Pre-installation preparation
MXK Hardware Installation Guide
29
Power supply safety information
Install an equipment grounding conductor not smaller in size than the
ungrounded branch-circuit supply conductors as part of the circuit that
supplies the product or system. Bare, covered, or insulated grounding
conductors are acceptable. Individually covered or insulated equipment
grounding conductors should have a continuous outer finish that is either
green, or green with one or more yellow stripes. Connect the
equipment-grounding conductor to ground at the service equipment.
Installation precautions
Avoid creating a hazardous condition by maintaining even weight distribution
within the chassis.
WARNING!
Two people are required to lift the MXK 819 or
MXK 823 systems because they weigh too much for one person to
lift. Do not attempt to lift the system chassis without assistance or
personal injury can result.
Maximum operating temperature should not exceed 55
0
C (131
0
F). The
temperature of the rack environment may be greater than ambient room
temperature when the system is installed in a closed or multiunit rack
assembly. Observe the maximum recommended operating temperature as
indicated here.
Do not block system air vents; this will deprive the system of the airflow
required for proper cooling. Sufficient clearance must exist on all sides of the
rack to permit equipment access.
Zhone recommends using cabling ducts for cable routing in rack mounts.
To facilitate proper cooling, cover unpopulated slots with a blank front panel.
All slots must have a card or a blank panel installed at all times for EMC,
safety and cooling requirements.
The system ships with mounting brackets. To avoid overloading the mounting
brackets, and damaging the system, do not use the MXK chassis to support
other equipment after it is mounted in the rack.
Connect the system to the power supply circuit as described in this document.
Do not overload the system or power supply circuit.
Ensure that proper system grounding is performed and maintained. Use power
supply connections for grounding instead of branch circuitry (such as power
strips).
Содержание MXK
Страница 1: ...MXK Hardware Installation Guide For software version 2 1 July 2010 Document Part Number 830 01734 10 ...
Страница 10: ...About This Guide 10 MXK Hardware Installation Guide ...
Страница 54: ...Install the MXK 54 MXK Hardware Installation Guide ...
Страница 74: ...MXK Hardware Maintenance 74 MXK Hardware Installation Guide ...
Страница 78: ...Index 78 MALC Hardware Installation Guide ...