Cannot Black start
Battery switch is not properly
closed:
Battery fuse is not open:
Or Battery low:
Battery quantity set wrong;
Power breaker in the rear panel not
switch ON.
Close the battery switch:
Change the fuse:
Recharge the battery:
Power ON the UPS with AC to set the battery
quantity &quantity;
Switch on the power breaker.
10
Buzzer beeps
continuously and
LCD indicates
1,3,5,9,15, etc. fault
codes
UPS is out of order
Consult with ZIGOR for repair
Table 6-1 Trouble shooting