: ...set When the device triggers a stop instruction it must be maintained until the manual reset mechanism is operated and safe conditions for a renewed start are given The manual reset must be only possible if all safety functions and protection devices are effective The stop instruction remains until a reset is made by pressing the push button Reset A start up is only possible if no case of failure ...

Страница 10: ...opean Union Equipment affected by this is indicated by the corresponding symbol You can find further information on this on our website 19 Manufacturer reference Our products are manufactured in accordance with the relevant international regulations If you have any questions concerning the use of our products or plan special uses please contact ZIEHL ABEGG SE ZIEHL ABEGG UK Ltd Heinz Ziehl Straße ...

Страница 11: ...21 EU Declaration of conformity ...

Страница 12: ...22 UKCA Declaration of Conformity ...

Отзывы: