U-EK230E
L-BAL-E185-GB 2023/10 Index 005
11660-0711-03
2/12
1
General Notes
Compliance with the following instructions is mandatory to ensure the functionality and safety of the
product. If the following instructions given especially but not limited for general safety, transport,
storage, mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal /
recycling are not observed, the product may not operate safely and may cause a hazard to the life and
limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material
defect liability rights and to the liability of the buyer for the product that has become unsafe due to the
deviation from the specifications.
2
Display- and control elements
1. Alarm (red)
2. ON (green)
3. Reset button (blue)
3
Pre-Adjustment
No settings have to be made. The tripping temperature is determined solely by the response
temperature of the connected thermistors.
Depending on the number of thermistors the following tripping temperatures and reset temperatures
arise related to TNF (detector operating temperature):
Only 3 or 6 thermistors in series are allowed for usage in explosive atmospheres.
Tripping temperature
Reset temperature
1 thermistor
TNF + 15 K
TNF + 5 K
3 thermistors in series
TNF + 5 K
TNF
– 5 K
6 thermistors in series
TNF
TNF
– 20 K